All:
We are including information regarding the fiber optic connections between the Rolling Oak Memorial Center
and the Wagon Wheel Tennis Center, in the construction plans for the tennis center expansion. Could you
provide a spec for the “Type A” Typical Ground Boxes? We want to include this information on the plans as
clarification for the bidders.
Thanks,
John Fielder
Phone: (214) 420-5629
Cell: (817) 937-9750
From: Fielder, John
Sent: Friday, March 19, 2010 10:16 AM
To: Jim Weathers
Subject: Fiber Optic
John A. Fielder, RLA
Kimley-Horn and Associates, Inc.
2201 West Royal Lane
Suite 275
Irving, TX 75063
email:
.
johnfielder@kimley-horn.com
Phone: (214) 420-5600
Fax:. (214) 420-5680
file://C:\Documents and Settings\radloo\Local Settings\Temp\XPgrpwise\4BA35986City_...9/16/2010
Tennis Center Fiber Connection Project
Pathway
Install 2” conduit, innerduct and 12 strand single mode fiber optic cable
from the Rolling Oaks Memorial Center to the Coppell Tennis Center.
Conduit should include pull boxes at a maximum distance of 500 ft
between each box.
Terminations
Memorial Center
Each strand of fiber will be terminated with laser optimized duplex LC
fiber connectors
Each LC fiber connector will placed in a 6 port duplex LC bulkhead
panel to inserted into a 3 port rack mount fiber distribution panel
The rack mount fiber distribution panel will accommodate (2) 6 port lc
bulhead panels
Each unused port in the fiber distribution panel will receive a blank
insert plate and be reserved for future fibers
Tennis Center
Each strand of fiber will be terminated with laser optimized duplex LC
fiber connectors
Each LC fiber connector will placed in a 6 port duplex LC bulkhead
panel to inserted into a 3 port rack mount fiber distribution panel
The rack mount fiber distribution panel will accommodate (2) 6 port lc
bulhead panels
Each unused port in the fiber distribution panel will receive a blank
insert plate and be reserved for future fibers
Testing
Each strand shall be tested for attenuation loss at two wavelengths,
1310/1550 nm per the ANSI/TIA/EIA-568-b.3 performance standard.