Loading...
Vista Properties-CS 961217 COPPELL ENGINEERING UTILITIES DIVISION MEMORANDUM DATE: 12-17-96 TO: G. Campbell FROM: L. Smith RE: Walk Thru for Vista Properties Water & Sewer A walk-thru on the above referenced project was conducted on 12-16-96 and the items below were found to be deficient. Fire Hydrant #1 Start at Denton Tap. 1. 6. 7. 8. 10. Fire Hydrant #1 has a mainline valve next to it. Needs valve stack replaced (stack and cap.) F.H. #2 needs a new pad poured. F.H #3 leaks at bottom section. Main valve #2 on corner of 553 and Ridgemont. Can't get on valve. Needs to be raised to ground level. F.H. #4 leaks at Bonnett. Repair F.H. #6 needs new pumper cap. Leaks at seal. F.H. #10 Leaking from bottom (below ground). F.H. #11 corner of MacArthur and East bound 553 Leaking at bottom (below ground) F.H at Lake Vista and MacArthur leaking below ground, At Peninsula and bridge on MacArthur- locate blow-off(.2"), From Denton Tap to MacArthur line has only two Main Line Valves. LINE A MH a, x 32 needs chimney seal installed properly (to bottom of Ring) also needs an extension for the rest of the chimney. MH At 3:2 bottom of seal still loose tots of flow on line for nothing to be on this iine. MH 10 + 01 top of seal not installed properiy to ring and bottom loose also needs dirt North side of MH. LINE D MH 0 + 00 needs new ring cover, rein pan, chimney seal, and leak in MH repaired. MH N. of 0 + O0 needs chimney seal properly installed ( to bottom of ring) and extension for rest of chimney (Between 0 + 00 and 5 + 00) MH 5 + 00 compaction bad, leaking in MH N. side at bottom 4 inches above floor, MH 10 + O0 chimney seal needs to be installed properly ( to bottom of ring) looks like it has been leaking 4 inches from bottom S. side. MH 10 + 66 needs chimney seal tightened on bottom, LINE E MH 4 + 15 is too high (higher than curb) Chimney seal loose on bottom. Leaking above outlet pipe to East at Ridgemont S. side. LINE F MH 2 + 55 Chimney seal loose on bottom. MH 5 + 77 W. side Denton Tap, Bottom of chimney seal loose. Stub out to North is White PVC. Replace it with green SDR35. VISTA RIDGE AREA 1st New-MH east on Denton Tap New-Chimney seal does not meet the ring and bottom loose, looks like seam is leaking. PIP 2nd Exist-MH needs new ring and not Lewisvilles lid. Rain pan chimney seal and levee (S3 Stake) PIP 3rd Exist-MH needs new ring and cover, chimney seal, Rain pan. PIP 4th Exist-MH needs new ring and cover, chimney seal, Rain pan. PIP 5th Exist-MH needs new ring and cover, chimney seal, Rain pan. (before drainage where bridge is on 553) leaking at drop about <5gpm. PIP 6th Exist-MH needs new ring and cover, chimney seal, Rain pan. (other side of drainage) PIP 7th Exist-MH needs new ring and lid, chimney seal, Rain pan. PIP 8th Exist-MH needs new ring and cover, chimney seal, Rain pan. No more than 500' feet between manholes