Sales Tax 09-LR110117GEOTECHNICML
GROUr
Consulting Engineering Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C10 -1013 Date Sampled: 01/06/2011
Report Date: 01/17/2011 Sampled By: Clay, Bill
Project: Heartz Road By Order Of: Cruz
Location: 141 to 157 Heartz Road, W. side Order Number: 1770
Number of
Client: The City of Coppell Specimens: 4
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 96684
Material: CONCRETE Test Method: See Below
TEST RESULTS Report No: 96684
Page 1 of 1
Spec
Age Tested
Nbr
(days)
A
7
B
28
C
28
D
Diameter Area
(in) (in 2)
6.00 28.27
6.00 28.27
6.00 28.27
Maximum
Load
(Ibs) Break Type
98,370 Type 5
Average
Strength
(PSI) Comments
3,480
HOLD (see remarks) -
Compressive
Cure
Strength
Loc
(PSI)
Lab
3,480
Lab
Lab
Average
Strength
(PSI) Comments
3,480
HOLD (see remarks) -
Quantity Represented: 10 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr, Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Type 1
Type 2 Type 3 Type 4
Type 5 Type 6
Specification: 3,000 psi @ 28 days
Date Received: 01/07/2011
Slump: 5.0 Inches
Transported By:
Redi -Mix
Curing Method: Standard
Air Content: 3.7%
Source /Sampled At:
Truck / Center
Time Sampled: 2:40 pm
Plant:
Redi -Mix - Plant #259
Temp.: Ambient: Mix: 56 °F
Mix Code: 10J11504
Truck/Ticket No:
1359 / 25284691
Quantity Represented: 10 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr, Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Acct ID: 1770
Report Date: 01/17/2011
Project: Heartz Road
Location: Heartz Road
Client: The Citv of
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
File No: C10 -1013
Previously Reported: 12/24/2010
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Date Sampled: 12/16/2010
Sampled By: Hanks, Marvin
By Order Of: Cruz w /RKM
Order Number: 1770
Test Method: See Below
TEST RESULTS Report NO: 96054
Page 1 of 3
Set: 1 of 3 Material: CONCRETE
Location: N.bound Heartz Rd, station 1 +95
Spec
Age Tested
Nbr
(days)
A
4
B
7
C
28
D
28
Diameter
Area
(in)
(in 2)
6.00
28.27
6.00
28.27
6.00
28.27
6.00
28.27
Lab
4,380
4,380
Lab
5,550
Type 1
Maximum
Load
(Ibs) Break Type
100,450 Type 2
123,805 Type 2
156,980 Type 2
157,710 Type 2
Number of Specimens: 4
Type 2 Type 3 Type 4 Type 5 Type 6
Specification: 3,600 psi @ 28 days
Date Received: 12/17/2010 Slump: 4.5 Inches Transported By: Redi -Mix
Curing Method: Standard Air Content: 4.1 % Source /Sampled At: Truck / Center
Time Sampled: 9:05 am Plant: Redi -Mix
Temp.: Ambient: 43 °F Mix: 54 °F Mix Code: 10L11504 Truck/Ticket No: N/A / 25279300
Quantity Represented: 10 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr. Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Compressive
Average
Cure
Strength
Strength
Loc
(PSI)
(PSI) Comments
Lab
3,550
3,550
Lab
4,380
4,380
Lab
5,550
Lab
5,580
5,560
Type 2 Type 3 Type 4 Type 5 Type 6
Specification: 3,600 psi @ 28 days
Date Received: 12/17/2010 Slump: 4.5 Inches Transported By: Redi -Mix
Curing Method: Standard Air Content: 4.1 % Source /Sampled At: Truck / Center
Time Sampled: 9:05 am Plant: Redi -Mix
Temp.: Ambient: 43 °F Mix: 54 °F Mix Code: 10L11504 Truck/Ticket No: N/A / 25279300
Quantity Represented: 10 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Ong: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr. Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
� 1` If IN CE
VIII
GEOTECHNVIL
GROUr
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C10 -1013
Report Date: 01/17/2011 Previously Reported: 12/24/2010
Project: Heartz Road
Location: Heartz Road
Client: The City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
Date Sampled: 12/16/2010
Sampled By: Hanks, Marvin
By Order Of: Cruz w /RKM
Order Number: 1770
Test Method: See Below
TEST RESULTS
Set: 2 of 3 Material: CONCRETE
Location: N.bound Heartz Road at 117 Heartz Rd
Maximum
Spec Age Tested Diameter Area Load
Nbr (days) (in) (in 2) (Ibs) Break Type
A
4
B
7
C
28
D
28
6.00
28.27
6.00
28.27
6.00
28.27
6.00
28.2
(PSI)
(PSI) Comments
4,040
Type 1
114,100
Type 1
138,420
Type 1
168,090
Type 3
167,205
Type 2
Cure
Loc
Lab
Lab
Lab
Lab
Report No: 96054
Page 2 of 3
Number of Specimens: 4
Compressive
Average
Strength
Strength
(PSI)
(PSI) Comments
4,040
4,040
4,900
4,900
5,940
5,910
5,930
Type 2 Type 3 Type 4 Type 5 Type 6
Specification: 3,600 psi @ 28 days
Date Received: 12/17/2010 Slump: 4.0 Inches Transported By: Redi -Mix
Curing Method: Standard Air Content: 4.5% Source /Sampled At: Truck / Center
Time Sampled: 10:47 am Plant: Redi -Mix
Temp.: Ambient: 45 °F Mix: 56 °F Mix Code: 1 01_1 1504 Truck/Ticket No: N/A / 25279439
Quantity Represented: 110 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P-E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr. Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED, THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Acct ID: 1770
Report Date: 01/17/2011
Project: Heartz Road
Location: Heartz Road
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
File No: C10 -1013
Previously Reported: 12/24/2010
Date Sampled: 12/16/2010
Sampled By: Hanks, Marvin
By Order Of: Cruz w /RKM
Order Number: 1770
Client: The City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 96054
Test Method: See Below
TEST RESULTS Report No: 96054
Page 3 of 3
Set: 3 of 3 Material: CONCRETE Number of Specimens: 4
Location: N.bound Heartz Rd at 133 Heartz Rd
Quantity Represented: 210 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr. Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICAI "IVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Maximum
Compressive Average
Spec Age Tested Diameter
Area
Load
Cure
Strength
Strength
Nbr (days) (in)
(in')
(lbs)
Break Type Loc
(PSI)
(PSI) Comments
A 4 6.00
28.27
107,675
Type 2 Lab
3,810
3,810
B 7 6.00
28.27
136,950
Type 1 Lab
4,840
4,840
C 28 6.00
28.27
181,435
Type 2 Lab
6,420
D 28 6.00
28.27
184,170
Type 2 Lab
6,510
6,470
Type 1
Type 2
Type 3 Type 4
Type 5
Type 6
Specification: 3,600 psi @ 28 days
Date Received: 12/17/2010
Slump: 4.5 Inches
Transported By: Redi -Mix
Curing Method: Standard
Air Content: 4.6%
Source
/Sampled At: Truck / Center
Time Sampled: 12:49 pm
Plant: Redi -Mix
Temp.: Ambient: 50 °F Mix: 56 °F
Mix
Code: 10L11504
Truck/Ticket No: N/A / 25279542
Quantity Represented: 210 cu. yds.
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr. Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICAI "IVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
41 CRL
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C10 -1013 Date Sampled: 12/17/2010
Report Date: 01/17/2011 Previously Reported: 12/27/2010 Sampled By: Hanks, Marvin
Project: Heartz Road By Order Of: Cruz w /RKM
Location: S.bound Heartz Rd, from 141 to 157 Heartz Rd Order Number: 1770
Number of
Client: The City of Coppell Specimens: 4
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 96124
Material: CONCRETE Test Method: See Below
TEST RESULTS Report No: 96124
Page 1 of 1
Spec
Age Tested
Nor
(days)
A
3
B
7
C
28
D
28
Diameter Area
(in)
(in 2)
6.00
28.27
6.00
28.27
6.00
28.27
6.00
28.27
Type 1
Specification: 3,600 psi @ 28 days
Date Received: 12/18/2010
Curing Method: Standard
Time Sampled: 8:55 am
Temp.: Ambient: 41 °F Mix: 54 °F
Quantity Represented: 10 cu. yds.
Slump: 4.25 Inches
Air Content: 4.4%
Mix Code: 101_11504
3,470
4,630
5,860
-.W . .......
Type 6
Transported By: Redi -Mix
Source /Sampled At: Truck / Center
Plant: Redi -Mix
Truck/Ticket No: N/A / 25279904
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ATM C172, C143, C231 or C173,
C1064 and C138. Compressive strength tests per ASTM C39.
Charge: The City of Coppell Attn: Mr. Keith Marvin, P.E.
Orig: The City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
(1 -cc copy)
1 -cc The City of Coppell Attn: Rhonda Adloo
1 -cc The City of Coppell Attn: Mr, Rick O'Dell
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, Sr. Project Manager
Maximum
Load
(Ibs) Break Type
98,115 Type 6
131,045 Type 1
165,825 Type 3
165,305 Type 3
Compressive Average
Cure Strength Strength
Loc (PSI) (PSI) Comments
Lab 3,470
Lab 4,630
Lab 5,860
Lab 5,850
I
Type 2 Type 3 Type 4 Type 5
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.