Loading...
CARC Exp-CS110307 (3/17/2011) Rhonda Adloo - Coppell Aquatics Center expansionPage 1 From: Tim Oates To:Michael Arellano; Richard Odell CC:David Malone Date: 3/7/2011 5:13 PM Subject: Coppell Aquatics Center expansion The 'proposed' fire hydrant at the SE corner of the project can be eliminated. There is an existing fire hydrant just to the east of this location at the entrance of the fire lane. Based on the square footage of the building, the 3 existing fire hydrants are adequate....min. requirements of 3 hydrants and 3000 gpm.