Sales Tax 09-LR101129Acct ID: 1770 Report Date: 11/29/2010 Project: Heartz Road Location: Heartz Road Client: The Citv of Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1013 REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST Date Sampled: 11 /17/2010 Sampled By: Spooner, Charles By Order Of: Larry w/ RKM Order Number: 1770 LAB NO: 95005 Test Method: See Below TEST RESULTS Report No: 95005 Page 1 of 2 Set: 1 of 2 Material: CONCRETE Location: Hand paving Heartz Road, stattion 1 +50, center lane Number of Specimens: 4 Quantity Represented: 9 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in') (Ibs) Break Type Loc (PSI) (PSI) Comments A 3 6.00 28.27 83,575 Type 2 Lab 2,960 2,960 B 7 6.00 28.27 117,850 Type 2 Lab 4,170 4,170 C 28 6.00 28.27 Lab D 28 6.00 28.27 Lab I l if I � _­­_­] JJ I X i L -� f__. _ - ...... _. . Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/18/2010 Slump: 4.75 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 3.8% Source /Sampled At: Truck / Center Time Sampled: 10:05 am Plant: Redi -Mix - Plant #P259 Temp.: Ambient: 59 ° F Mix: 64 °F Mix Code: 1 01_1 1504 Truck/Ticket No: 1371 / 25269232 Quantity Represented: 9 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. It I I IIII Acct ID: 1770 Report Date: 11/29/2010 Project: Heartz Road Location: Heartz Road Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1013 Client: The City of Coppell REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST Date Sampled: 11/17/2010 Sampled By: Spooner, Charles By Order Of: Larry w/ RKM Order Number: 1770 LAB NO: 95005 Quantity Represented: 91 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group F Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. Test Method: See Below TEST RESULTS Report No: 95005 Page 2 of 2 Set: 2 of 2 Material: CONCRETE Number of Specimens: 4 Location: Hand paving, Heartz Road, station 4 +50, center lane Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in 2) (Ibs) Break Type LOG (PSI) (PSI) Comments A 3 6.00 28.27 111,730 Type 2 Lab 3,950 3,950 B 7 6.00 28.27 149,755 Type 2 Lab 5,300 5,300 C 28 6.00 28.27 Lab D 28 6.00 2827 Lab Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/18/2010 Slump: 3.75 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 42% Source /Sampled At: Truck / Center Time Sampled: 12:35 pm Plant: Redi -Mix - Plant #259 Temp.: Ambient: 66 °F Mix: 73 °F Mix Code: 10L11504 Truck/Ticket No: 1388 / 25269379 Quantity Represented: 91 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group F Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. GEOTECHNUIL Wour Consulting Engineering F Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 Acct ID: 1770 File No: C10 -1013 Date Sampled: 11/18/2010 Report Date: 11/29/2010 Sampled By: Marvin Hanks Project: Heartz Road By Order Of: Larry Location: Heartz Road Order Number: 1770 Client: The City of Coppell A 3 REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 95048 Type 3 Lab B 7 Test Method: See Below 28.27 TEST RESULTS Report No: 95048 C 28 6.00 Page 1 of 3 Set: 1 of 3 Material: CONCRETE Location: S.bound Heartz Rd, east half, sta 5 +55 Number of Specimens: 4 Compressive Average Strength Maximum (PSI) Spec Age Tested Diameter Area Load Cure Nbr (days) (in) (in 2) (Ibs) Break Type Loc A 3 6.00 28.27 113,370 Type 3 Lab B 7 6.00 28.27 133,715 Type 2 Lab C 28 6.00 28.27 Lab D 28 6.00 28.27 Lab Type 1 Type 2 Type 3 Type 4 Specification: 3,600 psi @ 28 days Date Received: 11/19/2010 Slump: 4.25 Inches Curing Method: Standard Air Content: 3.4% Time Sampled: 9:55 am Temp.: Ambient: 48 °F Mix: 63 °F Mix Code: 10L11504 Number of Specimens: 4 Compressive Average Strength Strength (PSI) (PSI) Comments 4,010 4,010 4,730 4,730 Type 5 Type 6 Transported By: Redi -Mix Source /Sampled At: Truck / Center Plant: Redi -Mix Truck/Ticket No: N/A / 25269712 Quantity Represented: 10 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr Keith Marvin, P.E. Ong: The City of Coppell (Coppell, TX) Attn Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SANIPLEIS) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTL Y IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES- NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR 7 HE EXCLUSIVE USE OF THE ADDRESSED CLIENT V0 ARE T% 8E REPRODUCED �MTHOUT WRITTEN PERMISSION. nLUnNCE GEOTECHNUIL Acct I D: 1770 Report Date: 11/29/2010 Project: Heartz Road Location: Heartz Road Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1013 Client: The City of Coppell REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST Date Sampled: 11/18/2010 Sampled By: Marvin Hanks By Order Of: Larry Order Number: 1770 101000OL Quantity Represented: 130 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry G Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND 10 11 !E SAMPLES) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPAREN I LY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THE_ Y REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCP USIVE USE OF THE ADDRESSED -LIE r ' ND ARE NOT'r0 BE REPRODUCED %AATHOU I WRIT TEN PERMISSION. Test M et h od: See B elow TEST RESULTS Report No: 95048 Page 2 of 3 Set: 2 of 3 Material: CONCRETE Number of Specimens: 4 Location: S.bound Heartz Rd, E. side at 137 Heartz Rd Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in') (Ibs) Break Type Loc (PSI) (PSI) Comments A 3 6.00 28.27 101,805 Type 1 Lab 3,600 3,600 B 7 6.00 28.27 135,415 Type 1 Lab 4,790 4,790 C 28 6.00 28.27 Lab D 28 6.00 28.27 Lab Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/19/2010 Slump: 4.5 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 4.3% Source /Sampled At: Truck / Center Time Sampled: 12:30 pm Plant: Redi -Mix Temp.: Ambient: 54 °F Mix: 69 °F Mix Code: 1OL11504 Truck/Ticket No: N/A / 25269891 Quantity Represented: 130 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry G Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND 10 11 !E SAMPLES) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPAREN I LY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THE_ Y REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCP USIVE USE OF THE ADDRESSED -LIE r ' ND ARE NOT'r0 BE REPRODUCED %AATHOU I WRIT TEN PERMISSION. E Wour Acct I D: 1770 Report Date: 11/29/2010 Project: Heartz Road Location: Heartz Road Client: The Cit of Coppell Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1013 Date Sampled: 11/18/2010 Sampled By: Marvin Hanks By Order Of: Larry Order Number: 1770 REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 95048 Test Method: See Below TEST RESULTS Report No: 95048 Page 3 of 3 Set: 3 of 3 Material: CONCRETE Number of Specimens: 4 Location: S.bound Heartz Rd, E. side, at 149 Heartz Rd Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in') (lbs) Break Type Loc (PSI) (PSI) Comments A 3 6.00 28.27 107,875 Type 2 Lab 3,820 3,820 B 7 6.00 28.27 135,000 Type 1 Lab 4,770 4,770 C 28 6.00 28.27 Lab D 28 6.00 28.27 Lab Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/19/2010 Slump: 4.5 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 4.6% Source /Sampled At: Truck / Center Time Sampled: 1:30 pm Plant: Redi -Mix Temp.: Ambient: 57 °F Mix: 69 °F Mix Code: 10L11504 Truck/Ticket No: Quantity Represented: 200 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell. TX) Attn Mr. Keith Marvin, P E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND - 10 THE SAMPLES) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL. OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOING QUALITY ,ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR 7 HE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TC BE REPRODUCED'A4THOUT VvRiT T EN PERMISSION, nLLIMICE GEOTECHMICIfIL W our Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 Acct ID: 1770 File No: C10 -1013 Date Sampled: 11/19/2010 Report Date: 11/29/2010 Sampled By: Walker, III, John Project: Heartz Road By Order Of: Cruz Location: S. entrance on NW corner of Heartz & Sandy Lake Order Number: 1770 Nbr (days) Number of (in') Client: T he City of Coppell Specimens: 4 REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 95089 Material: CONCRETE Test Method: See Below TEST RESULTS Report No: 95089 Page 1 of 1 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/20/2010 Slump: 3.5 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 3.1% Source /Sampled At: Truck / Center Time Sampled: 1:30 pm Plant: Redi -Mix - P259 Temp.: Ambient: 66 °F Mix: 73 °F Mix Code: 1 01_1 1504 Truck/Ticket No: 1321 / 25270529 Unit Weight: 147.1 # /cu ft Quantity Represented: 10 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, 01064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn. Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(SI TESTED .AND /OR OBSERVED AND ARE NOT NECESSARILY !NDIC €.TIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOJHG QUALITY ASSURANCE PROGRA? UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT nND.ARE NOT TO BE REPRODUCED'A FHOUT APIT TEN PERMISSION Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in') (Ibs) Break Type Loc (PSI) (PSI) Comments A 7 6.00 28.27 123,495 Type 1 Lab 4,370 4,370 B 28 6.00 28.27 Lab C 28 6.00 28.27 Lab D HOLD (see remarks) Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 11/20/2010 Slump: 3.5 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 3.1% Source /Sampled At: Truck / Center Time Sampled: 1:30 pm Plant: Redi -Mix - P259 Temp.: Ambient: 66 °F Mix: 73 °F Mix Code: 1 01_1 1504 Truck/Ticket No: 1321 / 25270529 Unit Weight: 147.1 # /cu ft Quantity Represented: 10 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, 01064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn. Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(SI TESTED .AND /OR OBSERVED AND ARE NOT NECESSARILY !NDIC €.TIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOJHG QUALITY ASSURANCE PROGRA? UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT nND.ARE NOT TO BE REPRODUCED'A FHOUT APIT TEN PERMISSION P� �r _. r� �, ''°" .. it E C Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 Acct ID: 1770 File No: C10 -1013 Date Sampled: 11/22/2010 Report Date: 11/29/2010 Sampled By: Whitney, Steve Project: Heartz Road By Order Of: Cruz Location: Southbound right lane of Heartz Rd. at Station 6 +50 and 4 +00 Order Number, 1770 Type 2 Lab Number of 3,890 Client: The City of Coppell Specimens: 4 REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 95144 Material: Co ncrete Test Method: See Below TEST RESULTS Report No: 95144 Page 1 of 1 Spec Age Tested Nbr (days) A 4 B 7 C 28 D 28 Diameter Area (in) (in 2) 6.00 28.27 6.00 28.27 6.00 28.27 6.00 28.27 (Ibs) !I Type 1 Specification: 3,600 psi @ 28 days Date Received: 11/23/2010 Curing Method: Standard Time Sampled: 10:20 am Temp.: Ambient: 72 °F Mix: 77 °F Slump: 5.0 Inches Transported By: LMC Air Content: 3.5% Source /Sampled At: Truck / Center Plant: 6 Mix Code: 8097 Truck/Ticket No: 7008 / 6381105 Quantity Represented: 7 cu. yds. at 7 cu. yds. placed of a 7 cu. yd. total placement Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E. Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc The City of Coppell Attn: Rhonda Adloo 1 -cc The City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager Maximum Compressive Average Load Cure Strength Strength (Ibs) Break Type Loc (PSI) (PSI) Comments 109,960 Type 2 Lab 3,890 3,890 114,560 Type 1 Lab 4,050 4,050 Lab Lab ff I l Type 2 Type 3 Type 4 Type 5 Type 6 THIS REPORT APP - IES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCT S OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOT ED THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE .ADDRESSED CLIEIJ _ND ARE I TG's REPRODUCED ':hG t HOUi iVR1TTF'ti PER 1fSSi0N_