Rolling Oaks MC-CS080326TexasAbility
Design • Plan Review • Inspection
P.O. Box 729
Gun Barrel City, Texas 75156
(903) 288 -2962
TexasAbility@att.net
March 26, 2008
Mike Garza
City of Coppell Texas
255 Parkway Boulevard
Coppell, TX 75019 -9478
RE: AB Project Number EABPRJA8809546
Rolling Oaks Memorial Center Columbarium and Pavilion Buildings
400 S. Freeport Parkway
Coppell, TX 75019 (Dallas Co)
Response Letter dated March 17, 2008 and received by TA on March 25, 2008 --
TA# 08005
REVISIONS REVIEW - COMPLETED
Mr. Garza:
Enclosed are the results of the revisions review completed on the referenced facility. Identified on the
report are areas of nonconformance with accessibility standards adopted by the Texas Department of
Licensing for purposes of ensuring compliance with the Texas Government Code, Chapter 469.
Although deficiencies have been noted, the referenced project may be eligible for inspection approval if
constructed in accordance with the Texas Accessibility Standards. Items that are the responsibility of the
owner should be referred to the appropriate person for action.
The building or facility owner must request an inspection from the Registered Accessibility Specialist (RAS)
or the Department no later than 30 days after the completion of construction. If the completion date
provided on the Project Registration Form is no longer correct, notify this office (in writing) of the revised
completion date, as soon as possible.
This determination does not address the applicability of the Americans with Disabilities Act (ADA), (P.L.
101 -336), or any other local, state, or federal requirement. For information on the ADA, call the ADA
Hotline, (800) 949 -4232 or the United States Department of Justice at (202) 514 -0301.
Please reference the Department assigned project number in all future correspondence pertaining to this
project. Questions concerning this matter should be directed to Martin Mullins, RAS #291 at 214 - 532 -0386.
Respectfully,
A. Martin Mullins, III, LC, RAS
Registered Accessibility Specialist #291
CC: John Gary
Enclosure: Amended Plan Review Report
The information herein and related documents are provided by a Registered Accessibility Specialist (RAS) for the Texas Department of
Licensing and Regulation, upon completion of training and certification provided by TDLR. It is based upon plans and specifications
submitted and information available at the time of review and inspection. This shall not imply nor warrant complete compliance of the
referenced project to the Texas Accessibility Standard. The RAS and the Texas Department of Licensing and Regulation shall be
indemnified and held harmless by all parties from and against liability arising from the performance of the work.
TexasAbility
Design • Plan Review • Inspection
P.O. Box 729
Gun Barrel City, Texas 75156
(903) 288 -2962
TexasAbility@aft.net
Plan Review Report
Texas Government Code, Chapter 469
ARCHITECTURAL BARRIERS -TEXAS ACCESSIBILITY STANDARDS (TAS)
Project: Rolling Oaks Memorial Center TA Project: 08005
Project Scope 4.1.3
Facility: Rolling Oaks Memorial Center
Project Description: Phase I of 3 Phases. Project includes
Columbarium and Pavilion Buildings
Columbarium, Pavilion, sidewalks,
400 S. Freeport Parkway
roadways, parking, flagpole /
Coppell, Texas 75019 Dallas Co.
feature wall areas
Owner: Mike Garza, City of Coppell, 255 Parkway Boulevard, Coppell, TX 75019, 972.462.0022
Designer: Jo hn Gary, J. Stuart Todd, Inc. Architects, 2919 Welborn, Dallas, TX 75219, 214.522.4033
By: TexasAbility Date: March 12, 2008
RAS #0291- Martin Mullins Amended March 26, 2008 EABPRJ #A8809546
DEFINITION OF SYMBOLS: C = Complies
X =Not Acceptable RR = Response Required
I = Insufficient Information NA = Not Applicable
Accessible Elements & Spaces:
Technical Requirements Comments:
4.3 Accessible Route
4.3.2 Location
(1) Exterior Routes
C
(2) Connecting Routes
C
Based on JST Response Letter March 17, 2008
(3) Interior Routes
C
(4) Dwelling Units
NA
(5) Vehicle Hazards
C
4.3.3 Width
C
Based on JST Response Letter March 17, 2008
4.3.4 Passing Space
C
4.3.5 Head Room
C
4.3.6 Surface Textures
C
4.3.7 Slope
C
Based on JST Response Letter March 17, 2008
4.3.8 Changes In Levels
C
Based on JST Response Letter March 17, 2008
4.3.9 Doors
C
Based on JST Response Letter March 17, 2008
4.3. 10 Egress
C
Based on JST Response Letter March 17, 2008
4.3.11 Areas Of Rescue Assistance
NA
4.3.11.1 Location and Construction
NA
4.3.11.2 Size and Number
NA
4.3.11.3 Stairway Width
NA
Page 1 of 4
4.3.11.4 Two Way Communication
NA
4.3.11.5 Identification
NA
4.4 Protruding Objects
4.4.1 General
C
Based on JST Response Letter March 17, 2008
4.4.2 Head Room
C
4.5 Ground and Floor Surfaces
4.5.1 General
C
4.5.2 Changes In Level
C
Based on JST Response Letter March 17, 2008
4.5.3 Carpet
C
Based on JST Response Letter March 17, 2008
4.5.4 Gratings
NA
None shown or noted
4.6 Parking And Passenger Loading Zones
4.6.1 Minimum Number
C
4.6.2 Location
C
(1) Parallel Parking
NA
None shown or noted
4.6.3 Parking Spaces
C
Based on JST Response Letter March 17, 2008
4.6.4 Signage
C
(1) Height
C
(2) Accessible Routes
C
(3) Overhead
NA
None shown or noted.
4.6.5 Vertical Clearance
C
4.6.6 Passenger Loading Zones
NA
None shown or noted
4.7 Curb Ramps
4.7.1 Locations
C
For curb ramps shown
4.7.2 Slope
C
Based on JST Response Letter March 17, 2008
4.7.3 Width
C
4.7.4 Surface
(1) Texture
C
Based on JST Response Letter March 17, 2008
(2) Contrast
C
Based on JST Response Letter March 17, 2008
4.7.5 Sides of Curb Ramps
C
Return curbs
4.7.6 Built -up Curb Ramps
NA
None shown or noted
4.7.8 Obstructions
NA
None shown or noted
4.7.9 Location at Marked Crossings
NA
4.7.10 Diagonal Curb Ramps
NA
None shown or noted
4.7.11 Islands
NA
None shown or noted
4.8 Ramps
NA None shown or noted
4.9 Stairs
NA None shown or noted
4.10 Elevators
NA None shown or noted
4.11 Platform Lifts(Wheelchair Lifts)
NA None shown or noted
4.13 Doors
4.13.2 Turnstiles
NA
None shown or noted
4.13.3 Gates
NA
None shown or noted
Page 2 of 4
4.13.4 Double Leaf Doorways
C
4.13.5 Clear Width
C
4.13.6 Maneuvering Clearances at Doors
C
Based on JST Response Letter March 17, 2008
4.13.7 Two Doors in Series
NA
4.13.8 Thresholds at Doorways
C
Pemko 171 Saddle type specified
4.13.9 Door Hardware
C
Lever trim indicated in spec
4.13. 10 Door Closers
NA
Based on JST Response Letter March 17, 2008
4.13.11 Door Opening Force
NA
Based on JST Response Letter March 17, 2008
4.13.12 Automatic Doors and Power Assisted
Doors
NA
None shown or noted
4.14 Entrances
4.14.1 Minimum Number
C
4.14.2 Service Entrances
C
4.15 Drinking Fountains and Water
Coolers
NA None shown or noted
4.16 Water Closets
4.16.2 Clear Floor Space
C
4.16.3 Height
C
4.16.4 Grab Bars
C
4.16.5 Flush Controls
C
4.16.6 Dispensers
C
4.17 Toilet Stalls
NA
4.18 Urinals
NA None shown or noted
4.19 Lavatories and Mirrors
4.19.2 Height and Clearance
C
4.19.3 Clear Floor Space
C
4.19.4 Exposed Pipes and Surfaces
C
4.19.5 Faucets
C
4.19.6 Mirrors
C
Top of Mirror scales 76" AFF
4.20 Bathtubs
NA None shown or noted
4.21 Shower Stalls
NA None shown or noted
4.22 Toilet Rooms
4.22.1 Minimum Number
C
4.22.2 Doors
C
Based on JST Response Letter March 17, 2008
4.22.3 Clear Floor Space
C
4.22.4 Water Closet
C
4.22.5 Urinals
NA
None shown or noted
4.22.6 Lavatories and Mirrors
C
4.22.7 Controls and Dispensers
C
4.23 Bathrooms, Bathing Facilities, and
Shower Rooms
NA None shown or noted.
4.24 Sinks
NA None shown or noted
4.25 Storage
Page 3 of 4
4.25.1 General
C
Based on JST Response Letter March 17, 2008
4.25.2 Clear Floor Space
C
Based on JST Response Letter March 17, 2008
4.25.3 Height
NA
Based on JST Response Letter March 17, 2008
4.25.4 Hardware
C
Based on JST Response Letter March 17, 2008
4.26 Handrails, Grab Bars, & Tub and
Shower Seats
4.26.1 General
C
Based on JST Response Letter March 17, 2008
4.26.2 Size and Spacing of Grab Bars and
Handrails
C
Based on JST Response Letter March 17, 2008
4.26.3 Structural Strength
C
Based on JST Response Letter March 17, 2008
4.26.4 Hazards and Edges
NA
None shown or noted
4.27 Controls and Operating Mechanisms
4.27.2 Clear Floor Space
C
4.27.3 Height
C
4.27.4 Operation
C
4.28 Alarms
NA None shown or noted
4.29 Detectable Warnings
4.29.2 On Walking Surfaces
C
Based on JST Response Letter March 17, 2008
4.30 Signage
4.30.2 Character Proportion
C
Based on JST Response Letter March 17, 2008
4.30.3 Overhead Signs
NA
None shown or noted
4.30.4 Raised and Brailed Characters and
Pictograms
C
Based on JST Response Letter March 17, 2008
4.30.5 Finish and Contrast
C
Based on JST Response Letter March 17, 2008
4.30.6 Mounting Location and Height
C
Based on JST Response Letter March 17, 2008
4.30.7 Symbols of Accessibility
(1) Facilities and Elements
NA
Not required per 4.1.2(7)(d)
(2) Volume Control Telephones
NA
None shown or noted
(3)Text Telephones
NA
None shown or noted
(4) Assistive Listening Systems
NA
None shown or noted
4.31 Telephones
NA None shown or noted.
4.32 Fixed or Built -in Seating and Tables
NA None shown or noted
4.33 Assembly Areas
NA
4.34 Automated Teller Machines
NA None shown or noted
4.35 Dressing and Fitting Rooms
NA None shown or noted
5 Restaurants, Cafeterias, Snack Bars, Etc.
NA None shown or noted
6 Medical Care Facilities
NA None shown or noted
7 Business and Mercantile
NA None shown or noted
8 Libraries
NA
9 Accessible Transient Lodging
NA
10 Transportation Facilities
NA
Additional Comments:
The requirements shown in this list may be viewed on the internet at " www .license.state.tx.us /ab /ab.htm" .
Page 4 of 4