ST0701-LR100305 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091194.0032 'Terror ,.. . Service Date: 02/05/10 8901 Carpenter Frwy. Report Date: 03/05/10 Revision 2 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project PacTrust Pacific Realty Associates LP Southwestern Boulevard Attn: Matthew Oyen Grapevine Creek to Beltline Road 15350 Southwest Sequoia Pkwy Ste 300 Coppell, TX Portland, OR 97224 Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 02/05/10 Sample Time: 1440 Sampled By: Mario A.Garcia Mix ID: 1701 Weather Conditions: Partly cloudy Supplier: Lattimore Accumulative Yards: 9 Batch Size (cy): 9 Batch Time: 1330 Plant: 07 Placement Method: Bucket Truck No.: 5030 Ticket No.: 7214568 Water Added Before (gal):10 Water Added After (gal): 0 Field Test Data Sample Location: See Placement Location Test Result Specification Placement Location: Box Culvert, (2) at Sta. 10 +38 & Sta. Slump (in): 3 1/2 20+00 Air Content ( %): 4.8 Concrete Temp. (F): 57 Ambient Temp. (F): 56 Plastic Unit Wt. (pcf): 146.2 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (Ibs) (psi) Type 1 1 6.00 28.27 02/06/10 02/12/10 7 124,310 4,400 4 1 2 6.00 28.27 02/06/10 02/19/10 14 153,390 5,430 2 1 3 6.00 28.27 02/06/10 03/05/10 28 157,420 5,570 2 1 4 6.00 28.27 02/06/10 03/05/10 28 167,550 5,930 2 Average (28 days) 5,750 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and c.: compres ive • ength samples. Terracon Rep.: Mario A.Garcia Started: 1300 Reported To: Finished: 1530 Contractor: Lacy Construction Report Distribution: Reviewed By: (I) PacTrust Pacific Realty Associates LP (1) City of Coppell TX (1) City of Coppell TX (2) Halff Assoc Inc Eric J. Cle eland, P.E. (I) Lacy Construction Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 CR0001, 5-21-09, Rev .3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0089 Irerracon Service Date: 02/05/10 8901 Carpenter Frwy. Report Date: 03/05/10 Revision 2 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Specified Strength: 4,000 psi @ 28 days Mix ID: DCSOHSO4 Supplier: Redi -Mix Batch Time: 1421 Plant: 259 Truck No.: 1321 Ticket No.: 25161676 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 33/4 3 -5 5.1 3 -6 62 54 147.1 Laboratory Test Data Sample Information Sample Date: 02/05/10 Sample Time: 1520 Sampled By: Barry Cuble Weather Conditions: Sunny, light breeze Accumulative Yards: 16 Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal): 10 Water Added After (gal): 0 Sample Location: YS of N edge, 5'E of W edge Placement Location: Paving, W Bridge approach slab (27'x 20') Age at Maximum Set Specimen Diameter Area Date Date Test Load No. ID (in) (sq in) Received Tested (days) (lbs) 1 1 6.00 28.27 02/06/10 02/12/10 7 128,430 1 2 6.00 28.27 02/06/10 02/19/10 14 146,980 1 3 6.00 28.27 02/06/10 03/05/10 28 156,120 1 4 6.00 28.27 02/06/10 03/05/10 28 170,880 Average (28 days) Compressive Strength Fracture (psi) Type 4,540 4 5,200 6 5,520 4 6,040 2 5,780 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Barry Cuble Started: 1130 Reported To: Finished: 1730 Contractor: Lacy Construction Report Distribution: Reviewed By: (1) City of Coppell TX (1) City of Coppell TX (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 5- 21 -09, Rev.3 Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0098 Irerracon Service Date: 02/19/10 8901 Carpenter Frwy. Report Date: 03/05/10 Revision 1 Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: DCCOG504 Supplier: Redi -Mix Batch Time: 1434 Plant: 136 Truck No.: 1184 Ticket No.: 25164735 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 5 1/4 3 -5 5.2 3 -6 60 47 148.6 Laboratory Test Data Set Specimen Diameter Area Date No. ID (in) (sq in) Received 1 1 6.00 28.27 02/20/10 1 2 6.00 28.27 02/20/10 1 3 6.00 28.27 02/20/10 1 4 6.00 28.27 02/20/10 Sample Date: 02/19/10 Sample Time: 1513 Sampled By: Barry Cuble Weather Conditions: Overcast, breezy Accumulative Yards: 5 Batch Size (cy): 5 Placement Method: Direct Discharge Water Added Before (gal):0 Water Added After (gal): 0 Sample Location: See Placement Location Placement Location: Bridge Span #3 Rail Age at Maximum Date Test Load Tested (days) (lbs) 02/26/10 7 130,640 03/05/10 14 154,040 03/19/10 28 03/19/10 28 Compressive Strength Fracture (psi) Type 4,620 5,450 2 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and samples. Terracon Rep.: Barry Cuble Started: 1230 / Reported To: Finished: 1600 Contractor: Lacy Construction Report Distribution: Reviewed By: (1) City of Coppell TX (1) City of Coppell TX (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 5- 21 -09, Rev.3 Page 1 of 1