Loading...
ST0003-SP081031North Texas Contracting, Inc, SUBMITTAL Coppell Road from Cooper Lane to Sandy Lake Road Tiseo Paving Company Coppell, Texas Submittal Data Storm Structure Mix Designs Class A - 3,000 PSI Class C - 3,600 PSI NORTH TEXAS CONTRACTING INC. SUBMITTAL DATE: 10-31-08 ITEM:_Pipe Reviewed to Ensure Compliance: NG Reviewed & Rejected: Reviewed & Submitted: 10-31-08 Southern Star CC}NCRETE, INC, Southern Star Concrete, Inc. Technical Services Department 240 Singleton Blvd. Dallas, Texas 75212 Phone: (214) 651-8020 Fax: (214) 651-1810 MIX DESIGN SUBMITTAL for READY-MIXED CONCRETE Contractor: Inlet Structure Specialties Date: November 7, 2008 i Project: Coppell Road (Prom Cooper to Sandy Lake) -Coppell, Texas Mix Design #: 9339 New # D00000009339 Specific Use: Class A Minimum Compressive Strength: 3000 psi @ 28 Days Sack Content: 5.00 Air Content: 4.5% +/- 1.5% Fly Ash Content: 0% Slump Range (inches): 4 +/- 1" (After the addition of WR Admixtures) W/Cm Ratio (Ib/lb): 0.54 (6.05 gal/sk) Theoretical Plastic Unit Weight: 145 pcf Max. /Min. Concrete Temperature: 95°F Ref: ACI 305 / 306 Southern Star Concrete guarantees this mix design will achieve the specified compressive strength when tested and evaluated in accordance with ASTM C 172, C 31, C 39, C 94 and ACI 318, and when the recommended procedures for placement and curing in ACI 304, 305 / 306 are followed. When used for acceptance testing, strength specimens must be cured in strict accordance with Section 10 of ASTM C 31-03. MATERIAL REQUIREMENTS Materials ASTM Standards Weil=hts per Cubic Absolute Yard, SSD Volume Cement ASTM C 150 Type UII 470 lbs. 2.391 cu.ft. Coarse Aggregate ASTM C33 Grade #57 1" Limestone 1840 lbs. 11.003 cu.ft. Fine Aggregate ASTM C 33 Concrete Sand 1366 lbs. 8.355 cu.ft. Admixture ASTM C 494 Type A/D 18.8 oz. AEA ASTM C 260 AEA 1.9 oz. Water ASTM C94 252 lbs. 4.038 cu.ft. Air Void 1.215 cu.ft. 27.002 cu.ft. Dosage ofAdmixtures are adjusted according to current concrete temperatures. In accordance with ACI 318, please forward copies of all concrete test reports to the Quality Services Department at the above address so that we can monitor miz performance and provide data for future projects. T/:ank you. Submitted By: Janet Kinard Technical Services Office Manager Southern Star CUWCRETE, INC. Southern Star Concrete, Inc. Technical Services Department 240 Singleton Blvd. Dallas, Texas 75212 Phone: (214) 651-8020 Fax: (214) 651-1810 MIX DESIGNSUBMITTAL for READY-MIXED CONCRETE Contractor: Inlet Structure Specialties Date: November 7, 2008 Project: Coppell Road (from Cooper to Sandy Lake) -Coppell, Texas Mix Design #: 9363 New # D00000009363 Specific Use: Class C Minimum Compressive Strength: 3600 psi @ 28 Days Sack Content: 6.00 Air Content: 4.5% +/- 1.5% Fly Ash Content: 0% Slump Range (inches): 4 +/- 1" (After the addition of WR Admixtures) W/Cm Ratio (lb/Ib): 0.45 (5.10 gal/sk) Theoretical Plastic Unit Weight: 146 pcf Max. /Min. Concrete Temperature: 95°F Ref: ACI 305 / 306 Southern Star Concrete guarantees this mix design will achieve the specified compressive strength when tested and evaluated in accordance with ASTM C 172, C 31, C 39, C 94 and ACI 318, and when the recommended procedures for placement and curing in ACI 304, 305 / 306 are followed. When used for acceptance testing, strength specimens must be cured in strict accordance with Section 10 of ASTM C 31-03. MATERIAL REQUIREMENTS Materials ASTM Standards Wei:thts per Cubic Absolute Yard, SSD Volume Cement ASTM C 150 Type UII 564 lbs. 2.869 cu.ft. Coarse Aggregate ASTM C33 Grade #57 1" Limestone 1840 lbs. 11.003 cu.ft. Fine Aggregate ASTM C 33 Concrete Sand 1280 lbs. 7.829 cu.ft. Admixiure ASTM C 494 Type A/D 22.6 oz. AEA ASTM C 260 AEA 2.3 oz. Water ASTM C94 255 lbs. 4.087 cu.ft. Air Void 1.215 cu.ft. 27.003 cu.ft. Dosage of Admixtures are adjusted according to current concrete temperatures. In accordance wit/: ACI3l8, please forward copies ojall concrete test reports to the Quality Services Department at the above address so t/:at we can monitor mix performance and provide data for future projects. Thank you. Submitted By: Janet Kinard Technical Services Office Manager f Contractor: Various 2008 Project: Various Laboratory: Various Field Test Data Mix No. 9339 Basis for Selection ACI 318, Section 5.3.2.1 (5-1) Design Strength: 3000 psi Standard Deviation: 349 psi Data Represents: 4$ Tests Required Strength: 3467 psi Data Updated: 10/23/2008 Averaee Strength: d'i~tl oci Conc. Unit 7 Da Com ressive 28 Da Com ressive Stren th Data # Date Slum Tem Air% we;ght C L 1 C 1.2 7 Da Av C I. 1 C L 2 SetAv Av ./3 Ran a St. Dev. RunAv 56 Da i 04/03/2008 6.50 74 3.7 145.2 2840 2840 3520 4340 3930 820 3930 ~ 4650 2 04/03/2008 7.50 72 5.2 145.6 2890 2890 4280 4270 4280 ]0 247 4110 4570 3 04/09/2008 3.25 78 0.9 2980 2980 4310 4380 4350 4190 70 225 4190 a 04/12/2008 5.00 68 4.6 144.6 3490 3510 3500 4510 4620 4570 4400 110 266 4280 s 04/12/2008 5.50 68 5.8 143.0 2980 2660 2820 3870 3910 3890 4270 40 289 4200 6 04/12/2008 5.00 68 5.2 143.8 3580 3410 3500 4390 4750 4570 4340 360 299 4270 ~ 04/12/2008 5.50 70 5.5 143.8 3300 3250 3280 4510 4660 4590 4350 150 299 4310 s 04/12/2008 5.00 66 4.6 3290 3290 5200 5090 5150 4770 110 406 4420 9 04/12/2008 5.00 69 4.9 3290 3290 4420 4460 4440 4730 40 380 4420 ~0 04/12/2008 4.75 70 5.2 3420 3420 4710 4750 4730 4770 40 371 4450 it 04/21/2008 5.00 83 5.3 143.7 2830 2830 4370 4410 4390 4520 40 353 4440 5420 iz 04/21/2008 5.50 78 4.2 145.5 3050 3050 4460 4290 4380 4500 170 337 4440 4870 ~s 04/25/2008 5.75 82 3.9 2600 2600 3650 3600 3630 4130 50 393 4380 ~a 04/29/2008 4.50 69 1.0 149.0 2920 2920 4040 4090 4070 4030 50 386 4360 4810 is 04/29/2008 5.50 74 4.9 2580 2580 3450 3780 3620 3770 330 418 4310 ~6 05/01/2008 5.00 63 5.8 3590 3590 4780 4630 4710 4130 150 416 4330 5110 05/02/2008 3.00 78 4.1 146.8 3410 3410 4420 4620 4520 4280 200 405 4340 5490 is 05/09/2008 4.00 66 3.0 2740 2830 2790 4030 3970 4000 4410 60 401 4320 i9 05/09/2008 5.00 80 3.5 2840 2840 3510 3730 3620 4050 220 422 4290 zo 05/12/2008 6.50 77 4.5 144.0 3540 3540 3940 3900 3920 3850 40 419 4270 4300 zi 05/12/2008 5.25 80 3.6 146.4 3980 3980 4870 5100 4990 4180 230 438 4300 5100 22 05/13/2008 4.00 80 4.6 142.9 3480 3480 4480 4480 4480 4460 0 429 4310 zs 05/17/2008 4.00 75 3.8 144.6 2810 2800 2810 3890 3840 3870 4450 50 429 4290 2a 05/19/2008 6.75 86 4.0 145.2 2970 3050 3010 4020 3810 3920 4090 210 426 4280 zs 05/21/2008 6.00 85 3.9 145.0 3330 3330 4650 4270 4460 4080 380 419 4280 4690 26 05/21/2008 4.00 89 2.5 143.6 3080 3080 43]0 4350 4330 4240 40 411 4290 5010 z~ 05/22/2008 5.00 87 3.6 3380 3480 3430 4120 4120 4120 4300 0 404 4280 zs 05/23/2008 5.50 90 2.0 147.6 3060 3060 3970 4210 4090 4180 240 398 4270 4640 2v 05/23/2008 5.00 75 2.0 3650 3650 4550 4400 4480 4230 150 393 4280 4720 so 05/28/2008 6.00 89 2.8 148.4 3210 3210 4560 4580 4570 4380 20 389 4290 4560 3t 05/30/2008 5.50 84 5.0 144.8 3650 3650 4240 4570 4410 4490 330 384 4290 4920 sz 06/05/2008 5.00 87 2.9 3050 3050 4120 4210 4170 4380 90 378 4290 s3 06/06/2008. 3.75 91 3.4 3250 3250 4270 4220 4250 4280 50 372 4290 sa 06/24/2008 5.00 88 4.0 3600 3600 4610 4630 4620 4350 20 371 4300 ss 07/07/2008 5.50 90 2940 2940 4550 4710 4630 4500 160 370 4310 36 07/07/2008 6.00 89 2880 2880 4220 4280 4250 4500 60 364 4310 3~ 07/07/2008 6.00 90 2750 2750 3720 3810 3770 4220 90 370 4290 ss 07/18/2008 5.50 87 2.0 147.1 2620 2910 2770 4460 4110 4290 4100 350 365 4290 4630 s9 07/30/2008 5.50 92 2.7 148.4 2980 2980 4330 4370 4350 4140 40 360 4290 ao 08/01/2008 5.00 93 3.5 147.5 3570 3570 4660 4390 4530 4390 270 358 4300 ai 08/05/2008 4.50 92 3.4 139.8 3370 3370 4510 4490 4500 4460 20 354 4300 a2 08/06/2008 3.50 94 2.5 149.2 2530 2530 5100 5010 5060 4700 90 369 4320 as 08/07/2008 4.00 86 3.1 146.8 3770 3770 4830 4390 4610 4720 440 367 4330 as 08/11/2008 3.50 95 3.8 3450 3300 3380 4410 4350 4380 4680 60 363 4330 as 08/22/2008 4.25 84 3.9 147.0 3120 3120 4540 4240 4390 4460 300 359 4330 a6 08/25/2008 4.75 98 3.4 3260 3260 3260 4300 4180 4240 4340 120 355 4330 a~ 08/27/2008 5.00 91 3.5 3190 3150 3170 4160 4130 4150 4260 30 352 4320 as 08/27/2008 4.00 92 3.6 144.8 3380 3380 4390 4170 4280 4220 220 349 4320 Southern Star Concrete, Inc. Field Test Data for Mix 9339 -Various 2008 1 .: Contractor: Various Project: Various 2008 Laboratory: Various Field Test Data Mix No. 9363 Basis for Selection ACI 318, Section 5.3.2.1 (5-2) Design Strength: 3600 psi Standard Deviation: 52O psi Data Represents: 51 Tests Required Strength: 4313 psi Data Undated: 10/27/200R Average fitrenoth~ C1'7!1 Conc. Unit 7 Dav Compressive 28 Dav Compressive Strength Data # Date Slum Temp Air% Weight Cyl. 1 CyL 2 7 Day Avg. Cyl. 1 CyL 2 SetAv Av .13 Ran a St. Dev. RunAv 56 Da i 01/05/2008 5.00 67 5.2 3550 3540 3550 4470 4510 4490 4490 40 4490 2 01/07/2008 6.00 74 4.5 4380 4450 4420 5370 5420 5400 4950 50 643 4950 3 01/07/2008 4.75 74 4.2 4390 4400 4400 5510 5410 5460 5120 100 544 5120 a 01/07/2008 4.50 75 1.5 4380 4670 4530 5750 5630 5690 5520 120 528 5260 s 01/28/2008 3.75 63 4720 4670 4700 6500 6660 6580 5910 160 747 5520 6 01/30/2008 3.50 60 5060 5200 5130 6750 6610 6680 6320 140 818 5720 7 03/25/2008 2.00 75 2.6 4310 4310 5190 5550 5370 6210 360 758 5670 s 03/28/2008 4.00 71 4.8 4130 4130 5270 5330 5300 5780 60 714 5620 9 04/11/2008 5.00 75 3.3 3910 3910 5160 5230 5200 5290 70 682 5570 io 04/14/2008 5.00 69 3.4 4750 4750 5420 5330 5380 5290 90 646 5560 ii 04/17/2008 5.00 74 0.9 4600 4600 5840 5980 5910 5500 140 622 5590 iz 05/01/2008 4.00 86 4.5 4450 4450 5380 5500 5440 5580 120 595 5580 is 05/30/2008 4.50 94 4.1 3170 3170 4680 4540 4610 5320 140 629 5500 is 06/03/2008 3.75 94 2.2 4300 4300 5400 5380 5390 5150 20 605 5490 ~s 06/13/2008 4.75 89 1.6 3565 3570 4490 4330 4410 4800 160 647 5420 i6 06/13/2008 5.00 96 2.5 3980 3980 4490 4330 4410 4740 160 674 5360 06/16/2008 3.50 85 4490 4490 5730 5640 5690 4840 90 658 5380 is 06/18/2008 5.00 96 2.5 3980 3980 5370 4810 5090 5060 560 642 5360 is 06/20/2008 3.00 94 3.0 4010 4120 4070 5020 5040 5030 5270 20 628 5340 zo 06/23/2008 3.50 99 3.0 145.2 4520 4520 5450 5370 5410 5180 80 612 5350 21 06/25/2008 4.00 84 3.5 4710 4620 4670 5680 5540 5610 5350 140 599 5360 22 06/25/2008 2.25 93 4310 4310 5370 5360 5370 5460 10 584 5360 2s 06/25/2008 5.00 82 2.5 4170 4170 5310 5410 5360 5450 100 571 5360 za 07/01/2008 6.00 95 3.2 146.3 3760 3760 4700 4950 4830 5190 250 569 5340 2s 07/15/2008 5.00 95 1.0 4030 4030 5070 5140 5110 5100 70 559 5330 26 07/17/2008 6.00 90 3.2 148.4 3230 3230 4370 4400 4390 4780 30 577 5290 z7 07/17/2008 7.00 94 3.0 2890 2890 4140 4120 4130 4540 20 609 5250 2s 07/17/2008 3.00 95 1.2 148.2 3830 3830 5080 4890 4990 4500 190 600 5240 z9 07/18/2008 5.00 94 2.7 148.0 4010 4010 4460 4790 4630 4580 330 600 5220 so 07/18/2008 6.75 89 2.8 4310 4310 5310 5220 5270 4960 90 589 5220 si 07/21/2008 5.00 91 3.2 146.8 3930 3930 5270 5030 5150 5020 240 579 5220 sz 07/22/2008 5.00 85 4.5 3900 3900 4920 4990 4960 5130 70 572 5210 33 07/23/2008 7.00 92 2.0 4260 4260 5100 5240 5170 5090 140 563 5210 sa 07/23/2008 4.50 92 3.2 147.5 3540 3540 4800 4990 4900 5010 190 557 5200 35 07/23/2008 4.00 98 3.0 4170 4170 4170 5320 5170 5250 5110 150 549 5200 36 07/25/2008 5.00 92 3.1 148.0 3530 3530 4650 4420 4540 4900 230 552 5180 s~ 07/25/2008 4.00 92 3.1 4970 4370 4670 5530 5730 5630 5140 200 549 5200 ss 07/25/2008 5.00 88 1.0 148.0 3770 3770 4960 4820 4890 5020 140 544 5190 s9 07/28/2008 4.75 98 4.4 3670 3780 3730 5130 5120 5130 5220 10 537 5190 ao 07/28/2008 6.00 91 3.1 147.6 3190 3190 4640 4730 4690 4900 90 536 5170 ai 07/30/2008 4.50 90 3.6 146.8 3930 3930 4660 4540 4600 4810 120 536 5160 a2 07/30/2008 4.50 93 4.7 3540 3550 3550 4930 5030 4980 4760 100 531 5160 as 08/01/2008 3.50 92 3.0 147.1 4550 4550 5900 5520 5710 5100 380 531 5170 as 08/01/2008 3.50 93 3.2 146.8 4490 4490 5500 5590 5550 5410 90 528 5180 45 08/01/2008 2.00 94 4.4 3300 3540 3420 5060 4710 4890 5380 350 524 5170 a6 08/05/2008 4.00 97 4.0 3040 3150 3100 4320 4370 4350 4930 50 532 5150 a7 08/25/2008 3.50 90 3.1 144.7 4460 4460 5550 5540 5550 4930 10 529 5160 as 08/25/2008 3.00 90 3.6 144.4 4600 4600 5760 5820 5790 5230 60 531 5170 a9 08/25/2008 6.00 96 3.4 143.6 3470 3470 4970 4940 4960 5430 30 527 5170 sa 09/12/2008 5.00 94 0.9 150.8 4070 4070 4640 4900 4770 5170 260 524 5160 s~ 09/12/2008 5.50 90 0.9 150.8 4160 4160 5310 5570 5440 5060 260 520 5170 6120 5750 5970 5120 5620 5140 5200 5190 6000 5820 Southern Star Concrete, Inc. Field Test Data for Mix 9363 -Various 2008 ~ ~~ ~ N ~ • r, ~~ T /1 r1 ~~ ^~~ rl ~L! ~ U . r.., ~ ~ ~ N a +~ ~ b.A ~ y~~~ y~..~~ ~~ }~/~J w.J v~J y~n ® 0 L r~ Y i t ~~ O N V Z W W u 0 V i O O N M O O ~ ~ ~ 00 ~ O ti .--i ~ ~ O 7 Vi N o `G v~ N ~c ~ ~o ~ ~ ~ O~ O~ 01 ~? O O O O ~ 000 ~ ~ ~ ~ M N ~ 0 \° 0 u v Cw ~'' sanais ~uiss~d ~ua~aad ani~~inrun~ ~ V1 ~ e~ ~ c . ~ ao 0 ~ ~ ~ N I I O O C O .,. U ~U O "~ ~, ~a a 0 U bA A •.r C~ C U it a V1 ~~ ., I ~l O r~ ~/ ~ V1 •~ ~~~n ~J U bA ~-' ~~ ~ ~ ~ Trl {"i"'~ L Z H W AC L V tU o =v a•+ Q M M . ,..i MM~ F~ C~ Q~ i-~ O . ~..~ O C~ W M x i Q ~ O ~ ~ ~ ~ ~ ~ ~ ~ ~ M N N N O N O M O O M O i M ~--i O ~ ~ O N ~ ~ N0j ~ .fir `D ~ ~ ~ N ~ M ~ ~ ~ ~ ~ 00 C ~,.~ O O 00 v'7 M OMO~ ~ O ~ ~ ~ r O~ ~ O O O O OOi 000 ~ ~ V0) ~ M N ~ 0 ' \° 0 v ~ cv v ~ `~ ~ sanais ~uiss~d ~aaaaad ant;~Inrun,~ ~ ~ '~ ^O eke ~ .~ .~ ~ ~ ~ ~ ~ ~ O O ~--i L", O CC U ~i .U CL C/] O "'r7 i. C~ C. O to .~ a, c U it 6~ 0 0 N 'O C :n a ASH GROVE TEXAS L.P. 900 Gifco Road Post Office Box 520 Midlothian, Texas 76065 Production Period: September 1, 2008 - September 30, 2008 H GRO Cement Type: I/II STANDARD REQUIREMENTS ASTM C 150 Phone: 972-723-2301 Fax: 972-299-5127 Date: 10/81200tt CHEMICAL PHYSICAL Spec. Test Spy, Item Limit Result Item Limit Test Result SiOr (%) A 20.53 Air content of mortar (volume %) 12 max 7.3 AI=03("/•) 6.0 max 4.83 Fineness (cm~/g) Fe20;(%) 6.0 max 4.02 (Air permeability) 2800 min 3466 Ca0 (%) A 62.89 Autoclave expansion (°/.) 0.80 max 0.01 Mg0 (%) 6.0 max 1.19 SOS (%) 3.0 max 2.86 Compressive strength (psi) Min: Loss on ignition (%) 3.0 max 1.02 1 Day A 1834 NasO (%) A 3 Days 1740 2951 Ii=O (%) A 7 Days 2760 3870 Insoluble Residue (%) 0.75 max 0.31 28 Days A C02 (%) A 0.00 Limestone (%) per ASTM 5.0 max 0.0 Limestone (%) per TXDOT 3.00% max. 0.0 Limestone (%) per AHTD 3.00%max. 0.0 CaC03 in limestone (%) 70 min 0 Potential compounds (%) Time of setting (minutes) CAS A 54 (Vicat) C25 A 18 Initial Not less 83 CAA 8 max 6.0 than 45 CAF ,q CaAF+2(C~A) A Final Not more 206 C~S+ 4.75C~A 100 max 82 than 375 OPTIONAL REQUIREMENTS ASTM C150 Tables 2 and 4 CHEMICAL Spec. Test Item Limit Result CaS + CAA (%) A E uivalent alkalies (%) 0.60 0.56 A =Not applicable. H =Limit not specified by purchaser, test result provided for information only. C =Test results for this period not available. PHYSICAL Spec. Item Limit Test Result False set (%) A A Heat of hydration (kJ /kg) 7 days A 378 Heat of hydration (kJ /kg) 28 Days A A We certify that the above described cement, at the time of shipment, meets the chemical and physical requirement of the ASTM C 150-07. susAr, ca~rru odd o. h,,w~~~ NOtafy PUb~1C SiBrtattue: State of Texas Todd O. Hinton Comm. Expires 06-30-2012 Title: Quality Cnntro) Manager Product Data Sheet '' Edition 10.2005 Identification no. 147-540 Sika Air ~,,' ~. ,~.. Sika® Air `Air Entraining Admixture Description Sika Air admixture is an aqueous solution of organic materials. Sika Air meets the requirements of ASTM C-260 for air entraining admixtures. Applications Sika Air is recommended for use whenever air entrained concrete is desired. Ready-mix, precast and block producers can achieve predictable and uniform entrained air contents in concrete, even where harsh lean mixes are used or fly-ash is added to the concrete. Advantages Durability: ^ Air entrainment is recognized as the most effective prevention against con- crete scaling in exposed environments. Air entrained concrete delivers par- ticular benefits in the form of increased concrete durability. This is important in colder climates where frost and freeze-thaw cycles can cause scaling and damage to the concrete surface. ^ Air entraining agents help to prevent scaling by creating microscopic air voids that water trapped in the concrete can expand into when the concrete freezes, thus preventing cracks caused by the natural expansion. Entrained air voids in the concrete will also increase durability in harsh environments where concrete is exposed to deicing salts, marine salts and sulfates. Workability and Placeability: • Workability and placeability are also improved by the lubricating action of the microscopic bubbles in the concrete. Concrete will flow better, and bleeding and shrinkage will be reduced because less water is needed to obtain the desired workability. • Sika Air provides stable and predictable air contents in concrete, with uni- form air void spacing throughout the concrete matrix. How to Use Dosage rates for Sika Air will typically fall between 0.5 and 3 fl. oz. per 100 lbs. (32 - 195 ml/100 kg) of cementitious to entrain between 4 and 6 percent air. Higher air contents may be obtained by increasing the dosage rate. Dosage rates will vary depending on the air content required for a particular project. Typically air contents will be specified in the range of 4 to 8 percent by volume. Other factors that may affect the amount of air entrained into the concrete including total cementitious content, type of pozzolanic materials, sand grada- tion, salt/clay in aggregates, temperature and water content. The use of fly ash, particularly high LOI fly ash, can result in a higher dosage of air entrain- ment. Sika recommends that trial mixes be performed whenever material or any other changes are made that may affect the amount of entrained air. In mixes requiring a lower or higher amount dosage rate, please contact your local regional Sika office or Sika technical service department at 1-800-933- 7452 for further information. Mixing ~°s ,. ~~v, S ~~. ~:: i~ „Y,FH„ Measure the required quantity per batch manually or with automatic dispenser equipment. Add Sika Air to mixing water or sand. Do not mix with dry cement. When Sika Air is used in combination with other admixtures, care must be taken to dispense each admixture separately into the mix. Combination with Other Admixtures: Combination with other admixtures, particularly water reducers and retarders, may increase the amount of entrained air in the mix. Air contents should be checked with an air-meter after hatching and dosage adjustments made at the concrete plant. Packaging Sika Air is available in 55 gallon drum (208 liter), 275 gallon totes (1040 liters) drums and bulk delivery. Storage and Shelf life Sika Air should be stored at above 40°F (5°C). If frozen, thaw and agitate thoroughly to return to normal state. Shelf life when stored in dry warehouse conditions between 50°F and 80°F (10°C - 27°C) is~one year. Typical Data Appearance Dark Amber liquid. Specific Gravity Approx. 1.0 CAUTION: IRRITANT Contains Aqueous Solution (CAS:Mixture). May cause eye/skin/respiratory irritator. May be harmful if swallowed. Handling and Storage Avoid direct contact. Wear personal protective equipment (chemical resistant goggles/gloves/clothing) to prevent direct contact with skin and eyes. Use only in well ventilated areas. Wash thoroughly with soap and water after use. Remove contaminated clothing and launder before reuse. First Aid Eyes: Hold eyelids apart and flush thoroughly with water for 15 minutes. Skin: Remove contaminated clothing. Wash skin thoroughly for 15 minutes with soap and water. Inhalation: Remove person to fresh air. Ingestion: Do not induce vomiting. Dilute with water. Contact physician. In all cases contact a physician immediately if symptoms persist. Clean Up Use personal protective equipment (chemical resistant goggles/gloves/cloth- ing). Without direct contact, remove spilled or excess product and place in suitable sealed container. Dispose of excess product and container in accor- dance :Mith applicable anyirnnrr1ental reg~ilatipnc, KEEP CONTAINER TIGHTLY CLOSED KEEP OUT OF REACH OF CHILDREN NOT FOR INTERNAL CONSUMPTION FOR INDUSTRIAL USE ONLY CONSULT MATERIAL SAFETY DATA SHEET FOR MORE INFORMATION Sika warrants this product for one year from date of installation to be free from manufacturing defects and to meet the technical properties on the current Technical Data Sheet rf used as directed within shelf life. User determines suitability of product for intended use and assumes all risks. Buyer's sole remedy shall be limited to the purchase price or replacement of product exclusive of labor or cost of labor. NO OTHER WARRANTIES EXPRESSED OR IMPLIED SHALLAPPLY INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SIKH SHALL NOT BE LIABLE UNDER ANY LEGAL THEORY FOR SPECIAL OR CONSEQUENTIAL DAMAGES. SIKA SHALL NOT BE RESPONSIBLE FOR THE USE OF THIS PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS HELD BY OTHERS. Sika Corporation Sika Canada Inc. 1-800-933-SIKH p.UALITy 201 Polito Avenue 601, Delmar Avenue Lyndhurst, NJ 07071 Pointe-Claire, QC H9R 4A9 e t r Phone: (201) 933-8800 Phone: (514) 697-2610 ~ ~ Fax: (201)933-6225 Fax: (514)697-3087 MEN~ ~~HIE tvwwsikaconstruction.com twvwsika.ca VE Regional Information and Sales Centers. For the location of your nearest Sika representative, contact your regional center. U.S.: North East Region: Fairless Hills, PA, Phone: (215) 295 X600 North Central Region: Marion, OH, Phone: (800) 851-1545 South East Region: Conyers, GA, Phone: (770) 760-1300 South Central Region: Mesquite, TX, Phone: (972) 289£480 Western Region: Santa Fe Springs, C A, Phone: (562) 903-3650 Canada: Ontario: Mississauga, ON, Phone: (905) 795-3177, Alberta: Edmonton, A8, Phone: (780) 486-6111 Quality Certification Numbers: Lyndhurst: FM 69771 (180 8000), FM 70421 (OS 9000), Marion: FM 69715, Kansas City: FM 69107, Santa Fe Springs: FM 68408 Sika is a registered trademark. Made in USA. Printed in USA. Description Plastocrete 161 is a lignin polymer-type water-reducing admixture. Plastocrete 161 meets the requirements of ASTM C-494 Types A, B and D. Applications Plastocrete 161 is recommended for use in all applications where high quality concrete with superior workability is required. Advantages Plastocrete 161 water reducing admixture provides an economical and highly effective means of reducing the amount of mixing water required to produce concrete of a certain slump by acting as a dispersant for the cement particles in the mix. Through this dispersing action more of the surface area of the cement particles is available for early hydration. The more cement particles hydrated by contact with the mixing water, the greater the compressive strength of the concrete. Plastocrete 161 is formulated as a Type A water reducer to allow up to 10% water reduction and maximize the benefits of increased hydration in both the hardened and plastic states. ^ Reduced water content required to achieve desired slump, increases compressive and flexural strengths and allows the use of more economi- cal mixes. ^ Improved paste quality makes concrete easier to pump and finish. ^ Consistent normal setting times throughout the recommended dosage. ^ Lower water cement ratios provide decreased permeability and increased durability. ^ Plastocrete 161 does not contain intentionally added chlorides and will not initiate nor promote the corrosion of steel in the concrete. How to Use Dosage Dosage rates will vary depending on the material used, ambient conditions and the requirements of a specific project. For general concreting applications, Sika recommends a dosage rate between 2-4 fl.oz./100 lbs. (130-260 ml/100 kg) of cementitious materials for normal setting characteristics. Dosage rates of 4-6 fl.oz./100 lbs. (260-390 ml/100 kg) of cementitious materials are recommended for applications where higher water reduction is needed as well as extended workability and prolonged setting times. Dosage rates outside the recommended range may be used where ~z ~ specialized materials such as microsilica are specified, extreme ambient ~~ ' r, conditions are encountered or unusual project conditions require special con- ~~~~'~ sideration. In this case please contact your local regional Sika office or Sika ~~~ =_> technical service department at 1-800-933-7452 for further information. Plastocrete 161 is added at the concrete plant. Measure required quantity manually or by automated dispenser. Add into the water line at the batch plant or to the mixer at the end of the batching cycle. Combination with other Admixtures: Plastocrete 161 works effectively as a single admixture or in combination with other admixtures in the Sika System. When air entrained concrete is specified, Sika recommends the use of Sika air entraining admixtures. When used in combination with other admixtures, care must be taken to dispense each admixture separately into the concrete. Do not mix with dry cement. ' Packaging Plastocrete 161 is supplied in 55 gallon (208 liter) drums and bulk delivery. Storage and Shelf-life Plastocrete 161 should be stored at above 40°F (5°C). If frozen, thaw and agitate thoroughly to return to normal state before use. Shelf life when stored in dry warehouse conditions between 50°F and 80°F (10°C - 27°C) is one year. Typical Data Appearance Dark Brown liquid Specific Gravity Approx. 1.2 Caution Skin and eye irritant; avoid contact. The use of NIOSH approved respirator, safety goggles and rubber gloves is recommended. Avoid breathing product. Use with adequate ventilation. Remove contaminated clothing. Handling and Storage Avoid direct contact. Wear personal protective equipment (chemical resistant goggles/gloves/clothing) to prevent direct contact with skin and eyes. Use only in well ventilated areas. Wash thoroughly with soap and water after use. Remove contaminated clothing and launder before reuse. First Aid Eyes: Hold eyelids apart and flush thoroughly with water for 15 minutes. Skin: Remove contaminated clothing. Wash skin thoroughly for 15 minutes with soap and water. Inhalation: Remove person to fresh air. Ingestion: Do not induce vomiting. Dilute with water. Contact a physician. In all cases, contact a physician immediately if symptoms persist. Clean Up Use personal protective equipment (chemical resistant goggles/gloves/ clothing). Without direct contact, remove spilled or excess product and place in suitable sealed container. Dispose of excess product and container in ac- cordance with applicable environmental regulations. KEEP CONTAINER TIGHTLY CLOSED KEEP OUT OF REACH OF CHILDREN ~< NOT FOR INTERNAL CONSUMPTION FOR INDUSTRIAL USE ONLY CONSULT MATERIAL SAFETY DATA SHEET FOR MORE INFORMATION Sika warrants this product for one year from date of installation fo be free from manufacturing defects and to meet the technical properties on the current Technical Data Sheet if used as directed within shelf Irfe. User determines suitability of product for intended use and assumes all risks. Buyer's sole remedy shall be limited to the purchase price or replacement of product exclusive of labor or cost of labor. NO OTHER WARRANTIES EXPRESSED OR IMPLIED SHALLAPPLY INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SIKH SHALL NOT BE LIABLE UNDER ANY LEGAL THEORY FOR SPECIAL OR CONSEQUENTIAL DAMAGES. SIKA SHALL NOT BE RESPONSIBLE FOR THE USE OF THIS PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS HELD BY OTHERS. Sika Corporation Sika Canada Inc. 1-800-933-SIKA r,.UALITy 201 Polito Avenue 601, Delmar Avenue Lyndhurst, NJ 07071 Pointe-Claire, QC H9R 4A9 a ~ ~ Phone: (201) 933-8800 Phone: (514) 697-2610 ~ ~ Fax: (201) 933-6225 Fax: (514) 697-3087 www.sikaconstruction,com www.sika.ca ~CHIEVEMEN~ Regional Information and Sales Centers. For the location of your nearest Sika representative, contact your regional center. U.S.: North East Region: Fairless Hills, PA, Phone: (215) 295 6600 North Central Region: Marion, OH, Phone: (600) 851-1545 South East Region: Conyers, GA, Phone: (770) 760-130D South Central Region: Mesquite, TX, Phone: (972) 289.6480 Western Region: Santa Fe Springs, CA, Phone: (562) 903-3650 Canada: Ontario: Mississauga, ON, Phone: (905) 795-3177, Alberta: Edmonton, AB, Phone: (760) 466111 Quality Certification Numbers: Lyndhurst; FM 69711 (150 90001, FM 70421 IQS 90001, Marion: FM 69719, Kansas City: FM 69107, Santa Fe Springs: FM 69408 Sika and Plastocrete are registered trademarks. Made in USA. Printed in USA. Product Data Sheet Edition 10.2005 Identification no. 100-54 Plastiment Plastiment® Water Reducing and Retarding Admixture Description Plastiment is awater-reducing and retarding admixture. Plastiment meets the requirements of ASTM C-494 Types B and D. Applications Plastiment is recommended for use whenever high quality concrete with pre- dictable and controlled set times is desired. Use in flatwork and horizontal or vertical slipform placements where a superior surface finish is required. Advantages Plastiment is highly effective in hot weather concreting to offset the accelerat- ing effects of high ambient temperatures by slowing the hydration reaction and controlling the hydration heat. Concrete workability is enhanced and a supe- riorsurface finish is obtained. In mass concrete pours Plastiment controls temperature rise and reduces the risk of thermal cracking. ^ Initial set times are delayed, allowing time for proper placement and fin- ishing without cold joints in hot weather conditions. ^ Plastiment increases concrete density and delivers increased early and ultimate, compressive and flexural strengths. ^ For flatwork applications Plastiment acts as a finishing aid, workability is improved, bleeding is controlled and a superior surface finish is obtained. ^ Lower water cement ratios provide decreased permeability and increased durability.. ^ Plastiment can be used to retard concrete during the hot weather con- creting. Refer to ACI 305R Hot Weather Concreting for more information. Plastiment does not contain calcium chloride or any other intentionally added chlorides. Dosage rates will vary depending on the material used, ambient conditions and the requirements of a specific project. For general concreting applications, Sika recommends a dosage rate between 2-4 fl. oz./100 lbs. (130-260 ml/100 kg) of cementitious materials. Where extended retardation is required dosage may be increased. Dosage rates outside the recommended range may be used where specialized materi- als such as microsilica are specified, extreme ambient conditions are encoun- tered or unusual project conditions require special consideration. In this case please contact your local regional Sika office or Sika technical service department at 1-800-933-7452 for further information. Mixin ,~ 9 Add Plastiment at the concrete )ant. Measure re uired uantit manual) or P q q Y Y by automated dispenser. Add into the water line at the batch plant or directly - into the concrete at the end of the mixing cycle. ...: Combination with other Admixtures: Plastiment works effectively as a ~ single admixture or in combination with other admixtures in the Sika System. ~~" When used in combination with other admixtures, care must be taken to dis- pense each admixture separately into the mix. Do not mix with dry cement. Packaging .. Plastiment is supplied in 55 gallon (208 liter) drums and bulk delivery. Storage and Shelf-life Plastiment should be stored at above 40°F (5°C). If frozen, thaw and agitate thoroughly to return to normal state before use. '" ~; Shelf life when stored in dry warehouse conditions between 50°F and 80°F (10°C- 27°C) is one yeas Typical Data Appearance Flourescent Green Brown liquid. Specific Gravity Approx. 1.2 Caution Skin and eye irritant; avoid contact. The use of NIOSH approved respirator, safety goggles and rubber gloves is recommended. Avoid breathing product. Use with adequate ventilation. Remove contaminated clothing. Handling and Storage Avoid direct contact. Wear personal protective equipment (chemical resistant goggles/gloves/clothing) to prevent direct contact with skin and eyes. Use only in well ventilated areas. Wash thoroughly with soap and water after use. Remove contaminated clothing and launder before reuse. First Aid Eyes: Hold eyelids apart and flush thoroughly with water for 15 minutes. Skin: Remove contaminated clothing. Wash skin thoroughly for 15 minutes with soap and water. Inhalation: Remove person to fresh air. Ingestion: Do not induce vomiting. Dilute with water. Contact a physician. In all cases, contact a physician immediately if symptoms persist. Clean Up Use personal protective equipment (chemical resistant goggles/gloves/cloth- ing). Without direct contact, remove spilled or excess product and place in suitable sealed container. Dispose of excess product and container in accor- dance with applicable environmental regulations. KEEP CONTAINER TIGHTLY CLOSED KEEP OUT OF REACH OF CHILDREN NOT FOR INTERNAL CONSUMPTION FOR INDUSTRIAL USE ONLY CONSULT MATERIAL SAFETY DATA SHEET FOR MORE INFORMATION Sika warrants this product for one year from date of installation to be free from manufacturing defects and to meet the technical properties on the current Technical Data Sheet if used as directed within shelf life. User determines suitability of product for intended use and assumes all risks. Buyer's sole remedy shall be limited to the purchase price or replacement of product exclusive of labor or cost of labor. NO OTHER WARRANTIES EXPRESSED OR fMPLIED SHALLAPPLY INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SIKH SHALL NOT BE LIABLE UNDER ANY LEGAL THEORY FOR SPECIAL OR CONSEQUENTIAL DAMAGES. SIKA SHALL NOT BE RESPONSIBLE FOR THE USE OF THIS PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS HELD BY OTHERS. Sika Corporation Sika Canada Inc. 1-800-933-SIKA pUALl7y 201 Polito Avenue 601, Delmar Avenue Lyndhurst, NJ 07071 Pointe-Claire, QC H9R 4A9 t r ~ Phone: (201) 933-8800 Phone: (514) 697-2610 7 7 Fax: (201) 933-6225 Fax: (514) 697-3087 ik t ti ik q~H1EVEME~~ www.s acons ruc on.com www.s a.ca Regional Information and Sales Centers. For the location of your nearest Sika representative, contact your regional center. U.S.: North East Region: Fairless Hills, PA, Phone: (215) 295 -6600 North Central Region: Marion, OH, Phone: (BDO) 851-1545 South East Region: Conyers, GA, Phone: (770) 760-1300 South Central Region: Mesquite, TX, Phone: (972) 289-6480 Western Region: Santa Fe Springs, C A, Phone: (562) 903-3650 Canada: Ontario: Mississauga, ON, Phone: (905) 795-3177, Alberta: Edmonton, AB, Phone: (780) 486111 quality Certification Numbers: Lyndhurst: FM 69771 (ISO 9000), FM 70421 (QS 9000), Marion: FM 69715, Kansas City: FM 69107, Santa Fe Springs: FM 69408 Sika and Plastiment are registered trademarks. Made in USA. Printed in USA.