GEOTECHNICAL EXPI,ORATION REPORT
UNDERGROUND UTILITY
EVALUATION OF FLOWABLE FILLS
SANDY LAKE ROAD AND SHADYDALE LANE
COPPEI,L, TEXAS
STANTECH PROJECT NO.: 1530FOX01
PREPARED FOR:
Fox Constructors
Mr. Joe Velasquez
P.O. Box 951
Midlothian, Texas 75065
PREPARED BY:
STANTECH ENGINEERING COMPANY
9200 King Arthur Drive
Dallas, Texas 75247-3610
(214) 63 1-4372
August 30, 1999
Fox Constructors
P.O. Box 951
Midlothian, Texas 75065
Report No.: 1530FOX01
Report Type: UU/E
Date: August 30, 1999
Attention: Mr. Joe Velasquez
GEOTECHNICAL EXPLORATION
UNDERGROUND UTILITY
EVALUATION OF FLOWABLE FILLS
SANDY LAKE ROAD AND SHADYDALE LANE
COPPELL, TEXAS
Dear Mr. Velasquez:
This is a report of a geotechnical exploration performed to evaluate the flowable fills located at the
intersection of Sandy Lake Road and Shadydale Lane, Coppell, Texas. This study was authorized
and performed in accordance with our proposal P0017 dated July 19, 1999.
INTRODUCTION
Purpose and Scope
StanTech understands that the flowable fills were placed around the water line and as a base under
the asphalt road located at the intersection of Sandy Lake Road and Shadydale Lane in the City of
Coppell, Texas. According to the NTCOG construction specification referenced, the uncon~ned
compression strength of flowable fill placed should be a minimum of 250 pounds per square foot
after 28 days with a plasticity index less than 12 and 100% passing a 3~4-inch sieve.
The purpose of this investigation was to determine whether the material placed meets the strength
requirements of the NTCOG specifications. StanTech conducted geotechnical soil sampling,
performed laboratory testing, evaluated the flowable fill soils, and developed our findings and
recommendations.
Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppeli, Texas
Page 1
StanTech Engineering Co.
Project No.: 1530FOX01
To accomplish the purpose of the study, the following scope of services was provided:
· Three (3) soil borings were dry drilled to a maximum depth of six (6) feet below the existing
ground surface to obtain samples and determine subsurface materials and conditions;
· Laboratory tests including Bar Linear Shrinkage, percent passing a 3A-inch size sieve and sieves
no. 10 and 200, and moisture contents were conducted to determine the properties of the
sub surface materials; and,
· Results of field exploration and laboratory tests were analyzed to evaluate the flowable fills and
determine whether or not they meet NTCOG specification requirements.
Project Location and Description
The site is located at the intersection of Sandy Lake and Shadydale Lane, Coppell, Texas. The site
surface is generally flat. There is a ditch along each edge of street with depths of about three (3)
feet.
FIELD EXPLORATION
Field exploration activities are described in the following sections.
Drilling Information
Subsurface materials and conditions were investigated on July 21, 1999. Conditions at the site were
investigated with three (3) borings; boring B-1 at station No. 105+60, boring B-2 at station No.
103+60, and B-3 at station No. 102+38. The borings were advanced by solid flight auger
techniques. The borings were dry drilled to a maximum depth of six (6) feet below the existing
ground surface. The equipment used, field tests performed and soil samples taken are discussed
below.
Equipment
The three (3) borings were dry drilled with a truck-mounted drilling rig utilizing a 4-3/4-inch solid
flight auger. All borings were backfilled with bentonite chips after completion. Sampling equipment
included Split-Spoon tubes which were taken every foot to a depth of five (5) foot at each location.
· Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppell, Texas
Page 2
StanTech Engineering Co.
Project No.: 1530FOX01
Tests Performed
Disturbed samples were obtained from auger cuttings in general accordance with ASTM D 1452,
Standard Practice for Soil Investigation and Sampling by Auger Borings. Twelve (12) Standard
Penetration Tests were conducted by using a 140-pound hammer falling 30 inches in the flowable
sands. All samples were examined and classified in the field. The samples were labeled, sealed in
moisture-proof containers, and transported to StanTech's Dallas laboratory for further examination
and analysis.
Soils
The soils ecountered in the borings are presented as follows:
Penelxafion Resistance*
Boring No. Boring Depth, ft Soil Description Blows/6 in. three 6-in. increments
B-1 0-1.5 Cemented Sand, Very Dense, Tan 45/45/45
B-1 1.5-3 Cemented Sand, Very Dense, Tan 46/35/50
B-1 3-4.5 Cemented Sand, Very Dense, Tan 50/50/42
B-I 4.5-6 Cemented Sand, Very Dense, Tan 33/28/28
B-2 0-1.5 Cemented Sand, Very Dense, Tan 50/2-inch
B-2 1.5-3 Cemented Sand, Very Dense, Tan 50/l-inch
B-2 3-4.5 Cemented Sand, Very Dense, Tan 50/l-inch
B-2 4.5-6 Cemented Sand, Very Dense, Tan 50/5-inch
B-3 0-1.5 Cemented Sand, Very Dense, Tan 50/5-inch
B-3 1.5-3 Cemented Sand, Very Dense, Tan 25/26/30
B-3 4.5-6 Cemented Sand, Medium Dense, Tan
* See Appendix B - Key to Tenninology
Groundwater
During the drilling operation, groundwater was not encountered in borings B-1 through B-3.
LABORATORY TESTING
Laboratory testing was performed in order to determine the strength and plastic characteristics of
the subsurface materials as well as to confirm the soil classifications. General descriptions of the
encountered soils together with visual and laboratory classifications and numerical values of the test
results are shown on the field exploration section.
Underground Utility Project
Evaluation of Flowable Fffis
Sandy Lake Road and Shadydale Lane
Coppell, Texas
Page 3
StanTech Engineering Co.
Project No.: 1530FOX01
Tests Performed
Bar Linear Shrinkage Tests
Three (3) bar linear shrinkage tests were performed to assist in identification and classification
of the soils using the general provisions of the Standard Test Method, TEX- 107-E.
Minus 3/~-inch, 10- and 200-Mesh Sieve Tests
Three (3) minus ~-inch, 10- and 200-Mesh Sieve tests were performed primarily to aid in the
proper classification of the soils using the general provisions of the Standard Test Method for
Amount of Material in Soils Finer Than the No. 10 and 200 (75-1~m) Sieve, ASTM D 1140.
Moisture Content Tests
Twelve (12) moisture content tests were performed on collected samples and/or cores in general
accordance with the Standard Test Method for Laboratory Determination of Water (Moisture)
Content of Soil and Rock, ASTM D 2216.
A Summary of Laboratory Test Results is presented as follows:
Moisture Content (ASTM D 2216)
Boring No. Boring Depth, ft. Test Result
B-1 0-1.5 11.1%
B-1 1.5-3 11.1%
B-1 3-4.5 11.4%
B-1 4.5-6 11.7%__
B-2 0-1.5 10.9%
B-2 1.5-3 10.4%
B-2 3-4.5 14.8%
B-2 4.5-6 13.9%_..
B-3 0-1.5 10.6%
B-3 1.5-3 13.6%
B-3 3-4.5 13.3%
B-3 4.5-6 12.9%
Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppell, Texas
Page 4
StanTech Engineering Co.
Project No.: 1530FOX01
Bar Linear Shrinkage Tests (Tex-107-E)
Boring No. Boring Depth. ft. Test Result
B-1 0-1.5 1.4%
B-2 1.5-3 0.4%
B-3 4.5-6 1.0%
Sieve Analysis (ASTM D 1140)
Boring No. Boring Depth, ft. % Passing ~-inch % Passing No. 10 % Passing No. 200
B-1 0-1.5 100% 77.1% 6.1%
B-2 1.5-3 100% 89.3% 7.7%
B-3 4.5-6 100% 94.0% 8.4%
Soil Stratigraphy
GENERAL SOIL CONDITIONS
In general, the soils in the underground utility area (Borings B-1 through B-3) can be considered
one (1) major stratum with depth limits and characteristics as follows:
Stratum No. Range of Depth, ft Soil Description (Unified Soil Classification System)
I 0 - 6 CEMENTED SAND (SM), Medium Dense to Very
Dense, Tan.
Soil Conditions
· The cemented sands of stratum I are medium dense to very dense. Current moisture contents
ranged from 10.4% to 14.8%.
Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppe!l, Texas
Page 5
StanTech Engineering Co.
Project No.: 1530FOX01
FINDINGS AND RECOMMENDATIONS
Based on our field exploration and laboratory test results, the following are our findings and
recommendations:
· The general relationship of penetration resistance and unconfined compression strength of
cemented sands are as follows:
Penetration Resistance Descriptive Term Uncon~ned Compression Strength*
10 - 30 Medium Dense 0.5 - 1.0
30 - 50 Dense 1.0 - 2.0
Over 50 Very Dense 2.0 - 4.0
Note: * tons per square foot (tsf)
The results of standard penetration tests (SPT) for the cemented sands are ranging from 24 to
100 per foot. The soils are medium dense to very dense. The unconfined compression strength
results of the cemented sands ranged from 1.0- to 4.0 tsf which are greater than the 250 pounds
per square foot and satisfies NTCOG specification requirements.
· The percentage of bar linear shrinkage ranged from 0.4% to 1.4%, indicating the onsite
cemented soils are non-expansive. It is our opinion that the plasticity index (PI) based upon low
bar linear shrinkage should be less than 12 which satisfies NTCOG specification requirements.
· The results of sieve analysis of each of these samples tested indicated 100% passing a 3A-inch
sieve which meets NTCOG specification requirements.
· Excessive erosion can lead to a progressive sloughing of the ditch walls. Consequently,l
progressive failure of ditch walls can occur. Therefore, StanTech highly recommends providing
erosion control systems such as vegetation cover or gunnite to ensure successful long-term
performance.
In conclusion, the testing and evaluation found the cemented soils placed at subject location
satisfied the three NTCOG construction specification requirements for flowable fill.
Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppe!!, Texas
Page 6
StanTech Engineering Co.
Project No.: 1530FOX01
STANDARD OFCARE
The recommendations and conclusions contained in this report are conducted in a manner consistent
with the level of care and skill ordinarily exercised by reputable geotechnical engineers practicing
in this or similar localities. No other warranty, expressed or implied, is made other than that the
work was performed in a proper and workmanlike manner.
We appreciate the opportunity to assist you on this project. If you have any questions concerning
this submittal, or if we can be of further assistance, please call.
Very truly yours,
S Tech Enginee~le_~.~-~: .....
Shau, ....;;;;¥b"":.'."']
PS/ps
Copies Submitted:
1- City of Coppell - Mr. Kenneth Griffin
1- City ofCoppell - Mr. Larry Davis
1- Shimek, Jacobs & Finklea - Mr. Gary Hendricks
cc: File/CK/PS
Appendix A -
Appendix B -
ILLUSTRATIONS
Site Plan/Boring Location Plan
Key to Terminology
Underground Utility Project
Evaluation of Flowable Fills
Sandy Lake Road and Shadydale Lane
Coppe!i, Texas
Page 7
StanTech Engineering Co.
Project No.: 1530FOX01
Appendix A
Boring Location Plan
N
Not to Scale
Shadydale Lane
~D
B-3
Sta. 102+38
B-2
Sta- 103+60
Sandy Lake Road
B-1
Sta. 105+60
Legend: · - Approximate Boring Location
Boring Location Plan
StanTech Engineering Co
9200 King Arthur Drive
Dallas, Texas
Figure 1
Project No.: ~s3o~oxol
Project: Sandy Lake Road and
Shadydale Lane
Coppell, Texas
Appendix B
Key to Terminology
Terms Describim~ Consistencv or Condition
50% or more passes the No. 200 sieve. Includes (1) inorganic and organic silts and clays. (2) graveHy, sandy or silly clays. Comistency is raWd according to
shearing strength, as indicated by laboratory compression t~jng or by pene~rometer readings.
Unconfmed
Very Soft
Soft
Firm
Stiff
Very Stiff ZOO to 4.00
Hard 4.00 and higher
Identification Procedure Shear Strength Compressive Strength* Pocket Penetrometer*
Sags under own weight less than 0.25 0 0.13
Easily pem'tratM sevenl inches by thumb lessthan0.25 0.251o0.50 0.13 0.25
Penetrated several inches 0.25 to 0.50 0.50 to 1.00 0.25 0.50
Readily indented by thumb, but penetrated 0.50 to 1.00 1.00 to 2.00 0.50 1.00
only with great effort
Readily indented by thumbnail 1.00 to 2.00 1.00 1.5
No penetration over 2.00 > 1.5
*tons~fi~ or kg/cm:
Coarse - Grained Soils
More than 50% retained on No. 200 sieve. Includes (I) clean gravels and sands described as free,medium or coarse, depending on distribution of grain sizes and
(2) silty or clayey gravels and sands.
Penetration Resistance** Descriptive Term Relative Density
0 - 10'** Loose 0 to 40% *'140 pound drive weight having
10 - 30 Medium Dense 40 to 70% a hammer drop distance of
30 - 50 Dense 70 to 90% 30 inches
Over 50 Very Dense 90 to 100% ***Blow per foot
Terms Characterizing Soil Structure
Fissured
Sensitive
Laminated
Interbedded
Calcereous
Well-graded
Poorly-graded
Slickensided
snghtly
Moderately
Extremely
Intensely
containing shrinkage cracks, frequently filled with free sand or silt; usually more or less vertical.
pertaining to cohesive soils that are subject to appreciable loss of strength when retooltied.
composed of thin layers of varying color and texture.
composed of alternate layers of difforent soil types.
containing appreciable qualifies of calcium carbonate.
having a wide range in grain sizes and substantial amounts of all intermediate particle sizes.
predominantly of one grain size, or having a range of sizes with some intermediate size missing.
having inclined planes of weakness that are slick and glossy in appearance.
Degree of slickensided development:
slickensides are present at intervals of 1-2 feet and soil does not easily break along these planes.
sliekensides are spaced at equal intervals of 1-2 feet and soil breaks easily along these planes.
sliekensides are spaced at intervals of 4-12 inches, are continuous and interconnected.
8oil breaks easily along the slickensides. Resulting size of broken pieces three to six inches.
sliekensides are spaced at inter/als of less than four inches and are continuous in all directiota.
Terns Characterizing Rock Propertie
Bedding Characteristics
Massive - occurring in thick beds free from hinge joints and laminations, more
than 100 mrm in thickness.
Thin to Medium - occurring in relatively thin layers of laminate 2 mrm to 100 rant bedding planes
Fissile - bedding which consists of laminate less than 2ram. in thickness, splits
easily along closely spaced parallel planes.
Cross-bedded - arrangement of laminations of strata transverse or oblique to the main
planes of stratification of the strata concerne&
Foilsted - the !aminat~l structure resulting from segregation of granular and fine
minerals into layers parallel to the schistosily (result of the parallel
arrangement ofplaty and ellipsoidal mineral grains).
Platy - parallel arrangement of brood or fiat minerals (giving a fo!lation) by
slablike inclusions, by scMieren or by bonds of different mineralogy or texture.
Fragmental - consisting of broken material, particularly that which has been moved
from its place of origitt
Degree of Weathering
Unweathered - rock in its natural state before being exposed to atmospheric agents.
Slightly weathered - noted predominantly by color change with no disintegrated zones.
Weathered - complete color change with zones of slightly decomposed rock_
Extremely weathered - complete color change with consistency, texture, and general appearance
approaching soil.
DU = Dry unit weight (pcf)
Abbreviations
LL = Liquid Limit
Texture
Dense - fine-grained aphonitic rocks in which the grain size generally
averages less than 0.05 to 0. 1 ram.
Fine - more than 50% by weight smaller than 0.074 ram. in diameter
(seen only with a strong hand lens or microscope.).
Medium - majority of grain in sizes between O.074mm. and 0.5 ram.
Coarse - grain sizes range from 0.5mm to 1 .Ore (erystals
are visible to the un-aided eye).
Structure
Bedding - fiat (0-15), gently dipping (15-30), steeply dipping (30-
vertical).
Fractures - broken surfaco of minerals or rock which does not
(scattered or open) exhibit cleavage or bedding planes.
Fractures - show signs ofbrokan minerals but now are cemented.
(closely spaced)
Breeciated - rock mad~ up of highly angular ooam fragments-
(sheared & fragmented) may be sedimentary or formed by crushing or
grinding along faults.
Joints - fraaur~ in rock, generally more or less vertical or
transvers~ to b~lding along which no appreciable
movement has oocurrexL
Faulted - fracture or fracture zone along which there has been
displacengnt of the sides relative to one another
parallel to the fracture - the displacement may be
a few inches or many miles.
Slickensides - polished and siraired (scratched) surface that
results from friction along a fault plan._
MC = Moiture content (%)
UC = Unconfmed compt~ssive strength (tsf)
PP = Pocket Penetrometer
PI = Plasticity index
/~200 = percent passing #200 U.S. Standard sieve
USCS = Unified Soil Classification System
StanTech Engineering Co.
9200 King Arthur Drive, Dallas, Tx 75247
KEY TO TERMINOLOGY
USED ON LOGS