Sales Tax 09-LR110222Acct ID: 1770 Report Date: 02/22/2011 Project: Clear Creek Location: Clear Creek Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1014 Date Sampled: 02/11/2011 Sampled By: Hanks, Marvin By Order Of: Rick O'dell Order Number: 1770 Client: City of Coppell REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 97550 Test Method: See Below TEST RESULTS Set: 1 of 2 Material: CONCRETE Location: W.bound Clear Creek land at approx. 491 Clear Creek Report No: 97550 Page 1 of 2 Number of Specimens: 4 Compressive Average Strength Strength (PSI) (PSI) Comments 3,860 3,860 5,250 5,250 JI Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 02/12/2011 Slump: 3.0 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 4.3% Source /Sampled At: Truck / Center Time Sampled: 12:25 pm Plant: Redi -Mix - Plant #P259 Temp.: Ambient: 46 °F Mix: 57 °F Mix Code: 1 01_1 1504 Truck/Ticket No: 1256 / 25291364 Quantity Represented: 10 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P. E. (1 -cc copy) 1 -cc City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. Maximum Spec Age Tested Diameter Area Load Cure Nor (days) (in) (in') (Ibs) Break Type Loc A 3 6.00 28.27 109,080 Type 1 Lab B 7 6.00 28.27 148,425 Type 1 Lab C 28 6.00 28.27 Lab D 28 6.00 28.27 Lab Report No: 97550 Page 1 of 2 Number of Specimens: 4 Compressive Average Strength Strength (PSI) (PSI) Comments 3,860 3,860 5,250 5,250 JI Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 02/12/2011 Slump: 3.0 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 4.3% Source /Sampled At: Truck / Center Time Sampled: 12:25 pm Plant: Redi -Mix - Plant #P259 Temp.: Ambient: 46 °F Mix: 57 °F Mix Code: 1 01_1 1504 Truck/Ticket No: 1256 / 25291364 Quantity Represented: 10 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P. E. (1 -cc copy) 1 -cc City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. III Acct ID: 1770 Report Date: 02/22/2011 Project: Clear Creek Location: Clear Creek Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444 -8889 Fax: (972) 444 -8893 File No: C10 -1014 Date Sampled: 02/11/2011 Sampled By: Hanks, Marvin By Order Of: Rick Odell Order Number: 1770 Client: City of Coppell REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST LAB NO: 97550 Test Method: See Below TEST RESULTS Report No: 97550 Page 2 of 2 Set: 2 of 2 Material: CONCRETE Number of Specimens: 4 Location: Kbound Clear Creek at approx. 475 Clear Creek Maximum Compressive Average Spec Age Tested Diameter Area Load Cure Strength Strength Nbr (days) (in) (in 2) (Ibs) Break Type Loc (PSI) (PSI) Comments A 3 6.00 28.27 104,255 Type 6 Lab 3,690 3,690 B 7 6.00 28.27 138,775 Type 2 Lab 4,910 4,910 C 28 6.00 28.27 Lab D 28 6.00 28.2 Lab Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Specification: 3,600 psi @ 28 days Date Received: 02/12/2011 Slump: 4.0 Inches Transported By: Redi -Mix Curing Method: Standard Air Content: 41% Source /Sampled At: Truck / Center Time Sampled: 2:32 pm Plant: Redi -Mix - Plant #P259 Temp.: Ambient: 52 °F Mix: 59 °F Mix Code: Truck/Ticket No: 1321 / N/A Quantity Represented: 100 cu. yds. Remarks: Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C172, C143, C231 or C173, C1064 and C138. Compressive strength tests per ASTM C39. Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry G. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION. fILLMCE ,k -117 GEOTECHN101L Wour Acct ID: 1770 Report Date: 02/22/2011 Project: Clear Creek Location: 8" Waterline Client: City of Coppell Consulting Engineering * Oeotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444-8889 Fax: (972) 444-8893 File No: C10 -1014 Date Sampled: 02/19/2011 Sampled By: McDonald, Jack By Order Of: Cruz Order Number: 1770 REPORT: Nuclear Field Density Test LAB NO: 97796 Test Method: See Below TEST RESULTS Report No: 97796 Page 1 of 2 Optimum Maximum Proctor Moisture Dry Density Proctor No Date N (pcf) Color / Description 97796 -1 02/19/2011 21.0 102.1 Dark Brown Clay Specification Moisture Band Specification No. Compaction, % Minimum Maximum 1 95 -2.0 4.0 Material Test No. Lift # / Depth Location Wet Density (pcf) Moisture Content % Dry Density (pcf) Proctor Number Spec. No. Moisture Deviation Percent Proctor Density Pass Fail 1 -2' 8" Waterline - Clear Creek - Station 122.2 21.0 101.0 97796 -1 1 +0.0 98.9 Pass 11 +25 2 -1' 8" Waterline - Clear Creek - Station 124.5 23.8 100.6 97796 -1 1 +2.8 98.5 Pass 11 +25 3 Final 8" Waterline - Clear Creek - Station 123.3 23.2 100.1 97796 -1 1 +2.2 98.0 Pass 11 +25 4 -2' 8" Waterline - Clear Creek - Station 115.0 29.8 88.6 97796 -1 1 +8.8 86.8 Fail 8 +15 5 -1' 8" Waterline - Clear Creek - Station 112.1 21.4 92.3 97796 -1 1 +0.4 90.4 Fail 8 +15 Orig: City of Coppell (Coppell. TX) Attn. Mr. Keith Marvin, P.E. (1 -cc copy) 1 -cc City of Coppell Attn: Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLES? TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY fNDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NO ?ED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED 'A] FHOUT WRITTEN PERMISSION. YY I ­ t I J E r GEOT GROur Consulting Engineering * Geotechnical Engineering * Construction Materials 3228 Halifax Street, Suite A, Dallas, Texas 75247 Phone: (972) 444-8889 Fax: (972) 444-8893 Acct ID: 1770 File No: C10 -1014 Date Sampled: 02/19/2011 Report Date: 02/22/2011 Sampled By: McDonald, Jack Project: Clear Creek By Order Of: Cruz Location: 8" Waterline Order Number: 1770 Client: City of Coppell REPORT: Nuclear Field Density Test LAB NO: 97796 Test Method: See Below TEST RESULTS Report No: 97796 Page 2 of 2 Material: Wet Moisture Dry Percent Test Lift # / Density Content Density Proctor Spec. Moisture Proctor Pass No. Depth Location (pcf) % (pcf) Number No. Deviation Density Fail 6 Final 8" Waterline -Clear Creek -Station 117.6 23.9 94.9 97796 -1 1 +2.9 92.9 Fail 8 +15 Gauge No.: 17768 Daily Standard Counts: 02/19/2011 DS: 2433 MS: 545 Remarks: Backfill not observed. Pot Hole /Test Pit. Test Methods: ASTM D6938 -07 Orig: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin. P. E, (1 -cc copy) 1 -cc City of Coppell Alin Mr. Rick O'Dell Respectfully Submitted, Alliance Geotechnical Group f� Perry C. Kakara, Sr. Project Manager THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AHD/OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES. NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLEAT AND ARE NOT TO BE REPRODUCED WITHOUT'AARITTEN PERMISSION