Denton Creek NH-LR090727~7AM ~NG[NEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
truing, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials S.E&-~. Failure
Testing Investigatia
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26109
Copoell, TX
PROJECT' NO.: 108TXSK9
ATTN: Brandon Parker
REPORT NO.: 21
SE&T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: North Firelane 30' N, 115' E from NW Corner Bldg PAGE 1 OF 4
TEST DATA
, :: -MATE
RIALStSUPPLiER DATA
Time Arrived:. 1:00 AM Concrete Supplier: Cowtown
Time Left: 8:30 AM Ticket #: 525330
Slump (Inches): 4.75 Truck #: 907
Concrete Temperature (F): 92
Time Batched: __
12:30 AM
Air Content: 4.6
Time Sam led: _
1:20 AM
Total No. of Test C tinders Made: 16 Product Code: 257
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A regate: N/A
Air Temperature (F): 82 Water: N/A
Unit Weight of Fresh Concrete: N/A % Air Content : N/A
,~pccmen '' Age date Unit Wt. :Total Load Compressive Type of Strength Required
~~~lirmber Da s Tested ' cf Lbs. Stren th s'r ,Fracture si/da s
1A 7 7/3/09 14Ei yt3,uuU 346o Si~il itr JirE:di 3~^v023
1 B 14 7/10/09 145 112,000 3961 Sin le Shear 3600128
1C 28 7/24/09 146 133,000 4703 Single Shear 3600/28
1 D 28 7/24/09 147 130,000 4597 Single Shear 3600/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slump ASTM C-143 ASTM C-39 & 231 SE8~T SE8~T
Remarks: Tested concrete meets/exceeds required strength. _
Very Truly Yours,
~ --
f~
Mi a aint~ Manager & Vice President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of ou r company name must receiaae our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or silrnilar samples.
G:/2009/108tx5k9/Cpistr/CPISTR21; SA
~7AM ENGINEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCf Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd.
Coppell, TX
TTN: Brandon Parker
REPORT DATE: 7/27/09
SAMPLE DATE: 6/26/09
PROJECT NO.: 108TX5K9
Geotechnical
Materials S+E~-~ Failure
Testing Invesfigafio
Environmental
SEAT TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: North Firelane 30' N, 40' E from NW Corner of
Time Arrived:
Time L eft•
1:00 AM
st•zn onn
Concrete Supplier:
T:..I.-i mot.
REPORT NO.: 21
PAGE20F4
Cowtown
Slump (Inches): 4.25
Truck #: JL~JJJ /
910
Concrete Temperature (F): 92 Time Batched: 1:02 AM
Air Content: 4.6 Time Sampled: 1:55 AM
Total No. of Test C tinders Made: 16 Product Code: 257
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Temperature (F): 82 Water: N/A
Unit Weight of Fresh Concrete: N/A % Air Content : N/A
Specimen Age Date Unit 11Vt. Total'Laa d Compressive Type of Strength Required
~ Number Da s' Tested ` cf Lbs Stren th' si Fr
t
. ac
ure si/da s
2H ~ 7/3/09 146 99,uG0 3501 Single Shear 3(~00/2ti
26 14 7/10/09 146 109,000 3855 Sin le Shear 3600/28
2C 28 7/24/09 148 119,000 4208 Sin le Shear 3600/28
2D 28 7/24/09 148 118,000 4173 Sin le Shear 3600!28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slump ASTM C-143 ASTM C-39 & 231 SE8~T SE&T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours,
~ __--_
Mik aint, ab Manage Vice President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G:/2009/108tx5k9/Cpistr/CP I STR21 /SA
a7AM ~NG[NEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials SE&T Failure
Testing Investigatic
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26/09
Coppell, TX
PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 21
SE&T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: West Firelane 30' S, 40' E from SW Corner of Bldg PAGE 3 OF 4
TEST DATA _. $ ' ~ „ ; ~': MATE RIALS/SUPPLIER DATA
Time Arrived: 1:00 AM Concrete Supplier: Cowtown
Time Left: 8:30 AM Ticket #: 525347
Slum (Inches): 4.5 Truck #: 922
Concrete Temperature (F): 92 Time Batched: 1:54 AM
Air Content: 4.6 Time Sampled: 3:30 AM
Total No. of Test C tinders Made 16 Product Code: 257
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Temperature (F): 81 Water: N/A
Unit Weight of Fresh Concrete: N/A % Air Content : N/A
:Specimen Age Date Unit Wt. ' Total'Load Ce~mpressive Type of Strength Required
rgNumber ' Da s Tested cf Lbs, Stren tln si Fracture si/da s
3A 7 7/3/09 145 69,000 244u Single Shear- 3600;28
3B 14 7/10/09 147 87,000 3076 Single Shear 3600/28
3C 28 7/24/09 147 102,000 3607 Sin le Shear 3600/28
3D 28 7/24/09 148 103,000 3642 Single Shear 3600/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinder's Tested By'.
Slum ASTM C-143 ASTM C-39 & 231 SE8~T SEBT
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours,
MI a Saln ,Lab Ma ger & Vlce President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G/2009/108tx5k9/Cpistr/CA'ISTR21/SA
~7AM ~tVGI[~fEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials SE&T Failure
Testing Investiga[ic
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26109
Coppell, TX
PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 21
SE8~T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: North Firelane 30' N, 160' E, from NW Corner of Bldg PAGE 4 OF 4
}t
~~
_.. T~S~,_DAT`~r; ., x ~
... ._ ~.k...
~~~..,._..._... '°MATE . ~ AM -
RIAES/SUPPLIER DATA
Time Arrived: 1:00 AM Concrete Supplier: Cowtown
Time Left: 8:30 AM Ticket #: 525357
Slum (Inches): 5 Truck #: 908
Concrete Temperature (F): 91 Time Batched: 5:33 AM
Air Content: 4.8 Time Sampled: 6:15 AM
Total No. of Test C tinders Made 16 Product Code: 257
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A regate: N/A
Air Temperature (F): 80 Water: N/A
Unit Weight of Fresh Concrete: N/A % Air Content : N/A
~$pecimen Age< Date Unit Wt. Total Load Compressive Type of o Strength Required
t~
„~CVurnber Da s Tesfed cf Lbs. Stren th si Fracture psi/da s
4A 7 713/09 144 97,000 3430 Jiil I~ Jller7r 3600!28
4B 14 7/10/09 145 113,000 3996 Sin le Shear 3600/28
4C 28 7/24/09 146 125,000 4420 Single Shear 3600/28
4D 28 7/24/09 145 127,000 4491 Single Shear 3600/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slump ASTM C-143 ASTM C-39 & 231 SE&T SES~T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours,
M/~ La ana er & Vice President
g
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G:/2009/108tx5k9/Cpistr/CP I STR21 /SA
~7AM ENGfNEERiNG ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials SE&T Failure
Testing Investigatio
Environmental
CONCRETE PLACEMENT INSPECTInN R ~TR1=1ulr_TN r~cT c~ono~-
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/27/09
Coppell, TX
PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 22
SE8~T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: Bldg Slab 70' N, 30' W from SE Corner of Bldg PAGE 1 OF 4
...~. ., _;~ ~~, .. ,... r.. ~~ .~.: II~~T~ RlIA~5/v~U~?.PLt1=R C}ATA.
Time Arrived: 1:45 AM Concrete Supplier: Cowtown
Time Left: 6:45 AM Ticket #: 525401
Slump (Inches): 5 Truck #: g25
Concrete Temperature (F): 90 Time Batched: 1:28 AM
Air Content: N/A Time Sampled: 2:20 AM
Total No. of Test C tinders Made: 16 Product Code: 345-67
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Tem erature.(F): 84 Water: N/A
Unit Weight of Fresh Concrete: 14$ % Air Content : N/A
specimen Age Bate tJniit°;1IUt. Total Load Compressive Type of Strength Required
Number Da s Tested ~f Lbs. Stren th si Fracture
. si/da s
1A 7 7/4/09 145 00.000 2122 Sin le Shear 3^00;2Q
1B 14 7/11/09 147 78,000 2758 Sin le Shear 3000/28
1C 28 7/25/09 147 91,000 3218 Single Shear 3000/28
1 D _ 28 7/25/09 148 87,000 3076 Sin le Shear 3000/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slump ASTM C-143 ASTM C-39 & 231 SE&T SE&T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours,
il~~l k a
n
L
ti M
& Vi
,
i
a
anager
ce President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for.the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identirai nr similar carr,nlcc
G:/2009/108tx5k9/Cpistr/CPISTR22/SA
~7AM ENGINEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials SE&T Failure
Testing Investigatic
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 2$,27 S(~. IN,
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26/09
Coppell, TX
PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 22
SEAT TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: Bldg Slab 35' N, 10' W from SE Corner of Bldg PAGE 2 OF 4
~` ~ ~ „ .r; ~ ` ~ ~ ~~~T~ al~Yl~y T' 5 ~ ~ ~;
~,. .. ~.. ,. ,,_,~a.-~,r ,. - - - . ,.~. s~_.~, , ~. MATE
.-a . , .; .. RIALS/SUpPL1EFt DATA...
. .
Time Arrived: 1:45 AM Concrete Su pliers Cowtown
Time Left: 6:45 AM Ticket #: 525413
Slump (Inches): 5.25 Truck #: 930
Concrete Temperature (F): 92 Time Batched: 2:22 AM
Air Content: N/A Time Sampled: 3:05 AM
Total No. of Test C tinders Made: 16 Product Code: 345-67
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 Fly Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Temperature (F): 84 Water: N/A
Unit Weigh t of Fresh Concrete: 148 % Air Content : N/A
Specimen
~
~ . Age' [late unit Wt. Total Load Compressive Type of ` Strength Required
~
Nuenbdr Da s Tested cf Lbs. Stren th` si Fracture
,... si/da s
2A ? 7/4/Og 147 77,OOn ?723 Sinnle Shear 3pnrJi~g
2B 14 7/11/09 147 89,000 3147 Sin le Shear 3000/28
2C 28 7/25/09 148 99,000 3501 Sin le Shear 3000/28
2D 28" 7/25/09 149 96,000 3395 Sin le Shear 3000/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slum ASTM C-143 ASTM C-39 & 231 SES<T SE&T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Your ,
e Saint, ab anager & Vice President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G:/2009/108tx5k9/Cpistr/CPISTR22/SA
~7AM ENGlNEERtNG ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnical
Materials SE&T Failure
Testing Investigatia
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN,
Tyler, TX 75703
REPORT DATE: 7/27/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26/09
Coppell, TX
PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 22
SE&T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: Bldg Slab 15' N, 50' W from SE Corner of Bldg PAGE 3 OF 4
„,
~' ~ TEST -C7~ATA . ! , ~ ,.~ , ~ .. ~ . _ ~= _ ,,, ~~~. -;MATI=
RIALSISUP#~L~~1~'. DATA
Time Arrived: 1:45 AM Concrete Supplier: Cowtown
Time Left: 6:45 AM Ticket #: 525420
Slump Inches): 4.75 Truck #: 920
Concrete Temperature (F): 90 Time Batched: 2:57 AM
Air Content: N/A Time Sampled: 4:00 AM
Total No. of Test C tinders Made: 16 Product Code: 345-67
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Temperature (F): 83 Water: N/A
Unit Weigh t of Fresh Concrete: 148 % Air Content : N/A
Specimen
~~ Agee. .Date Unit Wt. ` Total Load Compressive Type of ;Strength Required
e,.
~q`Nurnber
Da s
Tested
cf
Lbs.
Stren t6 si
Fracture
si/da s
3A 7 7/4/09 146 82,000 2900 Single Shear 3000/28
36 14 7/11/09 147 93,000 3289 Sin le Shear 3000/28
3C 28 7/25/09 147 98,000 3466 Sin le Shear 3000/28
3D 28 7/25/09 148 100,000 3536 Sin le Shear 3000/28
Curing ASTM C-31 . Test Method Cylinders Made By: Cylinders Tested By:
Slump ASTM C-143 ASTM C-39 & 231 SE8~T SE8~T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours,
~
t
b
& Vi
P
id
In
anager
, a
ce
res
ent
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of ou r company name mus t receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G:/2009/108tx5k9/Cpistr/CPISTR22/SA
~7AM ENGINEERING ~ TESTING, L.P.
Serving The Geo-Industry Since 1974
1115 Luke Street, Suite 100
Irving, Texas 75061
Phone: (972) 790-1910 • FAX: (972) 790-0967
Geotechnlcal
Materials SE&T Failure
Testing Investigatic
Environmental
CONCRETE PLACEMENT INSPECTION & STRENGTH TEST REPORT
CLIENT: SCI Construction, LTD STANDARD 6" X 12"
5467 New Copeland Rd. AREA 28.27 SQ. IN.
Tyler, TX 75703
REPORT DATE: 7127/09
PROJECT: Pro. Denton Creek Nursing Home
1410 E. Sandy Lake Rd. SAMPLE DATE: 6/26/09
Coppell, TX
' PROJECT NO.: 108TX5K9
ATTN: Brandon Parker
REPORT NO.: 22
SE&T TECHNICIAN: Chris Cook
LOCATION OF PLACEMENT: Bldg Slab 5' N, 90' W from SE Corner of Bldg PAGE 4 OF 4
a... ` ~,...,,.:, ~ _T~ST ~?/~tA - ~, s .,
,.. ' . ~., ° . MATE ,
REAL~S/SUPPLIER DATA '
Time Arrived: 1:45 AM Concrete Supplier: Cowtown
Time Left: 6:45 AM Ticket #: 525431
Slum Inches): 4 Truck #: 923
Concrete Temperature (F): 90 Time Batched: 4:04 AM
Air Content: N/A Time Sampled: 4:50 AM
Total No. of Test Cylinders Made 16 Product Code: 345-67
Total Cubic Yards Placed: 400 Cement: N/A
Added Water: 0 FI Ash: N/A
Weather Conditions: Clear/Warm Coarse A re ate: N/A
Air Temperature (F): 82 Water: N/A
Unit Weigh t of Fresh Concrete: 148 % Air Content : N/A
Specimen Age Date Unit Wt. Total Load Compressive Type of> Strengfih Required
~~Vu-nber Da s Tested cf Lbs. Siren th psi Fracture.: s/da s ;
4A 7 7/4/09 148 84 000 2970 Single Shear 3000/28
46 14 7/11!09 149 98,000 3466 Sin le Shear 3000/28
4C 28 7/25/09 148 105,000 3713 Sin le Shear 3000/28
4D 28 7/25/09 150 104,000 3678 Sin le Shear 3000/28
Curing ASTM C-31 Test Method Cylinders Made By: Cylinders Tested By:
Slum ASTM C-143 ASTM C-39 & 231 SEBT SE&T
Remarks: Tested concrete meets/exceeds required strength.
Very Truly Yours
Mik Sai , L anager & Vice President
Texas Professional Firm Registration No: F-001587
Texas Registration No: 61893
This report is for the sole use of the client addressed. The use of our company name must receive our prior written consent.
This report only applies to the samples tested and does not necessarily represent identical or similar samples.
G:12009/108tx5k9/Cpistr/CPISTR22/SA