MA 98/99-LR 990728MA)aM
TECHNOLOGIES INC
Maxim Technologies Inc.
2575 Lone Star Drive
Dallas, Texas 75222
Telephone: (214) 631 -2700
FAX: (214) 920 -1891
REPORT OF
CONCRETE COMPRESSIVE STRENGTH
CLIENT: ABCON CONSTRUCTION
Attn: Rusty Whitaker PAGE 1 OF 1
1045 E. HWY 121
Lewisville, TX 75057 PROJECT NO.: 9710310
REPORT NO.: 148944
PROJECT: Pavement Renovation - Coppell DATEOFSERVICE: 6/30/99
Texas, Various AUTHORIZATION: Rusty
FREEPORT & GATEWAY REPORT DATE: 7/28/99
SERVICES: Sample concrete at location of placement, perform required field tests,
prepare and test concrete compressive strength specimens.
Technician: Lloyd Burtsell
Report Distribution:
(1 j City oNC CONSTRUCTION
Started: 06:00AM Stopped: 09:00AM
MAXIM TECHNOLOGIES INC.
Division
Our letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced except in
full without the 7007 RTB
apply only to the approval mple tested and/or inspected, and ace s f
notindicative e of the quantities of apparently O
identical or products.
PROJECT DATA
CONTRACTOR: ABCON
CONTRUCTION
CLASS OF CONCRETE: CC4050A
CONCRETE SUPPLIER:
Custom Crete
DATE OF PLACEMENT: 6/30/99
PLANT: Joe Field
TIME SAMPLED: 07 : 30AM BY: Lloyd Burtsell
SPECIFICATION REQUIREMENTS
TEMPERATURE (DegF) - AIR: 78 CONCRETE: 83
STRENGTH: 3000psi
@ 28 DAYS
TRUCK NO: 433 TICKET NO: 175766
SLUMP: 4"
AIR: 3 -5% MEASURED SLUMP (in.): 4.00
^^FTHOD OF TEST
AIR CONTENT( %): 4. 1
SAMPLING:
ASTM C -172
LOCATION OF PLACEMENT:
MOLDING & CURING:
ASTM C31
Paving- Freeport @ Gateway
SLUMP:
ASTM C143
sampled 20 north and 10 east of southwest
TEMPERATURE:
ASTM C1064
curb.
AIR CONTENT:
ASTM C231
UNIT WEIGHT:
CAPPING /PADS:
ASTM C1231
TESTING:
ASTM C39
REPORT OF TESTS
CONCRETE COMPRESSIVE STRENGTH - 6 X 12 CYLINDERS
CYLINDER
MAXIMUM COMPRESSIVE
MARKED
N0.
DATE AGE
TESTED (days
DIAMETER AREA LOAD STRENGTH
(in.) Isg.in.) pbs. force) si FRACTURE TYPE REMARKS
SET
7/07/99 7
_
6.00 28.27 73590 2600 UJIBONDED CAP
1 i
1 2
7/28/99 28
6.00 28.27 121660 4300 UNBONDED CAP
1 3
7/28/99 28
6.00 28.27 122590 4340 UNBONDED CAP
1 4
HOLD
Technician: Lloyd Burtsell
Report Distribution:
(1 j City oNC CONSTRUCTION
Started: 06:00AM Stopped: 09:00AM
MAXIM TECHNOLOGIES INC.
Division
Our letters and reports are for the exclusive use of the client to whom they are addressed and shall not be reproduced except in
full without the 7007 RTB
apply only to the approval mple tested and/or inspected, and ace s f
notindicative e of the quantities of apparently O
identical or products.