ST0701-LR100217CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0084 Irerracon Service Date: 02/02/10 8901 Carpenter Frwy. Report Date: 02/17/10 Revision 1 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix 1D: 1701 Supplier: Lattimore Batch Time: 0925 Plant: 6 Truck No.: 9114 Ticket No.: 6365462 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 4 1/2 3 -5 6.2 3 -6 58 44 143.2 Sample Date: 02/02/10 Sample Time: 1014 Sampled By: Michael W. Whyman Weather Conditions: Cloudy Accumulative Yards: 20 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal):20 Area Water Added After (gal): 0 Sample Location: Sta. 3 +20, Lane 2 and 3 Placement Location: SW Blvd, W Bound, Sta. 5 +60 to Sta. No. ID 6 +30 & Sta. 3 +10 to Sta. 3 +30 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 1 1 6.00 28.27 02/03/10 02/05/10 3 92,420 3,270 5 1 2 6.00 28.27 02/03/10 02/09/10 7 126,000 4,460 2 1 3 6.00 28.27 02/03/10 02/16/10 14 137,460 4,860 4 1 4 6.00 28.27 02/03/10 03/02/10 28 1 5 6.00 28.27 02/03/10 03/02/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required fie samples. Terracon Rep.: Michael W. Whyman Started: 0800 Reported To: Finished: 1230 Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX Reviewed By: (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Constntction (I) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5- 21.09, Rev.3 Page I of I Senior Project Manager CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 193.0089 f7 ' }:: r r, +,., + tv .., '` Service Date: 02 /05/10 8901 Carpenter Frwy. Report Date: 02/17/10 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project City of Coppell 'I'X Attn: Keith Marvin PO Box 9478 Coppell, TX 75019 Southwestern Boulevard Copped Road to Grapevine Creek Coppell, TX Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix 11): I)CS01-1504 Supplier: Redi -Mix Batch Time: 1421 Plant: 259 Truck No.: 1321 Ticket No.: 25161676 Field Test Data Test Slump (in): Air Content (' %o): Concrete Temp. (F): Ambient Temp. ((;): Plastic Unit Wt. (pct): Result Specification 3 3/4 3 -5 5.1 3 -6 62 54 147.1 Laboratory Test Data Sample Date: 02/05/10 Sample Time: 1520 Sampled By: Barry Cuble Weather Conditions: Sunny, light breeze Accumulative Yards: 16 Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal): 10 Water Added After (gal): 0 Sample Location: 5' S of N edge, 5' E of W edge Placement Location: Paving, W Bridge approach slab (27'x 02/06/10 20') Set Specimen Diameter Area Date Date No. 1 D (in) (sq in) Received Tested 1 1 6.00 28.27 02/06/10 02/12/10 1 2 6.00 28.27 02/06/10 02/19/10 1 3 6.00 28.27 02/06/10 03/05/10 1 4 6.00 28.27 02/06/10 03105110 Comments: Age at Maximum Test Load (days) (lbs) 7 128,430 14 28 28 Compressive Strength Fracture (Psi) Type 4,540 4 Samples Made 13y: Terracon Services: Obtain samples of fresh concrete at the placement locationq perform required field tests and cast compressive strength samples. Terracon Rep.: Barry Cubic Started: 1130 Reported To: Finished: 1730 Contractor: Lacy Construction Report Distribution: (1) City of Coppell Tx (1) City of Coppell TX Reviewed By: (1) City of Coppell Tx (2) Halff Assoc Inc (1) Lacy Conshuclion (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. ('10001.5-2 1- oo. Rev 3 Page 1 of I CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091194.0018 Service Date: 01/19/10 Report Date: 02/17/10 Revision 2 or n 8901 Carpenter Frwy. Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client Project PacTrust Pacific Realty Associates LP Southwestern Boulevard Attn: Matthew Oyen Grapevine Creek to Beltline Road 15350 Southwest Sequoia Pkwy Ste 300 Coppell, TX Portland, OR 97224 Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 01/19/10 Sample Time: 1448 Sampled By: Barry Cuble Mix ID: 1701 Weather Conditions: Partly sonny, light breeze Supplier: Lattimore Accumulative Yards: 6 Batch Size (cy): 6 Batch Time: 1402 Plant: 7 Placement Method: Direct Discharge Truck No.: 5030 Ticket No.: 7213987 Water Added Before (gal):5 Field Test Data Water Added After (gal): 0 Sample Location: See Placement Location Test Result Specification Placement Location: Inlet at B /5, Sta. 0 +29 Slump (in): 3 3 -5 Air Content ( %): 4.4 3 -6 Concrete Temp. (F): 71 Ambient Temp. (F): 70 Plastic Unit Wt. (pcf): 149.4 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 1 I 6.00 28.27 01/20/10 01/26/10 7 120,610 4,270 2 1 2 6.00 28.27 01/20/10 02/02/10 14 135,630 4,800 2 1 3 6.00 28.27 01/20/10 02/16/10 28 160,230 5,670 2 1 4 6.00 28.27 01/20/10 02/16/10 28 165,470 5,850 2 Average (28 days) 5,760 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast tCleved samples. Terracon Rep.: Barry Cuble Started: 1330 Reported To: Finished: 1600 Contractor: Lacy Construction Report Distribution: (1) PacTnisl Pacific Realty Associates LP (1) City of Coppell TX Reviewed By: (1) City of Coppell TX (2) Halff Assoc Inc Eric J (1) Lacy Construction Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5.21-09, Rev.3 Page I of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 194.0016 Terracon Service Date: 01115110 8901 Carpenter Frwy. Report Date: 02/17/10 Revision 2 Dallas, TX 75247 214- 630 -1010 Reg No:F -3272 Client PacTrust Pacific Realty Associates LP Attn: Matthew Oyen 15350 Southwest Sequoia Pkwy Ste 300 Portland, OR 97224 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 1701 Supplier: Lattimore Batch Time: 1439 Plant: 7 Truck No.: 1076 Ticket No.: 7213881 Field Test Data Test Slump (in): Air Content ('X.): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 2 1 /2 3.6 60 54 148.7 Laboratory Test Data Set Specimen Diameter Area No. ID (in) (sq in) I 1 6:00 28.27 I 2 6.00 28.27 I 3 6.00 28.27 I 4 6.00 28.27 Sample Date: 01115110 Sample Time: 1523 Sampled By: Barry Cuble Weather Conditions: Cloudy, light breeze Accumulative Yards: 7 Batch Size (cy): 7 Placement Method: Direct Discharge Water Added Before (gal):5 (lbs) Water Added After (gal): 0 Sample Location: See Placement Location Placement Location: Inlet Walls and Bottom at B /1, Sta. 14 1 +04; B /3, Sta. 0 +74 Compressive Age at Maximum Date Date Test Load Received Tested (days) (lbs) 01/16/10 01/22/10 7 170,260 01/16/10 01/29/10 14 185,630 01116110 02/12/10 28 199,840 01/16/10 02/12/10 28 200,720 Average (28 days) Compressive Strength Fracture (psi) Type 6,020 2 6,570 2 7,070 2 7,100 2 7,090 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made 11y: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and ca cot ressive strength samples. ,, _ �0 Terracon Rep.: [carry Cuble Started: 1500 Reported To: Finished: 1730 Contractor: Lacy Construction Report Distribution: (1) PacTrust Pucitic Really Associates LP (1) City ofCoppell TX Reviewed By: (1) City of Coppcll TX (2) Halff Assoc Inc Eri4KJ . a eland, P.E. (1) Lacy Construction Senior r ect Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cwxiut. i-21-01. R-,3 Page 1 of CONCRETE COMPRESSIVE STRENGTH TEST REPORT MW Em Report Nuniber: 94091 194.0032 'O N Fe g 1 p r Ica c a n Service Date: 02/05/10 8901 Carpenter Frwy. Report Date: 02/17/10 Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client PacTrust Pacific Realty Associates LP Attn: Matthew Oyen 15350 Southwest Sequoia Pkwy Ste 300 Portland, OR 97224 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi cCi 28 days Mix ID: 1701 Supplier: Lattimore Batch Time: 1330 Plant: 07 Truck No.: 5030 Ticket No.: 7214568 Field Test Data Test Slump (in): Air Content (' %o): Concrete Temp. (1 7 ): Ambient Temp. (1 7 ): Plastic Unit Wt. (pef): Result Specification 3 1/2 4.8 57 56 146.2 Laboratory Test Data Set Specimen Diameter No. ID (in) 1 1 6.00 1 2 6.00 1 3 6.00 1 4 6.00 Sample Date: 02/05/10 Sample Time: 1440 Sampled By: Mario A.Garcia Weather Conditions: Partly cloudy Accumulative Yards: 9 Batch Size (cy): 9 Placement Method; Bucket Water Added Before (gal): 10 Water Added After (gal): 0 Sample Location: See Placement Location Placement Location: Box Culvert, (2) at Sta. 10 +38 & Sta. 02/06/10 20 +00 Age at Area Date Date Test (sq in) Received Tested (days) 28.27 02/06/10 02/12/10 7 28.27 02/06/10 02/19/10 14 28.27 02/06/10 03/05/10 28 28.27 02/06/10 03/05/10 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 124,310- 4,400 4 Comments: Samples Made 13y: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast ompressive strength samples. Terracon Rep.: Mario A.Garcia Started: 1300 Reported To: Finished: 1530 Contractor: Lacy Construction Report Distribution: (1) PICT1'n %1 Pacific Really Associates LP (1) City ofCoppell TX Reviewed By: (1) City of Coppell T\ (2) Halff Assoc Inc tC . CleV land, P.E. (1) Lacy Consn,iclion Senior Projec Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Cluxun. I- ao.Ite.•.J Page I of