Loading...
OR 2002- 991 Adopts 2002 International Mechanical CodeAN ORDINANCE OF THE CITY OF COPPELL, TEXAS ORDINANCE NO. 2002-991 AN ORDINANCE OF THE CITY OF COPPELL, TEXAS AMENDING THE CODE OF ORDINANCES BY AMENDING CHAPTER 15, ARTICLE 15-3 TO PROVIDE FOR THE ADOPTION OF THE INTERNATIONAL MECHANICAL CODE, 2000 EDITION, AS THE CITY OF COPPELL MECHANICAL CODE; PROVIDING AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE, 2000 EDITION; PROVIDING A SEVERABILITY CLAUSE; PROVIDING A REPEALING CLAUSE; PROVIDING A SAVINGS CLAUSE; PROVIDING A PENALTY FOR VIOLATION OF THIS ORDINANCE NOT TO EXCEED THE SUM OF TWO THOUSAND DOLLARS ($2,000.00) FOR EACH OFFENSE; AND PROVIDING AN EFFECTIVE DATE. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COPPELL, TEXAS: SECTION 1. That the Code of Ordinances of the City of Coppell, Texas be, and the same is, hereby amended by amending Chapter 15, Article 15-3 to adopt the International Mechanical Code, 2000 Edition, and the amendments thereto, which shall read as follows: "ARTICLE 15-3. MECHANICAL CODE Sec. 15-3-1. Mechanical code adopted. There is hereby adopted the International Mechanical Code, 2000 Edition, and made a part hereof for all purposes, the same as if fully copied in full herein, with the exception of such sections hereof, which are hereafter deleted, modified or amended. Sec. 15-3-2. Amendments. The following sections of the International Mechanical Code, 2000 Edition, are hereby amended to read as follows: 1. Amend Section 102.8 shall be amended to reference other City Codes, which shall read as follows: 102.8 Referenced codes and standards ...... Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as 1 46755 well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the 1999 National Electrical Code as adopted and amended. 2. Amend Section 302.3 by deleting and adding the following: 302.3 Cutting, notching and boring in wood framing. When permitted by the International Building Code, 2000 Edition, as adopted and amended, the cutting, notching and boring of wood framing members shall comply with Sections 302.3.1 through 302.3. 3. Section 304.5 shall be deleted in its entirety. 4. Section 304.8 shall be amended to read as follows: 304.8 Clearances from grade ...... adjoining grades a minimum of 3 inches (76 mm) or shall be suspended a minimum of 6 inches (152 mm) above adjoining grade. 5. Section 304 shall be amended by adding 304.11, which shall read as follows: 304.11 Minimum burial depth. Underground fuel piping systems shall be installed a minimum depth of 18 inches (458 mm) below grade. 6. Amend Section 306.3 and 306.3.1 to read as follows: Section 306.3 Appliances in attics. Attics containing appliances requiring access shall be provided ..... side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm) or larger where such dimensions are not large enough to allow removal of the largest appliance. As a minimum, access to the attic space of residential uses shall be provided by one of the following: A permanent stair. A pull-down stair. An access door from an upper floor level. Exception: The passageway and level service space are not required where the appliance is capable of being serviced and removed through the required opening. 306.3.1 Electrical requirements ...... Low voltage wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 7. Amend Section 306.5 by deleting and replacing with new provisions, which shall read as follows: 46755 Section 306.5. Equipment and appliances on roof and elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (2438 mm), such access shall be provided by a permanent means of access. Permanent exterior ladders providing roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the equipment and appliances level service space. Such access shall ..... on roofs having a slope greater than 4 units vertical in 12 units horizontal. A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. Low voltage wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 8. Amend Section 306.6 by adding a second paragraph and adding subsection 306.6.1 to read as follows: 306.6 Sloped roofs ...... A receptacle outlet shall be provided at or near the equipment and appliance location in accordance with the Electrical Code. Low voltage wiring of 50 volts or less shall be installed in a manner to prevent physical damage. 306.6.1 Catwalk. On roofs having slopes greater than 4 units vertical in 12 units horizontal, a catwalk at least 16 inches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to the working platform at the appliance. 9. Add Section 306.7 and 306.7.1 to provide for water heaters above ground or floor, which shall read as follows: 306.7 Water heaters above ground or floor. When the mezzanine or platform in which a water heater is installed is more than 8 feet (2438 mm) above the ground or floor level, it shall be made accessible by a stairway or permanent ladder fastened to the building. 306.7.1 Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtainable from the main level, lighting and a receptacle shall be provided in accordance with the Section 306.3.1. 10. Amend Sections 307.2.1,307.2.2 and 307.2.3 to read as follows: 307.2.1 Condensate disposal ...... Condensate shall not discharge in a publicly exposed area such as a street, alley, sidewalk or other area so as to cause a nuisance. 46755 307.2.2 Drain pipe materials and sizes ...... Condensate waste pipes from air-cooling coils may be sized in accordance with equipment capacity as follows: Equipment capacity in tons of refrigeration condensate pipe I.D. Minimum Up to 20 tons Over 20 to 40 tons Over 40 to 90 tons Over 90 to 125 tons Over 125 to 250 tons 3¼ inch 1 inch 1% inch 1 lA inch 2 inch The size of condensate waste pipes may be for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1/8 inch per foot slope, with the pipe running three-quarters full. 307.2.3 Auxiliary and secondary drain systems ..... 2. 3. 4. Discharge, as noted, shall be to a conspicuous point of disposal to alert occupants in the event of a stoppage of the drain. However, the conspicuous point shall not create a hazard, such as dripping over a walking surface or other areas so as to create a nuisance. 11. Amend Section 401.5 to provide an additional exception, which shall read as follows: Exceptions: Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present. 12. Amend Section 403.2 by providing an exception, and subsection 403.2.1 by adding item 4, which shall read as follows: 403.2 Outdoor air required ...... Exception: Where the design professional demonstrates that an engineered ventilation system is designed in accordance with 46755 ASHRAE 62, the minimum required rate of outdoor air shall be permitted to be as specified in such engineered system design. 403.2.1 Recirculation of air ...... Toilet rooms within private dwellings that contain only a water closet, lavatory or combination thereof, may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. 13. Amend Table 403.3 by amending footnote g to read as follows: Transfer air permitted in accordance with Section 403.2.2. Toilet rooms within private dwellings that contain only a water closet, lavatory or combination thereof, may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air. 14. Amend Section 501.3 by providing an additional exception, which shall read as follows: Exceptions: Toilet room exhaust ducts may terminate in a warehouse or shop area when infiltration of outside air is present. 15. Section 504.6 and subsection 504.6.1 shall be amended to read as follows: 504.6 Domestic clothes dryer ducts ...... The size of the duct shall not be reduced along its developed length or at the point of termination. 504.6.1. Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more than two bends. When extra bends are installed, the maximum length of the duct shall be reduced 2.5 feet (762 mm) for each 45 degree (0.79 rad) bend and 5 feet (1524 mm) for each 90 degree (1.6 rad) bend that occur after the first two bends, measured in the direction of air flow. 16. Amend Subsection 506.3.11 by reducing the minimum number of inches separating the enclosure from the duct, which shall read as follows: 46755 506.3.11 Duct enclosure ...... The enclosure shall be separated from the duct by a minimum of 3 inches (76 mm) and a maximum of 12 inches (305 mm) and shall serve a single grease duct system. 17. Amend Section 510.7 by adding an additional exception to read as follows: Exceptions: Ducts where the largest cross-sectional area is less than 10 inches (254 mm). 18. Amend Section 604.1 to provide for Table 604.1 to read as follows: 604.1 General ...... Sections 604.2 through 604.11 and Table 604.1, and the International Energy Conservation Code, as adopted and amended. Should there be any conflicts between this section and the energy code, the energy code shall take precedence. Table 604.1 - Insulation of Ducts Insulation Types Duct Location Mechanically Heating Zone~ Insulation Types Cooled Heating Only I A and W On roof on exterior of building C, Va and W II B and W III C and W I A Attics, garages and crawl spaces A and Va II A III B I A In walls~, within floor-ceiling spaces~ A and Va II A III B Within the conditioned space or in None required None required Basements; return ducts in air plenums Cement slab or within ground None required None required Note: Where ducts are used for both heating and cooling, the minimum insulation shall be as required for the most restrictive condition. ~Heating Degree Days: Zone I below 4,500 D.D. Zone II 4,501 to 8,000 D.D. Zone III over 8,000 D.D. aVapor retarders shall be installed on supply ducts in spaces vented to the outside in geographic areas where the summer dew point temperature based on the 2-1/2 percent column of dry-bulb and mean coincident we-bulb temperature exceeds 60° F. (15.4° C). ~Insulation may be omitted on that portion of a duct which is located within a wall- or a floor-ceiling space where: ~'~ Both sides of the space are exposed to conditioned air. ~.a The space is not ventilated. ~'~ The space is not used as a return plenum. 6 46755 ~.4 The space is not exposed to unconditioned air. Ceilings which form plenums need not be insulated. INSULATION TYPE S*: A - A material with an installed conductance of 0.48 [2.72 W/(m*K)] or the equivalent thermal resistance of 2.1 [0.367 (m*K)/W]. Example of materials capable of meeting the above requirements: 1-inch (25 mm), 0.60 lb./cu.ft. (9.6 kg/m~) mineral fiber, rock, slag or glass blankets. ½-inch (13 mm), 1.5 to 3 lb./cu, ft. (24 to 48 kg/m~) mineral fiber blanket duct liner. ½-inch (13 mm), 3 to 10-lb./cu. ft. (48 to 160 kg/m~) mineral fiber board. B - A material with an installed conductance of 0.24 [1.36 W/(m*K)] or the equivalent thermal resistance of 4.2 [0.735 (m*K)/W]. Example of materials capable of meeting the above requirements: 2-inch (51 mm), 0.60 lb./cu, ft. (9.6 kg/m~) mineral fiber blankets. 1-inch (25 mm), 1.5 to 3 lb./cu, ft. (24 to 48 kg/m~) mineral fiber blanket duct liner. 1-inch (25 mm), 3 to 10 lb./cu, ft. (48 to 160 kg/m~) mineral fiberboard. C - A material with an installed conductance of 0.16 [0.9 W/(m*K)] or the equivalent thermal resistance of 6.3 [1.1 (m*K)/W]. Example of materials capable of meeting the above requirements: 3-inch (76 mm), 0.60 lb./cu, ft. (9.6 kg/m~) mineral fiber blankets. 1-1/2 inch (38 mm), 1.5 to 3 lb./cu, ft. (24 to 48 kg/m~) mineral fiber blanket duct liner. 1-1/2 inch (38 mm), 3 to 10 lb./cu, ft. (48 to 160 kg/m~ mineral fiberboard. V - Vapor Retarders: Material with a perm rating not exceeding 0.05 perm (29 ng/Pa*s*m:]. All joints to be sealed. W - Approved weatherproof barrier. 4The example of materials listed under each type is not meant to limit other available thickness and density combinations with the equivalent installed conductance or resistance based on the insulation only. 19. Section 604.11 by deleting the current section and adding the following: 604.11 Vapor retarders. Where ducts used for cooling are externally insulated, the insulation shall be covered with a vapor retarder in accordance with Table 604.1 or aluminum foil having a minimum thickness of 2 mils (0.051 mm). Insulation having a permeance of 0.05 perms (2.87 ng/(Pa.s..m2)), or less shall not be required to be covered. All joints and seams shall be sealed to maintain the continuity of the vapor retarder. 20. Amend Subsection 607.2.2 by deleting the same and replacing with the following: 607.2.2 Hazardous exhaust ducts. Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through ducts and plenums. Penetration of structural elements shall conform to this section and the International Building Code except that fire dampers are not required at the penetration of fire- resistant-rated assemblies. 46755 21 Amend Subsection 607.5.1 to read as follows: 607.5.1 Firewalls ...... Hazardous exhaust ducts shall not penetrate firewalls. 22. Amend Subsection 607.6.1 by deleting the same and adding the following: 607.6.1 Through penetrations. In occupancies other than Groups I-2 and I-3, penetrations by an air duct through a fire-resistive-rated floor/ceiling assembly that connects not more than two stories are permitted without shaft enclosure protection where a fire damper is installed at the floor line. 23. Chapter 14, Solar Systems, shall be deleted in its entirety. SECTION 2. If any section, subsection, paragraph, sentence, phrase or word in this ordinance, or application thereof to any person or circumstances is held invalid by any court of competent jurisdiction, such holding shall not affect the validity of the remaining portions of this ordinance, and the City Council of the City of Coppell, Texas hereby declares it would have enacted such remaining portions despite any such invalidity. SECTION 3. That the repeal of any ordinance or any portion thereof by the preceding sections shall not affect or impair any act done or right vested or accrued or any proceeding, suit or prosecution had or commenced in any cause before such repeal shall take effect, but every such act done, or right vested or accrued, or proceedings, suit or prosecution had or commenced shall remain in full force and effect to all intents or purposes as if such ordinance or part thereof so repealed shall remain in force. SECTION 4. That any person, firm or corporation violating any of the provisions of this ordinance or the Code of Ordinances as amended hereby, shall be guilty of a misdemeanor and upon conviction in the Municipal Court of the City of Coppell shall be subject to a fine not to exceed Two Thousand Dollars ($2,000) for each 8 46755 offense and each and every day such offense is continued shall constitute a new and separate offense. SECTION 5. That this ordinance shall become effective immediately from and after its passage and the publication of the caption, as the law and charter is such cases provide. DULY PASSED by the City Council of Coppell, Texas, this the 23rd day of April, 2002. APPROVED: CANDY SHEEHAN, MAYOR ATTEST: LIBBY BALL, CITY SECRETARY APPRO~TO ORM: ROBERT E. HAGER, CITY ATTORNEY (P,J~I/cdb 4/2/02) 9 46755