(8/18/2009) Keith Marvin - Re: Coppell RoadPage 1
From:
Keith Marvin
To:
kar@Huitt-Zollars.com
Date:
12/13/2007 1:19 PM
Subject:
Re: Coppell Road
Ken,
I am out of the office until Monday. I agree that we can not lay an 8" at 0.23%. If a 10" keeps is within
TCEQ guidelines then we should use it.
I forwarded your email to our engineering technician to look at the layout. If I get some comments from
him I'll pass them on, if not I'll call you on Monday.
Keith
-----Original Message-----
From: "Roberts, Ken" <kar@Huitt-Zollars.com>
To: Keith Marvin <KMARVIN@ci.coppell.tx.us>
Cc: Theressa Smith <Theressa@Huitt-Zollars.com>
Sent: 12/13/2007 11:51:41 AM
Subject: Coppell Road
Keith,
In looking at the section of sanitary sewer to replace the existing 8"
main is on a 0.23% grade. Because of the flat grade, we are proposing
to replace the 8" main with a 10" main on a 0.22% grade. I have
attached a sketch showing our proposed design for your review and
comment. Let us know.
Thanks,
Kenneth Roberts, PE
Huitt-Zollars, Inc.