Rolling Oaks MC-CS070703(12I7I2009) Ken Griffin - Re: Coppell Cemetery
From: Tim Oates
To: cdobecka~ndmce.com;
Date: 7/3/200710:48 AM
Subject: Re: Coppell Cemetery
Ken Griffin; mdaniel~ndmce.com
Gentlemen,
Based on the use of the property, the Fire Dept, believes the fire hydrants shown are adequate. It appears the
'maintenance' building in the NE corner of the property is under 5,000 sq ft, therefore it will not need to be equipped with
an automatic fire sprinkler system. If the building exceeds 5,000 sq ft, then a system will be required and the main water
system will have to 'loop' along the internal road. The other structures, other than the funeral home at the SW corner of
the property, we assume, will be constructed of non-combustible materials and they will contain minimal, if any,
combustible materials.
Long story short...the fire hydrants shown are adequate.
Tim Oates
Coppell Fire Department
Deputy Chief -Prevention & Building Div.
500 Southwestern Blvd.
Coppell, Texas 75019
Office # 972/304-7055
Fax # 972/304-3514
»> Ken Griffin 7/2/2007 5:12 PM »>
Mike
The only thing that could change may be additional fire hydrants. You may want to check with Tim Oates to determine how they
would handle a fire in the cemetery. If additional fire hydrants are needed, then the 2" waterline would need to be upsized to a 6
or 8" waterline. Long term there will be issues with the trail and potential buildings on the east side that encroach in the floodplain
and waters of the US.
I'm copying Tim on this response.
Hope this helps.
Ken Griffin
»> Mike Daniel <mdaniel@ndmce.com> 7/2/2007 3:22 PM »>
Ken,
We are being asked to help develop budget numbers for the infrastructure
costs in phase 1. Before we do anything more, I would like to get Staffs
comments on our preliminary plans. Has your department had a chance to look
them over yet?
Mike Daniel, PE, RPLS
Nathan D. Maier Consulting Engineers, Inc.
8080 Park Lane, Suite 600
Dallas, Texas 75231
(214) 739-4741
(214) 739-5961 FAX
mdaniel@ndmce.com