Loading...
ST0701-LR100204CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerrocan Report Number: 94091194.0020 Service Date: 01/20/10 8901 Carpenter Frwy. Report Date: 02/04/10 Revision 1 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project PaCTruSt Pacific Realty Associates LP Southwestern Boulevard Attn: Matthew Oyen Grapevine Creek to Beltline Road 15350 Southwest Sequoia Pkwy Ste 300 Coppell, TX Portland, OR 97224 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive stren samples. Terracon Rep.: Barry Cuble Started: 1300 Reported To: Finished: 1600 Contractor: Lacy Construction Report Distribution: Reviewed By: ( I) Pac Frost Pacific Realty Associates LP (1) City of Coppell TX (1) Ciiy of Coppell TX (2) Halff Assoc Inc Eric J. Cleveland, P.E. (1) Lacy Construction Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001. 5- 21 -09. Rm3 Page I of 1 Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 01/20/10 Sample Time: 1459 Sampled By: Barry Cuble Mix 1D: 1701 Weather Conditions: Partly sunny, light breeze Supplier: Lattimore Accumulative Yards: 6 Batch Size (cy): 6 Batch Time: 1405 Plant: 7 Placement Method: Direct Discharge Truck No.: 3012 Ticket No.: 7218054 Water Added Before (gal): 10 Water Added After (gal): 0 Field Test Data Sample Location: See Placement Location Test Result Specification Placement Location: Inlet Walls at B /2, Sta. 0 +31.2 and Inlet Slump (in): 3 1/4 Top Air Content ( %): 3.8 Concrete Temp. (F): 74 Ambient Temp. (F): 71 Plastic Unit Wt. (pcf): 147.8 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 1 1 6.00 28.27 01/21/10 01/27/10 7 134,810 4,770 2 1 2 6.00 28.27 01/21/10 02/03/10 14 150,230 5,310 2 1 3 6.00 28.27 01/21/10 02/17/10 28 1 4 6.00 28.27 01/21/10 02/17/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive stren samples. Terracon Rep.: Barry Cuble Started: 1300 Reported To: Finished: 1600 Contractor: Lacy Construction Report Distribution: Reviewed By: ( I) Pac Frost Pacific Realty Associates LP (1) City of Coppell TX (1) Ciiy of Coppell TX (2) Halff Assoc Inc Eric J. Cleveland, P.E. (1) Lacy Construction Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001. 5- 21 -09. Rm3 Page I of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0070 Irerrocan Service Date: 01/20/10 8901 Carpenter Frwy. Report Date: 02/04/10 Revision 1 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ Mix ID: DCSOHSO4 Supplier: Redi -Mix Batch Time: 0947 Plant: Truck No.: H89 Ticket No Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): 28 days 136 25156629 Sample Date: 01/20/10 Sample Time: 1019 Sampled By: Christopher P. Moran Weather Conditions: Overcast Accumulative Yards: 10 Batch Size (cy): 10 Placement Method: Pump Water Added Before (gal):10 6.00 Water Added After (gal): 0 Sample Location: Sta. 14 +10 Placement Location: Bridge Deck, East bound, Sta. 14 +02 to 7 Sta. 14 +47 Result Specification 5 3 -5 5.1 3 -6 66 62 145.1 Laboratory Test Data Set Specimen Diameter No. ID (in) 1 l 6.00 1 2 6.00 1 3 6.00 1 4 6.00 1 5 6.00 ments: Samples Made By: Terracon Age at Maximum Area Date Date Test Load (sq in) Received Tested (days) (lbs) 28.27 01/21/10 01/22/10 2 75,240 28.27 01/21/10 01/27/10 7 138,600 28.27 01/21/10 02/03/10 14 149,950 28.27 01/21/10 02/17/10 28 28.27 01/21/10 02/17/10 28 Compressive Strength Fracture (psi) Type 2,660 5 4,900 2 5,300 4 Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 0900 Reported To: Finished: 1400 Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX Reviewed By: (I) City or Coppell TX (2) Halff Assoc Inc Eric J. QIeveland, P.E. (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5- 21 -09. 11 -3 Page I of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091194.0022 Irerracan Service Date: 01/21/10 8901 Carpenter Frwy. Report Date: 02/04/10 Revision 1 Dallas, TX 75247 214 - 630 -1010 Reg No:F -3272 Client PacTrust Pacific Realty Associates LP Attn: Matthew Oyen 15350 Southwest Sequoia Pkwy Ste 300 Portland, OR 97224 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: 1701 Supplier: Lattimore Batch Time: 1327 Plant: 3 Truck No.: 9142 Ticket No.: 3273227 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 2 1/2 3.0 62 62 144.0 Laboratory Test Data Set Specimen Diameter No. ID (in) 1 1 6.00 1 2 6.00 1 3 6.00 1 4 6.00 Sample Date: 01/21/10 Sample Time: 1427 Sampled By: Burl E. Thomas Weather Conditions: Clear Accumulative Yards: 8 Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal):0 Water Added After (gal): 0 Sample Location: Approximately 50'W of west curb of 14 Belt Line Road Placement Location: Inlet top, eastbound Southwestern 28 Boulevard Age at Area Date Date Test (sq in) Received Tested (days) 28.27 01/22/10 01/28/10 7 28.27 01/22/10 02/04/10 14 28.27 01/22/10 02/18/10 28 28.27 01/22/10 02/18/10 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 136,140 4,820 4 152,420 5,390 2 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Burl E. Thomas Started: 1230 Reported To: Mr. O'Dell Finished: 1600 Contractor: Lacy Construction Report Distribution: (1) PacTnlst Pacific Realty Associates LP (1) City ofCoppell TX Reviewed By: (1) City ofCoppell TX (2) Halff Assoc Inc (1) Lacy Construction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOOI, 5- 21 -09, Rm3 Page I of I CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0071 Irerracan Service Date: 01/20/10 8901 Carpenter Frwy. Report Date: 02/04/10 Revision 1 Dallas, TX 75247 214- 630 -1010 Reg No:F -3272 Client Project City of Coppell TX Attn: Keith Marvin PO Box 9478 Coppell, TX 75019 Material Information Specified Strength: 3,000 psi @ 28 days Mix ID: DCB0C01 Supplier: Redi -Mix Batch Time: 1141 Plant: 136 Truck No.: 1189 Ticket No.: 25156768 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 6 2.8 65 66 149.3 Proiect Number: 94091193 Southwestern Boulevard Coppell Road to Grapevine Creek Coppell, TX Sample Information Sample Date: 01/20/10 Sample Time: Sampled By: Christopher P. Moran Weather Conditions: Overcast Accumulative Yards: 10 Batch Size (ey): Placement Method: Pump Water Added Before (gal):0 No. ID Water Added After (gal): 0 Sample Location: See Placement Location Placement Location: Riprap, SE side of bridge Laboratory Test Data Strength Fracture (lbs) (psi) Type 103,120 Age at Set Specimen Diameter Area Date Date Test No. ID (in) (sq in) Received Tested (days) 1 1 6.00 28.27 01/21/10 01/27/10 7 l 2 6.00 28.27 01/21/10 02/03/10 14 l 3 6.00 28.27 01/21/10 02/17/10 28 I 4 6.00 28.27 01/21/10 02/17/10 28 Comments: Maximum Compressive 1206 10 Load Strength Fracture (lbs) (psi) Type 103,120 3,650 2 112,110 3,970 4 Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples, Terracon Rep.: Christopher P. Moran Reported To: Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX Reviewed B y : (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Constnlclion (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5- 21 -09, 11- 3 Page I of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerracon Report Number: 94091 193.0080 Service Date: 01/27/10 8901 Carpenter Frwy. Report Date: 02/04/10 Dallas, TX 75247 214 - 630 -1010 Reg No:F -3272 Client Project City of Coppell TX Attn: Keith Marvin PO Box 9478 Coppell, TX 75019 Southwestern Boulevard Coppell Road to Grapevine Creek Coppell, TX Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi c@ 28 days Sample Date: 01/27/10 Sample Time: 1123 Sampled By: Barry Cuble Mix ID: DCCOG504 Weather Conditions: Cloudy, breezy Supplier: Redi -Mix Accumulative Yards: 5 Batch Size (cy): 5 Batch Time: 1044 Plant: 136 Placement Method: Bucket Truck No.: 1 186 Ticket No.: 25159904 Water Added Before (gal):0 Water Added After (gal): 0 Field Test Data Sample Location: See Placement Location Test Result Specification Placement Location: Wing Wall at south side, east and west Slump (in): 4 1/2 3 -5 walls Air Content (' %r): 4.8 3 -6 Concrete Temp. (F): 62 Ambient Temp. (F): 53 Plastic Unit Wt. (pcf): 150.7 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 1 1 6.00 28.27 01/28/10 02/03/10 7 143,280 5,070 2 1 2 6.00 28.27 01/28/10 02/10/10 14 1 3 6.00 28.27 01/28/10 02/24/10 28 1 4 6.00 28.27 01/28/10 02/24/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations perform required field tests and cast compressive strength samples. Terracon Rep.: Barry Cubic Started: 0900 Reported To: Finished: 1600 Contractor: Lacy Construction Report Distribution: (1) City of Coppell Tx (1) City of Coppell TX Reviewed By: (1) City ol'Coplxll'I'x (2) Halff Assoc hic (1) Lacy Cunslructinn (1) PncTrust Pacific Really Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. cRwert..- zt.rn), lie,•.: Page 1 of I REINFORCING 10 9 STEE OBSERVATIONS REPORT il Werracon Service Date: 02/02/10 8901 Carpenter Frwy. Report Date: 02/04/10 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 PROJECT DATA Drawings Utilized: SC1.27 Locations /Items Observed: Bridge Paving Approach — East end Test ]Method: Visual Observation REPORT OF OBSERVATION ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT Placing Drawings Approved X Bar Length and Shape X Column Tie Spacing & Type Bar Size X Proper Bar Placement X Stirrup Spacing & Type X Bar Grade X Properly Tied X Welded Splices Rebar Clean X Dowel Bars In Place X Mechanical Splices Trash & Debris Removed X Proper Bar Supports X Lapped Splices X Number of Bars X Proper Cover /Clearance X Discrepancies /Comments: Any discrepancies found were corrected prior to completion of this observation. 1. Top reinforcing steel bar at north edge was not properly tied. 2. Reinforcing steel bars at east end were not properly supported. Services: Reinforcing steel (rebar) placement observation. Terracon Rep.: Barry Cuble Reported To: Contractor: Lacy Construction Report Distribution: (1) City ul' Coppcll'I S (1) City of Coppell TX (1) Lacy Coustructirm (1) City of Coppell TX (2) 1 -Ialff Assoc Inc Reviewed By: (1) Pac "trust Pacific Realty Associates LP The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client Indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page I of I dgr Senior Project Manager