Duke Lesley 3A-LR100311Ro n e Engineering 7701 8908 Ambassador Row, Dallas, TX 75247 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements (inches) Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 01/20/2010 ASTM C -31 (except 10.1.2) 1.6% Unit Weight (pcf): NA ASTM C -143 Overall Placement Location: ASTM C -231 Parking expansion /paving, ASTM C -1064 (center curb) ASTM C -138 02/10/2010 ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Clear (inches) Time Sampled: 05:30am Batch time: 04:54am 6.0 Temperature - Air: 30 °F Concrete: 46 °F (in) Truck No: 9105 Ticket No: 3272775 01/20/2010 Air Content: 1.6% Unit Weight (pcf): NA 28.27 Overall Placement Location: 02/10/2010 Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) 1 3 02/10/2010 Sample Location: 2nd island from side street, center curb, 2' south, T west REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Compressive Load Strength Marked Date Age Diameter Area Set No. Tested (days) (in) (in') 1 1 01/20/2010 7 6.00 28.27 1 2 02/10/2010 28 6.00 28.27 1 3 02/10/2010 28 6.00 28.27 1 4 03/10/2010 56 6.00 28.27 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 114,610 4,050 Type 5 157,970 5,590 Type 2 151,270 5,350 Type 2 Average 5,470 172,420 6,100 Type 2 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 1 of 12 8908 Ambassador Row, Dallas, TX 75247 R o n e Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 ASTM C -31 (except 10.1.2) (center curb) ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Partly cloudy (inches) Time Sampled: 06:20am Batch time: 05:25am 6.0 Temperature - Air: 30 °F Concrete: 44 °F 3,770 Type 6 Truck No: 1049 Ticket No: 3272778 Type 2 Air Content: 1.4% Unit Weight (pcf): NA Overall Placement Location: Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) Sample Location: 2nd island from side street, 8' south, 7' west from center curb T4961 i9612MA &i Concrete Compressive Cylinder 6" x 12" 4,720 Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 2 1 01/20/2010 7 6.00 28.27 106,690 3,770 Type 6 2 2 02/10/2010 28 6.00 28.27 133,320 4,720 Type 5 2 3 02/10/2010 28 6.00 28.27 127,670 4,520 Type 2 Average 4,620 2 4 03/10/2010 56 6.00 28.27 137,580 4,870 Type 2 Ud �-�d �] [ILI r Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 3 of 12 R o n e Engineering 7701 8908 Ambassador Row, Dallas, TX 75247 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements 6.25 Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 Parking expansion /paving, paving starting from Dividend and going to the 2nd island ASTM C -31 (except 10.1.2) (in =) ASTM C -143 (psi) ASTM C -231 3 1 ASTM C -1064 7 ASTM C -138 28.27 ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Partly cloudy (inches) Time Sampled: 07:27am Batch time: 06:31 am 6.25 Temperature - Air: 30 °F Concrete: 45 °F Date Truck No: 5016 Ticket No: 7213746 Diameter Air Content: 1.1% Unit Weight (pcf): NA Load Overall Placement Location: Fracture Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) (in =) Sample Location: 1st entrance from side street island. 15' north. 5' east Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in =) (Ibs) (psi) Type 3 1 01/20/2010 7 6.00 28.27 97,250 3,440 Type 2 3 2 02/10/2010 28 6.00 28.27 125,000 4,420 Type 2 3 3 02/10/2010 28 6.00 28.27 128,650 4,550 Type 5 Average 4,490 3 4 03/10/2010 56 6.00 28.27 133,960 4,740 Type 5 H 2 F 1� Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 5 of 12 8908 Ambassador Row, Dallas, TX 75247 R o n e Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 3012 Ticket No: 7213753 ASTM C -31 (except 10.1.2) Air Content: ASTM C -143 Load ASTM C -231 Fracture ASTM C -1064 paving starting from Dividend and going to the 2nd island ASTM C -138 (in) ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Partly cloudy (inches) Time Sampled: 08:30am Batch time: 07:25am 5.25 Temperature - Air: 30 °F Concrete: 48 °F Truck No: 3012 Ticket No: 7213753 Age Air Content: 1.5% Unit Weight (pcf): NA Load Overall Placement Location: Fracture Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) (in) (in') Sample Location: Southeast corner curb, 2' north, 3' west REPORT OF TESTS �l If Ll C I,_._J r l Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 7 of 12 Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 4 1 01/20/2010 7 6.00 28.27 130,640 4,620 Type 2 4 2 02/10/2010 28 6.00 28.27 164,370 5,810 Type 5 4 3 02/10/2010 28 6.00 28.27 168,750 5,970 Type 2 Average 5,890 4 4 03/10/2010 56 6.00 28.27 171,710 6,070 Type 2 �l If Ll C I,_._J r l Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 7 of 12 8908 Ambassador Row, Dallas, TX 75247 Ro n e Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) Parking expansion /paving, paving starting from Dividend and going to the 2nd island ASTM C -143 Ld ASTM C -231 Type 1 ASTM C -1064 Type 4 ASTM C -138 ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Partly cloudy (inches) Time Sampled: 10:45am Batch time: 09:46am 6.5 Temperature - Air: 38 °F Concrete: 46 °F 4,460 Type 5 Truck No: 7060 Ticket No: 7213768 Average 5,860 Air Content: 1.2% Unit Weight (pcf): NA 03/10/2010 Overall Placement Location: 6.00 28.27 162,880 5,760 Type 5 Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) Ld Sample Location: Southwest corner, 9' north, 2' east REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 02/10/2010 Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (In) (in =) (Ibs) (psi) Type 5 1 01/20/2010 7 6.00 28.27 126,030 4,460 Type 5 5 2 02/10/2010 28 6.00 28.27 168,110 5,950 Type 5 5 3 02/10/2010 28 6.00 28.27 163,520 5,780 Type 5 Average 5,860 5 4 03/10/2010 56 6.00 28.27 162,880 5,760 Type 5 f �J IM � ] 2 Ld 1111 C.__I Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 9 of 12 8908 Ambassador Row, Dallas, TX 75247 Ro n e Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas. TX 75254 -2936 Report No.: 366256 Project No.: 0915747 Date of Service: 01/13/2010 Report Date: 03/11/2010 Project: Samsung -Point West VII Parking Lot Expansion Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Ia:Zir1x02ILAI_1 Contractor: Duke Construction, LP Concrete Supplier: LMC Plant: 3 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air ( %): NA Test Method: ASTM C -172 ASTM C -31 (except 10.1.2) (center curb) ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 Mix Design I.D.: 1621 Measured Placement Date: 01/13/2010 Slump Weather Conditions: Partly cloudy (inches) Time Sampled: 12:45pm Batch time: 12:14pm 6.0 Temperature - Air: 45 °F Concrete: 54 °F 4,640 Type 5 Truck No: 3012 Ticket No: 7213785 Type 5 Air Content: 1.0% Unit Weight (pcf): NA Overall Placement Location: Parking expansion /paving, paving starting from Dividend and going to the 2nd island (center curb) Sample Location: Northwest corner curb, 2' south, 2' east REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" 5,370 Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 6 1 01/20/2010 7 6.00 28.27 131,320 4,640 Type 5 6 2 02/10/2010 28 6.00 28.27 151,730 5,370 Type 2 6 3 02/10/2010 28 6.00 28.27 166,350 5,880 Type 2 Average 5,620 6 4 03/10/2010 56 6.00 28.27 159,840 5,650 Type 5 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW /KW) Page 11 of 12