· i ~ May 5, 2000
Transmitted via Facs
Architectural Utilities, Inc., dba AUI General Contractors
300 W. Ramsey
Fort Worth, Texas 76110
Re: City of Coppell
Addition of Pump Number 4
Gentlemen:
After observing the physical condition of the 600 horsepower General Electric motor at the job site for the
Addition of Pump Number 4 at the Village Parkway Pump Station, the City of Coppell has some doubts that
the motor is in fact new. On behalf of the City we are requesting verification that the motor provided is new
and not re-built or reconditioned. Using serial numbers on the motor housing, please have the motor
manufacturer provide verification of the date of manufacture, customer name, shipping date and delivery
location. In addition, we request a representative of the motor manufacturer meet with us at the job site to
verify the data and operating condition of the motor.
Any other data you, the pump supplier or the motor manufacturer can supply to verify the status of the motor
would be helpful. In the meantime, it is advisable not to connect the motor to the pump nor otherwise start
the motor until the motor is verified as new.
Please coordinate and provide this information at your earliest convenience and notify us of the date for the
meeting with the manufacturer' s representative. If you have any questions or need additional direction,
please do not hesitate to contact this office.
P.E.
cc: Mr. Kenneth M. Griffin, P.E
Mr/Glenn D. Hollowell, P.E
t,~r. Larry Davis
j:\clerical\coppell\1999-153\letwrs\cons6kXmotor condition.doe
'! I l'
DEC 83 1999 18:47 FR G.~UPPLY 972 388 ?036 TO 9"~3332785 P.81/05
> q
To ~A~I L F
co~.p~. ~/~ ~T~
Control Systems
Customer Service Dept
Fort Wayne, IN 46802
(219) 439-2000
Customer:
Customer Requested DataPack
Genented by EDDS/CustomerLink
Customer Order ....................: NONE
Customer Part .......................:None
GEICS Reqn / Item ...............: None
GEICS Job Number ..............:NONE
MODEl. NUMRF. R ...............: 5KSS13AN3661VI
Outline Drawing ....................: 50DP4109G004AG
Connection Diagram .............: GEM2034E-FIG7
Desi!~n Code: ..........................: 50DS3544CW
Type ........................................: KS
Frame ......................................: 5013S
Phases .....................................: 3
Poles ........................................: 6
Horsepower .............................600
RPM .........................................1190
Voltage ....................................: 4160
Hertz ........................................60
Amps - FL ...............................80.5
Service Factor .........................1.15
I~.STIM~,T~.Y} WY.I~HT ....... : 5180 Lbs (2349.65Kg)
Time Rating ............................: CONT
Enclosure ................................: WPI
Encl Construction ..................: OPEN
Ambient ..................................: 40
Insulation Class ......................: F
NEMA Design ........................: -
Nominal Efficiency ................: 95.8
Guaranteed Effideney ...........: 95.4
KVA Code ..............................: G
Max KVAR. ............................: 212.3
Power Factor ................' ..........: 80,5
Bearing - DE ...........................: 6320ZC3
Bearing - ODE ........................: 6320ZC3
Enclosure is Weather Protected One OPEN
Addi~on~iMn~r Data:
GREASE RYKON PREM #2
HTR LDS H ll5V 350W
6P-FORM COIL-WPI FEAT-115V HTR LDS & 100
0HMWDG RTD LDS TO ACESS BOX
*******SPIDER ARM SET*******************
C!:!N~CrInN
TX
T3 ~ T2
V0L'k'~ LL L~ L3
|& 5INC~E rl T2 T3
PaEe I
FIG. 1
HEATER CONN.
· · ·
VOLTAGE ONLY
II !