Tennis Ctr Exp-CS100621Page 1 of 1
George Marshall - Coppell Tennis Center Improvements Project
From: <john.fielder @kimley- horn.com>
To: <marrellano @coppelltx.gov >, <gmarshall @coppelltx.gov>
Date: 6/21/2010 12:33 PM
Subject: Coppell Tennis Center Improvements Project
Attachments: RetainingWall.pdf
Michael /George,
Attached is the shop drawing submittal from the Schmoldt Construction for the Tennis Center Improvements
project. The max height of the retaining wall is 3.5'. Let me know if you have any concerts or exceptions you
wish to make on the wall and we will get the items revised.
Thanks,
John A. Fielder, RLA
Kimley -Horn and Associates, Inc.
2201 West Royal Lane
Suite 275
Irving, TX 75063
email: iohn. fielder kimley -horn. com
Phone: (214) 420 -5600
Fax:. (214) 420 -5680
file: HC: \Documents and Settings \radloo \Local Settings\ Temp \XPgrpwise \4C 1F5C18City_... 8/30/2010
Stone Gravity Type Retaining Wall Specifications:
Stone type Milsap Sandstone
Fascia Pattern Random (Mosaic Pattern)
Mortar 3000 psi (minimum)
Mortar Color Gray Mortar
Wall Cap Top of wall to have defined 5" manicured cap ( +/- 1 "). Solid stone or multi -piece is
acceptable.
Gravel Pocket Continuous Gravel pocket with 3" weep holes every 8' to 10' o.c. Gravel
backfill to extend from weep hole to elevation 12" below finished grade behind wall and
completely wrap gravel backfill (ie ... top, back, and bottom) with filter fabric — Typar 3201 or
comparable.
Engineering Complete Structural Engineering Design by a Licensed Professional Engineer
Permits Contractor to provide all retaining wall permits and periodic inspections by the
structural engineer of record, followed by a final letter of inspection.
Sleeve for wood fence In the event, owner chooses to sleeve walls for future 6' wood fence
installation, contractor to install 4" sleeves at 8' o.c. Sleeves to be 4 "dia. x 18" long and 3' long
- #3 Rebar (6 count) to be installed at each sleeve. Steel to be installed at 6" o.c. (Vertical) and
centered on each sleeve (horizontal). Contractor to provide unit cost for sleeve installation.
Backfill Contractor to backfill retaining wall with continuous gravel pocket as defined above.
Gravel pocket should be minimum 6" to 12" wide on all walls under 4' tall (wall height assumes
elevation from sub -grade to top of wall). Walls over 4' in height should have minimum 12" to
18" gravel pocket. Taller walls subject to increased gravel pocket dimensions in order to
alleviate hydrostatic pressure build -up and decrease active / passive pressure on the back of the
wall.
Surcharge Any walls within equal distance to wall height of existing structure to be designed
for surcharge. For example: a 6' tall wall located within 6' of future house or Firelane must be
designed for Firelane surcharge which should increase wall dimensions a minimum 30 %.
Footin s: All retaining walls should have minimum 9" footings below sub - grade. Structural
design is the responsibility of the structural engineer of record.
Warranty Contractor to provide a (1) Year on all walls constructed against structural defects
and workmanship.
12" MIN. / 18" MAX CLOSEST APPROACH
TO ='SOIL OVER D = 2N 0 N.) OF eURCHARGE
DRAINAGE MATERIAL
STONE AND -
MORTAR WALL
9
- I � FIRM NATIVE
SOIL OR
— COMPACTED FILL
1
6
X
FINAL 3 t w
GRADE _
1 4 MIN
F_
FQ
1
_I DRAINAGE MATERIAL
MIN. WIDTH AT BOTTOM
WR,4=PED IN FILTER FABRIC
WEEP HOLES
(SEE NOTE)
TEMPORARY
SLOPE
TYPICAL RETAIN FALL. SECTION