Loading...
OR 2007-1171 Adopting the International Mechanical Code AN ORDINANCE OF THE CITY OF COPPELL, TEXAS ORDINANCE NO.2007-1171 AN ORDINANCE OF THE CITY OF COPPELL, TEXAS AMENDING THE CODE OF ORDINANCES BY AMENDING CHAPTER 15 ARTICLE 15-3 TO ADOPT THE INTERNATIONAL MECHANICAL CODE, 2006 EDITION, AS THE CITY OF COPPELL MECHANICAL CODE; PROVIDING AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A REPEALING CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING A PENALTY FOR VIOLATION OF THIS ORDINANCE NOT TO EXCEED THE SUM OF FIVE HUNDRED DOLLARS ($500.00) FOR EACH OFFENSE; EXCEPT HOWEVER, WHERE A DIFFERENT PENALTY HAS BEEN ESTABLISHED BY STATE LAW FOR SUCH OFFENSE WHICH IS A VIOLATION OF ANY PROVISION OF LAW THAT GOVERNS FIRE SAFETY, ZONING, OR PUBLIC HEALTH AND SANITATION, INCLUDING DUMPING OF REFUSE, THE PENALTY SHALL BE A FINE NOT TO EXCEED THE SUM OF TWO THOUSAND DOLLARS ($2,000.00) FOR EACH OFFENSE; AND PROVIDING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COPPELL, TEXAS: SECTION 1. That the City of Coppell Code of Ordinances be, and the same is, hereby amended by amending Chapter 15, Article 15-3, in part to adopt the International Mechanical Code, 2006 Edition, with amendments to read as follows: “ARTICLE 15-3. MECHANICAL CODE Sec. 15-3. Mechanical Code - Adopted. There is hereby adopted the International Mechanical Code, 2006 Edition, and made a part hereof for all purposes, the same as if fully copied in full herein, with the exception of such sections hereof, which are hereafter deleted, modified or amended. Sec. 15-3-2. Amendments. The following sections of the International Mechanical Code, 2006 Edition, are hereby amended to read as follows: 1. Amend Section 102.8, to read as follows: 102.8 Referenced Codes and Standards. The codes and standards referenced herein shall be those that are listed Chapter 15, and such codes when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the 2005 National Electrical Code as adopted. 2. Amend Section 302.3, to read as follows: 302.3 Cutting, Notching and Boring in Wood Framing. When permitted by the International Building Code, the cutting, notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3. 3.Section 304.6 shall be deleted. 4. Amend Section 304.9, to read as follows: 304.9 Clearances from Grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade a minimum of 3 inches (76 mm) or shall be suspended a minimum of 6 inches (152 mm) above adjoining grade. 5. Add Section 304.11, to read as follows: 304.11 Minimum Burial Depth. Underground fuel piping systems shall be installed a minimum depth of 18 inches (458 mm) below grade. 6. Amend Section 306.3, to read as follows: 306.3 Appliances in Attics. Attics containing appliances requiring access shall be provided…(bulk of section unchanged)…side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm) or larger where such dimensions are not large enough to allow removal of the largest appliance. As a minimum, access to the attic space of residential uses shall be provided by one of the following: 1.A permanent stair. 2.A pull-down stair. 3.An access door from an upper floor level. Exception: The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening. 7. Amend Section 306.3.1, with the following additional sentence: 306.3.1 Low Voltage Wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 8. Amend Section 306.5, to read as follows: 306.5. Equipment and Appliances on Roof and Elevated Structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (2438 mm), such access shall be provided by a permanent means of access. Permanent exterior ladders providing roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliances level service space. Such access shall…(bulk of section to read the same)…on roofs having a slope greater than 4 units vertical in 12 units horizontal. A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. Low voltage wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 9. Amend Section 306.6, to add a second paragraph to read as follows: A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. Low voltage wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 10. Add Section 306.6.1, to read as follows: 306.6.1 Catwalk. On roofs having slopes greater than 4 units vertical in 12 units horizontal, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to the working platform at the appliance. 11.Add Sections 306.7 and 306.7.1, to read as follows: 306.7 Water Heaters Above Ground or Floor. When the mezzanine or platform in which a water heater is installed is more than 8 feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle shall be provided in accordance with the Section 306.3.1. 12. Modify Section 307.2.1, to read as follows: 307.2.1 Condensate Disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan to an approved place of disposal. Condensate shall not discharge in a publicly exposed area such as a street, alley, sidewalk or other area so as to cause a nuisance. 13. Add second paragraph to Section 307.2.2, as follows: Condensate Waste Pipes from air-cooling coils may be sized in accordance with equipment capacity as follows: Equipment capacity in tons of refrigeration: Minimum condensate pipe I.D.: Up to 20 tons ¾ inch Over 20 to 40 tons 1 inch Over 40 to 90 tons 1 ¼ inch Over 90 to 125 tons 1 ½ inch Over 125 to 250 tons 2 inch The size of condensate waste pipes may be for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1/8 inch per foot slope, with the pipe running three-quarters full. 14. Add item #4 to Section 307.2.3, to read as follows: 4. Discharge, as noted, shall be to a conspicuous point of disposal to alert occupants in the event of a stoppage of the drain. However, the conspicuous point shall not create a hazard, such as dripping over a walking surface or other areas so as to create a nuisance. 15. Add a second exception to Section 401.5, to read as follows: 1. (existing to remain unchanged) 2.Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present. 16. Add a second exception to Section 403.2, to read as follows: 1. (existing to remain unchanged) 2. Where the design professional demonstrates that an engineered ventilation system is designed in accordance with ASHRAE 62, the minimum required rate of outdoor air shall be permitted to be as specified in such engineered system design. 17. Add item #4 to Section 403.2.1, to read as follows: 4. Toilet rooms within private dwellings that contain only a water closet, lavatory or combination thereof, may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. 18. Amend footnote “g” of Table 403.3, to read as follows: g. Transfer air permitted in accordance with Section 403.2.2. Toilet rooms within private dwellings that contain only a water closet, lavatory or combination thereof, may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. 19. Section 501.2; add a second exception, to read as follows: 1. (existing to remain unchanged) 2. Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present. 20. Amend Section 504.6, to read as follows: 504.6Size of Duct. The size of the duct shall not be reduced along its developed length or at the point of termination. 21. Amend Section 506.3.11, to read as follows: 506.3.11 Duct enclosure. A grease duct serving a Type I hood that penetrates a ceiling, wall or floor shall be enclosed…(bulk of the paragraph unchanged)…through the use of weather protected openings. The enclosure shall be separated from the duct by a minimum of 3 inches (76 mm) and a maximum of 12 inches (305 mm) and shall serve a single grease duct system. 22. Add a second exception to Section 510.7, to read as follows: 1. (existing exception unchanged) 2. Ducts where the largest cross-sectional area is less than 10 inches (254 mm). 23. Amend Section 607.5.1, to read as follows: 607.5.1 Fire walls. Ducts and transfer openings permitted in fire walls in accordance with Section 705.11 of the International Building Code shall be protected with approved fire dampers installed in accordance with their listing. For hazardous exhaust systems, see Section 510.1 through 510.9 of the International Mechanical Code.” SECTION 2. If any section, subsection, paragraph, sentence, phrase or work in this ordinance, or application thereof to any person or circumstance is held invalid by any court of competent jurisdiction, such holding shall not affect the validity of the remaining portions of this ordinance, and the City Council of the City of Coppell, Texas hereby declares it would have enacted such remaining portions despite any such invalidity. SECTION 3. That the repeal of any ordinance or any portion thereof by the preceding sections shall not affect or impair any act done or right vested or accrued or any proceeding, suit or prosecution had or commenced in any cause before such repeal shall take effect; but every such act done, or right vested or accrued, or proceedings, suit or prosecution had or commenced shall remain in full force and effect to all intents or purposes as if such ordinance or part thereof so repealed shall remain in force. SECTION 4. That any person, firm or corporation violating any of the provisions of this ordinance or the Code of Ordinances as amended hereby, shall be guilty of a misdemeanor and upon conviction in the Municipal Court of the City ofCoppell, Texas, shall be subject to a fine not to exceed the sum of Five Hundred Dollars ($500.00) for each offense, except where a different penalty has been established by State law for such offense, the penalty shall be that fixed by State law, and for any offense which is a violation of any provision of law that governs fire safety, zoning or public health and sanitation, including dumping of refuse, the penalty shall be fine not to exceed the sum of Two Thousand Dollars ($2,000.00) for each offense; and each and every day such offense is continued shall constitute a new and separate offense. SECTION 5. That this ordinance shall become effective immediately from and after its passage and the publication of the caption, as the law and charter in such cases provide. PASSED by the City Council of Coppell, Texas, this the Z4~ , 2007. ATTEST: