ST0701-LR100121LABORATORY COMPACTION CHARACTERISTICS OF SOIL REPORT Report Number:94091 194.0012 Ireirrocan Service Date: 01/12/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214 - 630 - 1010 Reg No: F -3272 Client PacTrust Pacific Realty Associates LP Attn: Matthew Oyen 15350 S011thwest Sequoia Pkwy Ste 300 Portland, OR 97224 Material Information Source of Material: Treated on site Proposed Use: Paving subgrade Laboratory Test Data Test Procedure: ASTM D698 Test Method: Method A Sample Preparation: Wet Rammer Type: Mechanical Maximum Dry Unit Weight (pcf):88.1 Optimum Water Content (' %r; 30.2 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Project Number 94091194 Sample Information Sample Date: 01/12/10 Sampled By: Francisco J. Morillo Sample Location: Eastbound, Southwestern Blvd., Sta. 17 +50 Sample Description: Brown clay (lime treated) Result Specifications Liquid Limit: 44 Plastic Limit: 36 Plasticity Index: 8 90 89 Zero Air Voids Curve for Assumed Specific Gravity 2.65 v- U 88 a 87 L 86 _m Q 85 _ 84 C 83 D T 82 O 81 80 33 34 35 36 37 3 Water Content ( %) Comments: Services: Moisture- Density Relations Terracon Rep:Francisco J. Morillo Reported To: Contractor: Lacy Construction Report Distribution: ( I ) Paerrusl Pacific Really Assuciutes LP (I) City ol'Coppell TX (1) City oI Coppell'fx (2) Hilff Assoc Inc (1) Lacy Cunslruction Reviewed By: Eric J. Clevela d, P.E. Senior Project Wage: Test Methods: ASTM D698, ASTM D4318 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the clie indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicabl to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CONCRETE COMPRESSIVE STRENGTH TEST REPORT 11111111 1011111 Report Number: 94091 194.0013 lFerracon Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214- 630 -10 10 Reg No:F -3272 Client Project PacTrust Pacific Realty Associates LP Southwestern Boulevard Attn: Matthew Oyen Grapevine Creek to Beltline Road 15350 Southwest Sequoia Pkwy Ste 300 Coppell, TX Portland, OR 97224 Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: Supplier: Batch Time: Plant: Truck No.: Ticket No.: Field Test Data Test Slump (in): Air Content Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 23/4 1 -3 6.5 3 -6 60 53 147.7 Laboratory Test Data Set Specimen Diameter Area Date No. ID (in) (sq in) Received 1 1 6.00 28.27 01/14/10 1 2 6.00 28.27 01/14/10 1 3 6.00 28.27 01/14/10 1 4 6.00 28.27 01/14/10 Sample Date: 01/13/10 Sample Time: 1400 Sampled By: Christopher P. Moran Weather Conditions: Overcast, windy Accumulative Yards: Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal):0 Water Added After (gal): 0 Sample Location: Sta. 23 +00 Placement Location: Paving, east of bridge from Sta. 15 +50 to Sta. 23 +00 Maximum Age at Date Test Tested (days) 01/20/10 7 01/27/10 14 02/10/10 28 02/10/10 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 143,840 5 2 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locationq perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) PIIcTrusl Pacific Realty Associnlcs LP (1) Cily of Coppell TX (1) Cily ol'Coppell 'I'X (2) Halff Assoc Inc (1) Lacy Constmelion Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 4 CR111111I. + -? 1 •09, Rcv.3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 194.0013 Service Date: 01/13/10 Report Date: 01/21/10 terracon 8901 Carpenter Frwy. Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client Project PacTI - USt Pacific Realty Associates LP Southwestern Boulevard Attn: Matthew Oyen Grapevine Creek to Beltline Road 15350 Southwest Sequoia Pkwy Ste 300 Coppell, TX Portland, OR 97224 Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 01/13/10 Sample Time: 1429 Sampled By: Christopher P. Moran Mix ID: Weather Conditions: Overcast, windy Supplier: Accumulative Yards: Batch Size (cy): 8 Batch Time: Plant: Placement Method: Direct Discharge Truck No.: Ticket No.: Water Added Before (gal):0 Water Added After (gal): 0 Field Test Data Sample Location: Sta. 21 +25 Test Result Specification Placement Location: Paving, east of bridge from Sta. 15 +50 Slump (in): 3 1 -3 to Sta. 23 +00 Air Content 5.9 3 -6 Concrete Temp. (F): 58 Ambient Temp. (F): 50 Plastic Unit Wt. (pcf): 149.6 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 2 1 6.00 28.27 01/14/10 01/20/10 7 156,620 5,540 2 2 2 6.00 28.27 01/14/10 01/27/10 14 2 3 6.00 28.27 01/14/10 02/10/10 28 2 4 6.00 28.27 01/14/10 02/10/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) NcTrasl Pneilic Realty Associates LP (1) City of Coppell TX (1) City of Coppcll'I'x (2) HnlfrAssoc Inc (1) Lacy Construction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRM)1, 5- 21 -09. Iter.3 Page 2 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 194.0013 Iterracon Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214 - 630 -1010 Reg No: F -3272 Client PacTrust Pacific Realty Associates LP Attn: Matthew Oyen 15350 Soutliwest Sequoia Pkwy Ste 300 Portland, OR 97224 4,000 psi r@ 28 days Project Number: 94091194 Material Information Sample Information Specified Strength Mix ID: Supplier: Batch Time: Truck No.: Field Test Data Test Slump (in): Air Content ( %,): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pct): Plant: Ticket No.: Result Specification 2 1 -3 6.4 3 -6 58 50 149.1 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Sample Date: 01/13/10 Sample Time: 1532 Sampled By: Christopher P. Moran Weather Conditions: Overcast, windy Accumulative Yards: Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal):0 Water Added After (gal): 0 Sample Location: Sta. 19 +10 Placement Location: Paving, east of bridge from Sta. 15 +50 to Sta. 23 +00 Laboratory Test Data Set Specimen No. I D Com Diameter Area Date Date (sq in) Received (in) Tested 28.27 01/14/10 6.00 01/20/10 28.27 01/14/10 6.00 01/27/10 28.27 01/14/10 6.00 02/10/10 28.27 01/14/10 6.00 02/10/10 Samples Made By: Terracon Age at Test (days) 7 14 28 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 151,030 5,340 2 Services: Obtain samples of fresh concrete at the placement locations perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) PNcTnist PNcilic Really Associates LP (1) City orCoppell TX (1) City orcoppcll Tx (2) HNIff Assoc Inc (1) Lacy Construction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRINNIL 3-21-09. RUV.I Page 3 of 4 Samples Made By: Terracon Age at Test (days) 7 14 28 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type 151,030 5,340 2 Services: Obtain samples of fresh concrete at the placement locations perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) PNcTnist PNcilic Really Associates LP (1) City orCoppell TX (1) City orcoppcll Tx (2) HNIff Assoc Inc (1) Lacy Construction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRINNIL 3-21-09. RUV.I Page 3 of 4 Services: Obtain samples of fresh concrete at the placement locations perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) PNcTnist PNcilic Really Associates LP (1) City orCoppell TX (1) City orcoppcll Tx (2) HNIff Assoc Inc (1) Lacy Construction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CRINNIL 3-21-09. RUV.I Page 3 of 4 Area (sq in) 28.27 Date 01/14/10 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Irerracon Report Number: 94091 194.0013 Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214 - 630 -1010 Reg No:F -3272 Client PaCT Pacific Realty Associates LP Attn: Matthew Oyen 15350 Southwest Sequoia Pkwy Ste 300 Portland, OR 97224 Project Southwestern Boulevard Grapevine Creek to Beltline Road Coppell, TX Project Number: 94091194 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: Supplier: Batch Time: Plant: Truck No.: Ticket No.: Field Test Data Test Slump (in): Air Content ( %,): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Result Specification 3 1 -3 6.3 3 -6 58 49 148.1 Sample Date: 01/13/10 Sample Time: 1641 Sampled By: Christopher P. Moran Weather Conditions: Overcast, windy Accumulative Yards: 400 Batch Size (cy): 6 Placement Method: Direct Discharge Water Added Before (gal):0 Water Added After (gal): 0 Sample Location: Sta. 17 +25 Placement Location: Paving, east of bridge from Sta. 15 +50 28.27 to Sta. 23 +00 Laboratory Test Data Compressive Load Strength Fracture Age at Set Specimen Diameter Area Date Date Test No. I D (in) (sq in) Received Tested (days) 4 1 6.00 28.27 01/14/10 01/20/10 7 4 2 6.00 28.27 01/14/10 01/27/10 14 4 3 6.00 28.27 01/14/10 02/10/10 28 4 4 6.00 28.27 01/14/10 02/10/10 28 Comments: Maximum Compressive Load Strength Fracture (lbs) (psi) Type 144,890 5,120 2 Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement location$ perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 1330 Reported To: Finished: 1800 Contractor: Lacy Construction Report Distribution: (1) PacTrust Pacific Really Assoclntes LP (1) City of Coppell TX Reviewed By : (1) City of Coppell Tx (2) Halff Assoc Inc (1) Lacy Comirtiction Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. i'tuunn. 5.21 -rn9. a�' i Page 4 of 4 Senior Project Manager CONCRETE COMPRESSIVE STRENGTH TEST REPORT am Report Number: 94091 193.0064 'InFerracon Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214 - 630 - 1010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard AUn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Sample Information 1 Specified Strength: 4,000 psi @ 28 days Sample Date: 01/13/10 Sample Time: 0958 Sampled By: Christopher P. Moran Mix ID: Weather Conditions: Sunny, light breeze Supplier: Lacy Accumulative Yards: 16 Batch Size (cy): 8 Batch Time: Plant: Placement Method: Direct Discharge Truck No.: Ticket No.: Water Added Before (gal):0 Water Added After (gal): 0 Field Test Data Sample Location: Sta. 12 +60 Test Result Specification Placement Location: Paving from Sta. 7 +25 to Sta. 12 +60, Slump (in): 4 1 -3 west of bridge Air Content (' %,): 9.2 3 -6 Concrete Temp. (F): 52 Ambient Temp. (F): 46 Plastic Unit Wt. (pct): 142.1 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (Ibs) (psi) Type 1 1 6.00 28.27 01/14/10 01/20/10 7 135,440 4,790 2 1 2 6.00 28.27 01/14/10 01/27/10 14 1 3 6.00 28.27 01/14/10 02/10/10 28 1 4 6.00 28.27 01/14/10 02/10/10 28 Comments: Samples Made By: Teri Services: Obtain samples of fresh concrete at the placement location4 perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 0800 Reported To: Alfredo, Lacy Construction Finished: 1330 Contractor: Lacy Construction Report Distribution: (1) City of C'appcll 'I'x (1) City of Coppell TX (1) City nl'Cuppcll 'I'X (2) Halff Assoc Inc (1) Lacy Conxunctio„ (1) PacTntst Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page I of 3 CItUOU 1. 5.21 -U9, Rcv.7 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 193.0064 lVerracon Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client Project City of Coppell TX Attn: Keith Marvin PO Box 9478 Coppell, TX 75019 Southwestern Boulevard Coppell Road to Grapevine Creek Coppell, TX Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 01/13/10 Sample Time: 1055 Sampled By: Christopher P. Moran Mix ID: Weather Conditions: Sunny, light breeze Supplier: Lacy Accumulative Yards: Batch Size (cy): 8 Batch Time: Plant: Placement Method: Direct Discharge Truck No.: Ticket No.: Water Added Before (gal):0 Water Added After (gal): 0 Field Test Data Sample Location: Sta. 10 +25 Test Result Specification Placement Location: Paving from Sta. 7 +25 to Sta. 12 +60, Slump (in): 3 1 -3 west of bridge Air Content ( %,): 5.0 3 -6 Concrete Temp. (F): 57 Ambient Temp. (F): 48 Plastic Unit Wt. (pcf): 151.0 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 2 1 6.00 28.27 01/14/10 01/16/10 3 108,890 3,850 5 2 2 6.00 28.27 01/14/10 01/20/10 7 130,560 4,620 2 2 3 6.00 28.27 01/14/10 01/27/10 14 2 4 6.00 28.27 01/14/10 02/10/10 28 2 5 6.00 28.27 01/14/10 02/10/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement location4 perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Started: 0800 Reported To: Alfi•edo, Lacy Construction Finished: 1330 Contractor: Lacy Construction Report Distribution: (1) City or Coppell Tx (1) City of Coppell TX (1) City of Coppell '1'x (2) Halff Assoc Inc (1) Lacy Construction (1) PncTntst Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively forthe use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. r•tuwmi. 5.31.09, Rev.) Page 2 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091 193.0064 lVerracon Service Date: 01/13/10 8901 Carpenter Frwy. Report Date: 01/21/10 Dallas, TX 75247 214- 630 -1 010 Reg No: F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: Supplier: Lacy Batch Time: Plant: Truck No.: Ticket No.: Field Test Data Test Slump (in): Air Content (' %t): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pct): Result Specification 3 1/4 1 -3 5.9 3 -6 59 50 148.6 Laboratory Test Data Set Specimen Diameter Area Date No. ID (in) (sq in) Received 3 1 6.00 28.27 01/14/10 3 2 6.00 28.27 01 /14 /10 3 3 6.00 28.27 01/14/10 3 4 6.00 28.27 01/14/10 m m ents: (1) City of Coppell TX (2) Halff Assoc Inc (1) PncTtnst Pacific Really Associates LP Maximum Compressive Load Strength Fracture (lbs) (psi) Type 97,580 3,450 2 Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement location4 perform required field tests and cast compressive strength samples. Terracon Rep.: Christopher P. Moran Reported To: Alfredo, Lacy Construction Contractor: Lacy Construction Report Distribution: (1) City of Coppell "rx (1) City of Coppcll'I'x (1) Lacy Construction Test Methods: Sample Date: 01/13/10 Sample Time: 1145 Sampled By: Christopher P. Moran Weather Conditions: Sunny, light breeze Accumulative Yards: Batch Size (cy): 8 Placement Method: Direct Discharge Water Added Before (gal):0 28 Water Added After (gal): 0 Sample Location: Sta. 8 +00 Placement Location: Paving fiorn Sta. 7 +25 to Sta. 12 +60, west of bridge Started: 0800 Finished: 1330 Reviewed By: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Cntxnt1. 5- 2t -ou, ttm.1 Page 3 of 3 Senior Project Manager Age at Date Test Tested (days) 01/20/10 7 01%27/10 14 02/10/10 28 02/10/10 28 Started: 0800 Finished: 1330 Reviewed By: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Cntxnt1. 5- 2t -ou, ttm.1 Page 3 of 3 Senior Project Manager