PA9901-LR000627 CONCRETE COMPRELJ IVE STRENGTH TES „ Fir
ENGINEERING, INC.
a division of lrerracon
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
Date of Service: 05/25/2000 Report No.: 0013854 Report Date
06/27/2000
Client No.: 36503000 Project No.: 94001043
Client: Hisaw & Associates Project: Wagon Wheel Park
Attn: Bill Morgan 154 S. State Road
3116 Keliway Dr., Suite 116 Coppell, Texas
Carrollton TX 75006 pp
Services: Obtain samples of fresh concrete at the placement locations, perform required field test and cast
compressive strength samples.
PROJECT DATA
CONTRACTOR: Hisaw MIX I.D.: 9339
CONCRETE SUPPLIER: Pioneer PLACEMENT DATE: 05/25/2000 BATCH TIME: N/A
PLANT: 22 TIME SAMPLED: 8:44am BY: Mario Garcia
SPECIFICATION REQUIREMENTS WEATHER CONDITIONS: Cool
STRENGTH: 3500 psi @ 28 Days TEMPERATURE (F) - AIR 84 F CONCRETE: 89 F
SLUMP: 4 -6" TRUCK NO: 1824 TICKET NO: 568083
AIR: N/A AIR CONTENT ( %): N/A UNIT WEIGHT (pcf): N/A
TEST METHOD: ASTM C -143 PLACEMENT LOCATION:
Sidewalk on S side of site
ASTM C -172
ASTM C -39
SAMPLE LOCATION: 105' W of SE corner
REPORT OF TESTS ACCUMULATIVE YARDS: 20
CYLINDER MEASURED MAXIMUM COMPRESSIVE
MARKED SLUMP DATE AGE LOAD STRENGTH FRACTURE
SET NO. (inches) TESTED (days) (lbs. force) (psi) TYPE
1 1 6.00 06/01/2000 7 72430 2560
1 2 6.00 06/01/2000 7 71800 2540
Average 2550
1 3 6.00 06/22/2000 28 99310 3510
1 4 6.00 06/22/2000 28 100870 3570
Average 3540
Technician: Mario Garcia Started: 7:OOam Finished: 9:30am ■•
Report Distribution: Engineering, Inc.
(1) Hisaw & Associates
(1) City of Coppell - Engineering Dept. E ric J. Cleveland, P.E.
Senior Project Engineer