OR 2002- 992 Adopts the 2000 International Plumbing CodeAN ORDINANCE OF THE CITY OF COPPELL, TEXAS
ORDINANCE NO. 2002-992
AN ORDINANCE OF THE CITY OF COPPELL, TEXAS
AMENDING THE CODE OF ORDINANCES BY AMENDING
CHAPTER 15 BY DELETING AND REPEALING ARTICLE 15-4,
UNIFORM PLUMBING CODE, SECTIONS 15-4-1 THROUGH 15-
4-4 AND BY ADDING A NEW ARTICLE 15-4 TO ADOPT THE OF
THE INTERNATIONAL PLUMBING CODE, 2000 EDITION, AS
THE CITY OF COPPELL PLUMBING CODE; PROVIDING
AMENDMENTS TO THE INTERNATIONAL PLUMBING CODE
2000 EDITION; PROVIDING A SEVERABILITY CLAUSE;
PROVIDING A REPEALING CLAUSE; PROVIDING A SAVINGS
CLAUSE; PROVIDING A PENALTY FOR VIOLATION OF THIS
ORDINANCE NOT TO EXCEED THE SUM OF FIVE HUNDRED
DOLLARS ($500.00) FOR EACH OFFENSE; EXCEPT
HOWEVER, WHERE A DIFFERENT PENALTY HAS BEEN
ESTABLISHED BY STATE LAW FOR SUCH OFFENSE WHICH
IS A VIOLATION OF ANY PROVISION OF LAW THAT
GOVERNS FIRE SAFETY, ZONING, OR PUBLIC HEALTH AND
SANITATION, INCLUDING DUMPING OF REFUSE, THE
PENALTY SHALL BE A FINE NOT TO EXCEED THE SUM OF
TWO THOUSAND DOLLARS ($2,000.00) FOR EACH OFFENSE;
AND PROVIDING AN EFFECTIVE DATE.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF COPPELL,
TEXAS:
SECTION 1. That the Code of Ordinances of the City of Coppell, Texas be and
the same is hereby amended by amending Chapter 15, Article 15-4 in part to adopt the
International Plumbing Code, 2000 Edition, with amendments to read as follows:
"ARTICLE 15-4. PLUMBING CODE
Sec. 15-4-1. Plumbing Code Adopted
There is hereby adopted the International Plumbing Code, 2000
Edition, and made a part hereof for all purposes, the same as if fully
copied in full herein, with the exception of such sections hereof, which are
hereafter deleted, modified or amended.
PAGE 1
46725(Rev.)
Sec. 15-4-2. Amendments
The following sections of the International Plumbing Code, 2000
Edition, are hereby amended to read as follows:
1. Table of Contents, Chapter 7, Section 714; shall to read as follows:
"S ection 714 Engineered Drainage Design ........................... 60"
2. Section 102.8 shall be amended to read as follows:
"102.8 Referenced codes and standards. The codes and standards
referenced in this code shall be those that are listed in Chapter 13 and
such codes, when specifically adopted, and standards shall be
considered part of the requirements of this code to the prescribed
extent of each such reference. Whenever amendments have been
adopted to the referenced codes and standards, each reference to said
code and standard shall be considered to reference the amendments as
well. Any reference to NFPA 70 or the ICC Electrical Code shall
mean the 1999 National Electrical Code, as adopted and amended."
3. Section 305.6.1; shall be amended to read as follows:
"305.6.1 Sewer depth ...... Building sewers shall be a minimum of
12 inches (304 mm) below grade."
4. Section 305.9 shall be amended to read as follows:
"305.9 Protection of components of plumbing system. Components
of a plumbing system installed within three (3') feet along alleyways,
driveways, parking garages or other locations in a manner in which
they would be exposed to damage shall be recessed into the wall or
otherwise protected in an approved manner."
5. Section 310.4 Water closet compartment shall be deleted in its
entirety.
6. Sections 312.9.1 and 312.9.2 shall be amended to read as follows:
"312.9.1 Inspections ...... In the absence of local provisions, the
owner is responsible to insure that testing is being performed.
312.9.2 Testing ...... The testing procedure shall be performed in
accordance with applicable local provisions. In the absence of local
provisions, the owner is responsible to ensure that testing is done in
accordance with one of the following standards: ..... "
PAGE 2
46725(Rev.)
7. Section 314.2.1; shall be amended to read as follows:
"314.2.1 Condensate disposal ...... Condensate shall not discharge
in a publicly exposed area such as onto a street, alley or sidewalk or
other areas so as to cause a public nuisance."
8. Section 314.2.2; add a second paragraph to read as follows:
"314.2.2 Drain pipe materials and sizes ......
Condensate waste pipes from air-cooling coils may be sized in
accordance with equipment capacity as follows:
Equipment capacity in tons of refrigeration Minimum condensate pipe I.D.
Up to 20 tons
Over 20 to 40 tons
Over 40 to 90 tons
Over 90 to 125 tons
Over 125 to 250 tons
3¼ inch
1 inch
14¼ inch
1 lA inch
2 inch
The size of condensate waste pipes may be for one unit or a
combination of units, or as recommended by the manufacturer. The
capacity of waste pipes assumes a 1/8 inch-per-foot slope, with the
pipe running three-quarters full."
9. Section 314.2.3 shall be amended by adding item #4, which shall read
as follows:
"314.2.3 Auxiliary and secondary drain systems ......
Discharge, as noted, shall be to a conspicuous point of disposal to
alert occupants in the event of a stoppage in the drain. However,
the conspicuous point shall not create a hazard such as dripping
over a walking surface or other area so as to create a nuisance."
10. Section 401.1 shall be amended by adding a sentence to read as
follows:
"Scope ...... The provisions of this Chapter are meant to work in
coordination with the provisions of the Building Code. Should any
conflicts arise between the two chapters, the Building Official shall
determine which provision applies."
11. Section 403.1 shall be amended and a new section 403.1.2 added
which shall read as follows:
PAGE 3
46725(Rev.)
"403.1. Minimum number of fixtures. Plumbing fixtures shall be
provided for the type of occupancy and in the minimum number as
follows:
1. Assembly occupancies: At least one drinking fountain shall be
provided at each floor level in an approved location.
Exception: A drinking fountain need not be provided in a drinking
or dining establishment.
Groups A, B, F, H, I, M and S occupancies: Buildings or portions
thereof where persons are employed shall be provided with at least
one water closet for each sex except as provided for in Section
403.2.
3. Group E occupancies: Shall be provided with fixtures as shown in
Table 403.1.
4. Group R occupancies: Shall be provided with fixtures as shown in
Table 403.1.
It is recommended, but not required that the minimum number of
fixtures provided also comply with the number shown in Table 403.1.
Types of occupancies not shown in Table 403.1 shall be considered
individually by the Building Official. The number of occupants shall
be determined by the International Building Code, 2000 Edition.
Occupancy classification shall be determined in accordance with the
International Building Code.
403.1.2 Finish material. Finish materials shall comply with Section
1209 of the International Building Code, 2000 Edition."
12. Section 404.2 shall be amended to read as follows:
"404.2. Unisex toilet and bathing rooms. In assembly and
mercantile occupancies, an accessible unisex toilet room shall be
provided where an aggregate of six or more male or female water
closets are provided ...... "
13. Section 405.6 Plumbing in mental health centers shall be deleted in its
entirety
14. Section 409.2 shall be amended to read as follows:
"409.2 Water connection.
dishwashing ..... "
The water supply to a commercial
PAGE 4
46725(Rev.)
15. Section 410.1; shall be amended by deleting the requirement for water
served in restaurants or bottled water coolers, and by providing an
exemption, which shall read as follows:
"410.1 Approval. Drinking fountains shall conform to ASME
Al12.19.1, ASME Al12.19.2 or ASME Al12.19.9, and water coolers
shall conform to ARI 1010.
Exception: A drinking fountain need not be provided in a drinking or
dining establishment."
16. Section 412.4, Public laundries and central washing facilities, shall be
deleted it is entirety and replaced with Required location, providing for
the installation of floor drains, which shall read as follows:
"412.4 Required location. Floor drains shall be installed in the
following areas:
1. In public coin-operated laundries and in the central washing
facilities of multiple family dwellings, the rooms containing the
automatic clothes washers shall be provided with floor drains
located to readily drain the entire floor area.
2. Commercial kitchens. (in lieu of floor drains, in commercial
kitchens, the Building Official may accept floor sinks.
3. Toilet rooms in restaurant occupancies."
17. Section 413.4 shall be amended by adding a provision for the
protection of the water supply, which shall read as follows:
"413.4 Water supply required ...... The water supply shall be
protected against backflow by an air gap or with the installation of a
backflow preventer in accordance with Section 608 of this Code."
18. Section 417.5; shall be amended by adding language addressing
thresholds, which shall read as follows:
"417.5 Shower floors or receptors ......
Thresholds shall be a minimum of 2 inches (51 mm) and a maximum
of 9 inches (229 mm), measured from top of drain to top of threshold
or dam. Thresholds shall be of sufficient width to accommodate a
minimum 22 inch (559 mm) door."
19. Section 417.5.2 shall be amended to read as follows:
PAGE 5
46725(Rev.)
"417.5.2 Shower lining ...... Such liners shall turn up on all sides at
least 3 inches (51 mm) above the finished threshold level and shall
extend outward over the threshold and fastened to the outside of the
threshold jamb ...... "
20. Section 417.7, Test for shower receptors, shall be added to read as
follows:
"417.7 Test for shower receptors. Shower receptors shall be tested
for water tightness by filling with water to the level of the rough
threshold. The drain shall be plugged in a manner so that both sides of
pans shall be subjected to the test at the point where it is clamped to
the drain."
21 Section 419.3 shall be amended to read as follows:
"419.3 Surrounding material ...... a smooth, readily cleanable,
hard, nonabsorbent material."
22. Section 502.5 shall be amended to read as follows:
"502.5 Water heaters installed in attics ...... The clear access
opening dimensions shall be a minimum of 20 inches by 30 inches
(508 mm by 762 mm), or larger where such dimensions are not large
enough to allow removal of the water heater."
23. Section 502.5.1, Electrical requirements, shall be added to read as
follows:
"502.5.1 Electrical requirements. A lighting fixture controlled by a
switch located at the required passageway opening with a receptacle
outlet shall be provided at or near the equipment location in
accordance with the electrical code."
24. Section 502.6 shall be amended by specifying "2000 Edition" after the
words International Building Code, which shall read as follows:
"502.6 Seismic supports .... International Building Code, 2000
Edition... International Building Code, 2000 Edition."
25. Sections 502.7 and 502.7.1, shall be added to read as follows:
"502.7 Water heaters above ground or floor. When the attic, roof,
mezzanine or platform in which a water heater is installed more than 8
feet (2438 mm) above the ground or floor level, it shall be made
accessible by a stairway or permanent ladder fastened to the building.
PAGE 6
46725(Rev.)
502.7.1 Whenever the mezzanine or platform is not adequately lighted
or access to a receptacle outlet is not obtainable from the main level,
lighting and a receptacle outlet shall be provided in accordance with
Section 502.5.1 of this Code."
26. Section 504.6.1 shall be amended to read as follows:
"504.6.1 Discharge. The relief valve shall discharge through full size
piping to a safe place of disposal such as a floor drain, outside the
building, or an indirect waste receptor. The discharge pipe shall not
have any trapped sections. When the drain pipe run is exposed, in an
area outside of the room where the water heater is located, in a manner
that would make it subject to damage, the drain shall have a visible air
gap or air gap fitting located in the same room as the water heater.
The discharge shall be installed in a manner that does not cause
personal injury to occupants in the immediate area or structural
damage to the building in the event it operates.
(1) The end of the discharge pipe shall not be threaded. The discharge
shall not discharge into the pan required in Section 504.7 of the
Code.
(2) When discharging outside the building, the point of discharge shall
be with the end of the pipe not more than two feet (610 mm) or
less than 6 inches (152 mm) above the ground or the floor level of
the area receiving the discharge and pointing downward."
27. Section 505.1 shall be amended to read as follows:
"505.1 Unfired vessel insulation. Unfired hot water storage tanks
shall be insulated so that heat loss is limited as specified in Section
504, International Energy Conservation Code, 2000 Edition."
28. Section 506 and subsection 506.1, providing for Combustion Air and
Ventilation, shall be added to read as follows:
"SECTION 506
Combustion Air and Ventilation
"506.1 Combustion Air and Ventilation. Combustion air and
ventilation for fuel burning water heaters, other than gas-fired, shall be
in accordance with the International Mechanical Code. Combustion
air and ventilation for gas-fired water heaters shall be in accordance
with the International Fuel Gas Code, 2000 Edition."
PAGE 7
46725(Rev.)
29. Section 604.4 shall be amended by adding Subsection 604.4.1,
providing for State maximum flow rate, shall be added to read as
follows:
"604.4.1 State maximum flow rate. Where the State mandated
maximum flow rate is more restrictive than those of this section, the
State flow shall take precedence."
30. Amend Tables 605.4 and 605.5 by deleting all references to
"Polybutylene plastic pipe and tubing"
31 Amend Section 606.1 by deleting subsections 4, 5 and 6.
32. Amend Section 606.2, subsections 1 and 2, to read as follows:
"606.2 Location of shutoff valves. Shutoff valves shall be installed
in the following locations:
1. On the fixture supply to each plumbing fixture.
Exception: Tub and shower valves.
2. On the water supply pipe to each sill cock when subject to
freezing."
33. Amend Section 607.2.1 by deleting in its entirety and replacing the
same with the following:
"607.2.1 Piping insulation. Piping in required return circulation
systems shall be insulated as required in Section 504, International
Energy Conservation Code, 2000 Edition."
34. Section 608.1 shall be amended to read as follows:
"608.1 General. A potable water supply system shall be designed,
installed and maintained in such a manner so as to prevent
contamination from nonpotable liquids, solids or gases being
introduced into the potable water supply through cross-connections or
any other piping connections to the system. Backflow... conform to
applicable local regulations, ..... "
35. Section 608.17 shall be amended to read as follows:
"608.17 Protection of individual water supplies. An individual
water supply shall be located and constructed so as to be safeguard
against contamination accordance with applicable local regulations. In
PAGE 8
46725(Rev.)
the absence of other local regulations, installation shall be in
accordance with sections 608.17.1 through 608.17.8."
36. Amend Section 708.3.4, Base of stack, by deleting in its entirety and
replace the same with a new Section 708.3.4, Upper terminal, which
shall read as follows:
"708.3.4 Upper terminal. Each horizontal drain shall be provided
with a cleanout at its upper terminal.
Exception: Cleanouts may be omitted on a horizontal drain less
than 5 feet (1524 mm) in length unless such line is serving sinks or
urinals."
37. Amend Section 712 by adding subsection 712.5, which shall read as
follows:
"712.5 Dual pump system. All sumps shall be automatically
discharged and, when in any 'public use' occupancy where the sump
serves more than 10 fixture units, shall be provided with dual pumps
or ejectors arranged to function independently in case of overload or
mechanical failure. For storm drainage sumps and pumping systems,
see Section 1113 of the Code."
38. Amend Section 714 by changing the name of the Section title, and by
amending subsection 714.1 to read as follows:
"Section 714
Engineered Drainage Design
714.1 Design of drainage system. The sizing requirements for
plumbing drainage systems shall be determined by approved design
methods."
39. Section 802.1.1 shall be amended by deleting the exception thereto.
40. Section 802.4 shall be amended to read as follows:
"802.4 Standpipes ...... No standpipe shall be installed below the
ground."
41 Section 904.1 shall be deleted and replaced with similar language
which shall read as follows:
"904.1 Roof extension. All open vent pipes that extend through a
roof shall be terminated at least 6 inches (152 mm) above the roof,
PAGE 9
46725(Rev.)
except that where a roof is to be used for any purpose other than
weather protection, the vent extensions shall be run at least 7 feet
(2134 mm) above the roof."
42. Section 912 shall be amended by amending subsections 912.1 and
912.2 to read as follows:
"912.1 Type of fixture. A combination drain and vent system shall
not serve fixtures other than floor drains, standpipes and indirect waste
receptors ......
912.2 Installation. The only vertical pipe of a combination drain and
vent system shall be the connection between the fixture drain of a
standpipe, and the horizontal combination drain and vent pipe ...... "
43. Section 1002.10, Plumbing in mental health centers, shall be deleted in
its entirety.
44. Section 1003.3 shall be amended by adding section 1003.3.5 and by
deleting subsections 1003.3.1 through 1003.3.4 and replacing with the
same with similar language which shall read as follows:
"1003.3 Grease traps and grease interceptors ..... sections
1003.3.1 through 1003.3.6.
1003.3.1 Grease traps and interceptors required. All food
establishments having a food waste disposal or a discharge of more
than 50 gallons per minute shall discharge into a grease interceptor of
at least 750-gallon capacity.
Establishments with a discharge of 50 gallons per minute or less shall
discharge into at least a 100-lb. size grease trap. An approved grease
trap or interceptor complying with the provisions of this section shall
be installed in the waste line leading from sinks, drains and other
fixtures or equipment in establishments such as restaurants, cafes,
lunch counters, cafeterias, bars and clubs, hotel, hospital, factory or
school kitchen, or other establishments where grease may be
introduced into the drainage or sewage system in quantities that can
effect line stoppage or hinder sewage treatment or private disposal.
1003.3.2 Food waste grinders. Where food waste grinders connect to
grease traps or grease interceptors, the grease interceptor shall be sized
and rated for the discharge of the food waste grinder.
1003.3.3 Less restrictive requirements. Where in the opinion of the
Administrative Authority, grease would not be introduced into the
PAGE 10
46725(Rev.)
sewage or drain system in a quantity that would hinder sewage
treatment or private disposal, less restrictive measures may be
accepted by the Administrative Authority.
1003.3.4 Grease trap and interceptor not required. A grease trap or
interceptor shall not be required for individual dwelling units or
private living quarters.
1003.3.4.1 Grease trap capacity ......
1003.3.4.2 Rate of flow controls ......
1003.3.5 Engineered design. Interceptors required by section
1003.3.1 and 1003.3.2 shall be designed and sized by a mechanical
engineer."
45. Section 1106.1 shall be amended by deleting Figure 1106.1 and to read
as follows:
"1106.1 General. The .... shall be based on six inches per hour
rainfall rate."
46. Section 1107.3 shall be amended to read as follows:
"1107.3 Sizing of secondary drains .... shall be sized in accordance
with Section 1106 ...... "
47. Chapter 12, Special Piping and Storage Systems, Sections 1201
through 1203, shall be deleted in its entirety.
SECTION 2. If any section, subsection, paragraph, sentence, phrase or
work in this ordinance, or application thereof to any person or circumstance is
held invalid by any court of competent jurisdiction, such holding shall not affect
the validity of the remaining portions of this ordinance, and the City Council of
the City of Coppell, Texas hereby declares it would have enacted such remaining
portions despite any such invalidity.
SECTION 3. That all provisions of the Code of Ordinances of the City of Coppell,
Texas, in conflict with the provisions of this ordinance be, and the same are hereby,
PAGE 11
46725(Rev.)
repealed, and all other provisions not in conflict with the provisions of this ordinance shall
remain in full force and effect.
SECTION 4. That any person, firm or corporation violating any of the
provisions of this ordinance or the Code of Ordinances as amended hereby, shall be
guilty of a misdemeanor and upon conviction in the Municipal Court of the City of
Coppell, Texas, shall be subject to a fine not to exceed the sum of Five Hundred Dollars
($500.00) for each offense, except where a different penalty has been established by State
law for such offense, the penalty shall be that fixed by State law, and for any offense
which is a violation of any provision of law that governs fire safety, zoning or public
health and sanitation, including dumping of refuse, the penalty shall be fine not to exceed
the sum of Two Thousand Dollars ($2,000.00) for each offense; and each and every day
such offense is continued shall constitute a new and separate offense.
SECTION 5. That this ordinance shall become effective immediately from and
after its passage and the publication of the caption, as the law and charter in such cases
provide.
DULY PASSED by the City Council of Coppell, Texas, this the 23rd day
of April, 2002.
CANDY SHEEHAN, MAYOR
ATTEST:
LIBBY BALL, CITY SECRETARY
PAGE 12
46725 (Rev.)
ROBERT HAGER, CITY ATTORNEY
(REl-I/cdb II'vised] 3/18/02)
PAGE 13
46725 (Rev.)