Loading...
ST0301A-SP100820N TL CN7 o> a o+ O U •EE- }LO C+ L O LOU owc 3 T+ O +- Z -y a U N m C N UmE Lv o0L LCO 0- U) aN+ E L U) U) a C H+ Oro U CON w ri O . U XLC N a) ~ 00 Lt + LO � N+ E °O > n o L P CC moo ~ L 'D 00 LW+ C:O L COL X 00 0 yi ° c 0 +Nm o •- OE+ WN0 'v c NCO HYm a 0 W 0 ww H J Q � O L� I. GENERAL REQUIREMENTS FOR ALL ELECTRICAL WORK The location of all conductors, conduits, junction boxes, ground boxes, and electrical services is diagrammatic only and may be shifted by the Engineer to accommodate local conditions. Materials shall be new and unused. Materials and installation shall comply with the applicable provisions of the National Electrical Code (NEC), National Electrical Manufacturers Association (NEMA) standards, and shall be Underwriters Laboratories (UL) Listed unless other- wise shown on the plans or specifications or approved by the Engineer in writing. Faulty fabrication or poor workmanship in any material, equipment, or installation shall be justification for rejection. when reference is made to UL, it can be considered to mean a Nationally Recognized Independent Testing Lab (NRTL). Comparable standards of Canadian Standard Association, Electrical Testing Laboratories or Factory Mutual can be equal to the referenced UL standard. Where reference is made to NEMA listed devices, IEC listed devices shall not be considered to be an acceptable equal to a NEMA listed device. Acceptable devices may have both a NEMA and IEC listing. With the exception of high strength bolts, miscellaneous nuts, bolts and hardware may be stainless steel when plans specify galvanized, provided that bolts are 1/2 inch or less in diameter. The Contractor shall provide the following electrical test instruments as required by the Engineer to confirm compliance with the contract and the NEC. Those test instruments are voltmeter, amp probe, megger (1000 volt DC) and torque wrenches. All meters shall have been properly calibrated within one year. Calibration certification shall be provided to the Engineer upon request. Calibration certification tag shall also be applied to the meter. The Contractor shall operate meters during inspection as requested by the Engineer. Grounding shall be as shown on the plans and in accordance with the NEC. Metallic conduit, light poles, luminaires on bridge structures, and all metal enclosures shall be bonded to the system - grounding conductor. The ground rod in each ground box or junction box at the bridge ends, and in each ground box installed for underpass lighting will also be bonded to the system grounding conductor. The grounding conductor shall be bare or, if insulated, shall be green. Ground rods, connectors, and bonding jumpers will not be paid for separately, but will be subsidiary to the various bid items. SUBMITTALS: The contractor shall submit for approval six (6) copies of catalog cut sheets for each of the following three (3) categories. Category 1. Electrical services including photocell. Catagory 2. Breakaway disconnects, heat shrink tubing, heat shrink filler tape, GelCaps and ground boxes which will include loading capacity certification. Category 3. Highmast assembly kits, when applicable. See Item 614 "Highmast Illumination Assemblies ". Submittals shall be legible and shall be marked to indicate which product on a out sheet is to be supplied. Where manufacturers provide warranties and guarantees as a customary trade practice, the Contractor shall furnish to the State such warranties and guarantees. Any deviation from plans or specifications, including deviations due to plan error should be prominently displayed on the submittal. Any changes not prominently noted in submittal and incorporated into the work without proper authorization will constitute grounds for rejection of that portion of the work. II. CONDUIT A. MATERIALS 1. Conduit and fittings shall be UL Listed for the intended use shown on plan sheets. 2. Conduit shall be the type shown by descriptive code or shown elsewhere on the plans. Substitution of the various types of conduits will not be permitted. All flexible conduit in rigid metallic conduit (RMC) systems shall be Liquidtight Flexible Metal (LFMC) conduit. All flexible conduit in PVC systems shall be Liquidtight Flexible Non - metallic conduit (LFNC). 3. All exposed conduits shall be RMC, unless otherwise specifically shown on the plans. All metal conduit shall be properly grounded. 4. Couplings, connectors, conduit bodies, grounding bushings, and offset nipples for RMC shall be electro -zinc plated steel or hot dipped galvanized malleable iron, threaded or threadless compression type, rain -tight and shall be UL listed for the intended use. 5. Expansion joints for metal conduit shall be provided with an internal or external bonding jumper and shall be UL listed. 6. Unless otherwise shown on the plans, junction box minimum sizes shall be in accordance with the following table which applies to the greatest number of conductors entering the box through one conduit with no more than four conduits per box. When a mixture of conductor sizes are present, the conductors shall be counted as if all are of the larger size. Situations not applicable to the table shall be sized in accordance with NEC 370 -28. AWG 3 CONDUCTORS 5 CONDUCTORS 7 CONDUCTORS #1 10" x 10" x 4" 12" x 12" x 4" 16" x 16" x 4" *2 8" x 8" x 4" 10" x 10" x 4" 12" x 12" x 4" #4 8" x 8" x 4" 10" x 10" x 4" 10" x 10" x 4" #6 8" x 8" x 4" 8" x 8" x 4" 10" x 10" x 4" #8 8" x 8" x 4" B" x B" x 4" B•• x 8" x 4" 7. RMC system junction boxes equal to or smaller, in any dimension, than 12 x 12 x 6 (HxWxD), surface mounted and containing conductors #8 or larger, shall be hot dipped galvanized cast iron with minimum wall thickness of 3/16 inch, shall have external - W v w' w w here mounting lugs, and shall be UL listed Crouse Hinds Type AB OZ /Gedne Type YS or approved ed a ual. Unless otherwise shown else g 9 � YP � Y YP PP q on the plans, RMC system junction boxes larger than the aforementioned boxes but equal to or smaller, in any dimension, than 18 x 18 x 6 (HxWxD) shall be 14 -ga. stainless steel; RMC system junction boxes larger than 18 x 18 x 6 (HxWxD) shall be 12 -go. stainless steel. All metal junction boxes shall be equipped with a threaded hole or lug for grounding. Stainless steel boxes 12 x 12 x 6 and larger need not be UL Listed but shall meet the other requirements of the NEC and shall have ribs, stiffeners, or thicker metal and shall have external mounting feet. Junction boxes with an internal volume of more than 100 cu. in. may be supported by connection of two or more rigid metal conduits, where specifically shown on the plans or where approved by the Engineer. 8. Junction boxes containing only X10 or X12 AWG conductors shall be Crouse Hinds Type GRFX, Appleton Type JBOX, two -gang FD, or similar approved cost iron box. Boxes shall be sized according to NEC Table 370- 16(a). 9. IMC and EMT conduit shall not be used unless specifically required by the plan layout sheets. Junction boxes in EMT conduit systems shall be made from galvanized sheeting and shall be UL listed and approved for outdoor use, unless otherwise noted on the plans. Sheet metal junction boxes shall be sized in accordance with the NEC. Junction boxes for IMC conduit systems shall meet the requirements of boxes used with RMC systems. 10. Junction boxes in PVC conduit systems shall be PVC, intended for outdoor use, unless otherwise noted on the plans. 11. Elbows in PVC conduit systems one inch and larger shall be rigid metal, with the exception of traffic signal systems which may have PVC elbows instead of rigid. If any part of the rigid metal elbow is buried less than 18 inches underground the elbow and rigid metal extension shall be grounded. Grounding shall be accomplished by means of a grounding bushing installed on the extension. Un- less specifically shown on the plans, rigid metal elbows containing, or entering ground boxes containing only communications con- ductors, loop detectors, or other low voltage power limited circuits need not be grounded unless a ground wire is present in the conduit or ground box. The rigid metal elbows located in concrete foundations may be extended with PVC conduit and need not be grounded provided that the end of the elbow nearest the end of the conduit run exiting the foundation is at least 2 inches below the concrete. RMC elbows will not be eliminated. RMC elbows will not be paid for directly, but will be subsidiary to various bid items. 12. High- Density Polyethylene (HOPE) conduit shall meet the requirements of Item 622, Duct Cable, except that the HOPE conduit, when bid under Item 618, Conduit, shall not contain factory installed conductors. Fittings for HOPE conduit shall be UL listed as an electrical conduit connector or shall be thermally fused using an electrically heated wound wire resistance welding method. HOPE conduit may be substituted for bored schedule 40 or schedule 80 PVC conduit. When such substitution is made, bored HOPE shall be schedule 40 of the size PVC being replaced. The HOPE conduit shall transition to PVC (or RMC elbow when required) at the bore pit. Size and schedule shall be as shown on the plans. Substituted conduit may not be extended to ground boxes or foundations; RMC elbows shall be installed at ground boxes and foundations. RMC elbows will not be eliminated. 13. All conduit support hardware including straps, nuts, bolts, screws, retaining anchors and washers shall be hot dipped galvanized or stainless steel. Strut type conduit straps shall be stainless steel or hot dipped galvanized. Strut type straps need not be made of malleable type material. Stamped- cadmium plated straps will not be allowed. Straps having only one mounting hole shall not be allowed for use on conduits 2 inches and larger with the exception of electrical service poles where stainless steel standoff straps will be allowed. Two piece conduit straps designed to be used with a mounting shoe shall be installed only with the correctly sized shoe. B. CONSTRUCTION METHODS 1. Conduit in structures shall have expansion fittings at structure expansion joints. All straight runs of RMC conduit exposed on structures such as bridges shall have expansion joints installed at maximum intervals of 150 feet. Expansion joints shall be in- stalled so they allow for movement of the conduit. Installation of the joint in such a manner that will not allow for movement shall be repaired at no expense to the state. The method of determining the final setting length of the expansion joint shall be provided to the Engineer upon request. 2. Conduit supports shall be spaced at maximum intervals of 5 feet. Conduit spacers shall be used with metal conduit placed on surfaces of concrete structures (See conduit mounting options). 3. Conduit supports shall not be attached directly to prestressed concrete beams except as shown specifically in the plans and approved by the Engineer. 4. Unless otherwise shown on the plans, conduit placed beneath existing roadways, driveways, or sidewalks, or after the base or surfacing operation has begun, shall be accomplished by jacking or boring. The Contractor shall back fill and compact the bore pits to the bottom of the conduit prior to installing connecting conduit or duct cable to prevent bending of the connection. 5. Conduit trenched in the subgrade of new roadways shall be backfilled with excavated material, unless otherwise noted on the plans. Conduit trenched in the sub -base of new roadways shall be backfilled with cement- stabilized base. 6. Open ends of all conduit and raceways shall be fitted with temporary caps or plugs to prevent entry of dirt, debris and rodents during construction. The temporary cap may be constructed of duct tape, but in all cases shall be tightly fixed to the conduit and shall be durable. The contractor shall clean out the conduit and prove it clear in accordance with Standard Specifications Item 618.3 prior to installing any conductors. 7. Conduit entry into the top of enclosures such as safety switches, meter cans, service enclosures, auxiliary enclosures and junction boxes shall be made weatherproof using conduit sealing hubs, or threaded bosses. B. A bonding jumper shall be installed from each grounding bushing to the nearest grounding rod, grounding lug, and /or equipment grounding conductor. All jumpers shall be the some size as equipment grounding conductor. Conduit used as casing under roadways for duct cable need not be grounded if duct extends full length through the casing. At electrical services, grounding electrode conductor shall be a solid Copper #6 AWG. 9. Metal junction boxes shall be bonded to the grounding conductor in accordance with the NEC. 10. Conduits entering ground boxes shall be placed so that the conduit ends shall be not less than 3 inches nor more than 6 inches from bottom of box (See ground box detail on sheet ED(3). 11. Conduit ends shall be sealed with heat shrink boots with waterproof sealant, urethane foam, or by other methods approved by the Engineer. Sealing shall be done after completion of any required pull tests. Duct tape shall not be used as a permanent conduit sealant. Silicone caulking shall not be used as a sealant. 12. All strut mounting material and hardware shall be hot -dip galvanized or shall be stainless steel. The out ends of strut and non - galvanized rigid metal conduit threads shall be coated with a zinc rich paint (90% or more zinc content). Zinc rich paint may only be used to touch up galvanized material as allowed under item 445.6 galvanizing. The painting of non - galvanized material with a zinc rich paint shall not be considered as an approved alternative for galvanized materials. 13. All PVC conduit terminations shall be fitted with bushings or bell ends. All metal conduit terminations shall be fitted with a grounding type bushing. Conduit Spacer Conduit I (mounting shoe) u Concrete Structure Conduit Strap, !' Steel expansion malleable, anchor (3/8 in. dia. typ. Hot - dipped goly. 1 in. min., 1� /2in. max. depth) CONDUIT MOUNTING OPTIONS (Attachment to concrete surfaces) (See para. II.B.2) 1 in. min. Conduit Strut Type - Stainless steel or hot dipped galvanized J Conduit Strap Conduit Mounting Channel (B -line, ; Kindorf, Unistrut +, or equal) (Hot dip galvanized) Secure at a min. of 2 places (3/8 " x 1 1/2 " anchors typ.) to structure or as directed by the Engineer. RMC to PVC H or HOPE coupling below grade when PVC or HOPE is shown on layout. Wing Wall Circuit Conduit 3' max. RMC Grade line 2 to 4" Ground Rod Clamp - % " X 8' Ground Rod RMC /z" PVC =4 to 6" #8 Ground Wire Minimum TYPICAL CONDUIT ENTRY TO BRIDGE STRUCTURE DETAIL X /3" 1 D ong a' CONDUIT HANGER DETAIL conc. anchor Existing Kwikbolt, Bridge (Attachment to horizontal surfaces) Parabolt, ` � Slab Hangers need not be UL listed for or equal. electrical use ie: plumber pipe hangers are acceptable Threaded 2" min. coupling 3/8 Dia. linked eyerods welded, Elcen Fig. 690, Grinnel Fig. 278X, Lock or equal nut Adjustable hanger Blow 5/03 Revision R. M. �� Knox Fig. 9 Conduit Elcen Fig. 13, 0 Rev ised or equal notes. /zin. min. Concrete Structure Steel expansion anchor (3/8 in. di a. typ. 1 in. min., 1 1/2 in. max. depth) NOTES ) Ground rod clamp to be UL listed 1 for direct burial. 2.) For conduit placed in structure, use flush - mounted box. 3.) Bond junction box and metal conduits to equipment grounding conductor and grounding electrode conductor using listed connector. 4.) Seal all conduits entering the junction box from underground. 5.) Install bell end or bushing on 1/2 " PVC conduit both ends. 6.) Ground rod to be driven within 8 inches of 1/2 inch PVC conduit end. W C L D Cm7 ° Cu, a O+ O O •EE— }LO C+ L L0rn Owc 3 T+ O +— Z _ y - a) a QCN 0U U0E Lv ooL LCO d U) 0 am+ E L N a) a�Wd a)0L C -H+ Oo O CO WXL HL C, O O .O XLC a) m•- ~mL 00 a> to w }OL T3 n u, m+ E °a > n o L P CL ~ m0. L ' 00 C:O L 00 0 U) ° C O rq T+ L +mur o •- OE+ WN0 10 OE2 -C a J W 0 ww H J Q � O W I. ELECTRICAL CONDUCTORS A. MATERIALS 1. Insulated conductors shall be NEC Type XHHW. Insulated conductors shall be color coded in accordance with the NEC, articles 200, 250, and 310; i.e. Insulation of grounded conductors (neutrals) shall be white. Grounding conductors (ground wires) shall be bare or in- sulation shall be green.Insulation of ungrounded conductors (hots) shall be any color except green, white, or gray. Identification of conductors #6 American Wire Guage (AWG) and smaller shall be by continuous jacket color. Color coding of electrical conductors #4 AWG and larger shall be either by continuous color jacket or by colored tape. Colored tape marker shall consist of a half -lap of tape covering a 6 -inch length of conductor. 2. Where two or more circuits are present in one conduit or enclosure, the conductors of each circuit shall be identified by a permanent non - metallic tag at each accessible location. The tag shall be fastened to the conductors by two plastic straps. Each tag shall indicate circuit number, letter, or other identification shown in the plans. 3. Grounding electrode conductor #6 AWG for bonding to ground rod at electrical service, shall be solid. Connection of conductor to ground rod shall be made using UL Listed connectors designed for such purposes. 4. Heat Shrink Tape filler shall be used to seal the ends of heat shrink tubing around two or more conductors that are insulated with heat shrink tubing. Tape material shall have a minimum dielectric strength of 225 volts per mil and shall be cross - linked butyl rubber. Tape shall be supplied in rolls and shall have a backing (release paper) to prevent the tape from sticking to itself. 5. Heat shrink tubing shall be heavy wall, UL listed for 600 volts or greater and shall have factory applied internal sealant. 6. GelCaps shall be UL listed for 600 -volt applications. GelCap shall have see - through elastomer molded cover. Cover shall be filled with high dielectric insulating gel silicone sealant to provide waterseal. Cover shall be held in place by snap -lock, molded clamp made of UV stable polypropylene. T. Splicing materials, insulating materials, breakaway disconnects, GelCaps and fuse holders will not be paid for directly but shall be subsidiary to various bid items. B. CONSTRUCTION METHODS 1. After conductors have been installed in conduit, a pull test shall be mode on conductors. When any length of conductor cannot be freely pulled, the Contractor shall make any needed alterations or repairs at no expense to the State. 2. The Contractor shall perform insulation resistance tests in accordance with Item 620, "Electrical Conductors." The Contractor shall coordinate with the Engineer to witness the tests. 3. A sufficient length of conductor for making up connections shall be left in ground boxes (2 feet minimum, 3 feet maximum, to point of splice, 3 feet minimum, 4 feet maximum, when conductor is pulled through with no splice), enclosures, weatherheads and pole bases (1 foot minimum, 1.5 feet maximum). 4. Splices shall be made only in junction boxes, ground boxes, pole bases, or electrical enclosures and shall be made with listed compression or screw type pressure connectors, terminal blocks, bolted lugs, or split bolt connectors. Splices shall be insulated with heavy wall heat shrink tubing or GelCaps and shall be made so as to provide a watertight splice. Heat shrink sleeve shall over- lap conductor insulation a minimum of 2 inches on both sides of the splice. Where heat shrink tubing may not shrink sufficiently to provide a watertight seal around the individual conductors, prior to heating the tubing, the Contractor shall increase the diameter of the conductors insulation using heat shrink filler tape to provide a watertight seal between the individual conductors and the heat shrink tubing. Tape shall be visible after completion of all splices. Where filler tape is used but not visible, the Engineer shall approve each individual splice by conducting a physical inspection of each splice. When it appears the tubing has been burned, or overheated the tubing shall be considered to be defective and shall be replaced. 5. GelCaps when used in place of heat shrink method of splicing, shall be sized and installed according to manufacturer's specifications. ( Raychem GelCap and GelCap SL or equal.) 6. Wire nuts may be used for #8 AWG or smaller conductors in above - ground junction boxes, but not in pole bases or ground boxes. Wire nuts shall be positioned upright to prevent the accumulation of water. Wire nuts used at these locations shall have factory applied waterproof sealant. 7. Conductors in illumination poles shall be supported by a J -hook in the top of the pole. 6. All conductors bid under Item 620 "Electrical Conductors" shall have breakaway electrical disconnects installed anytime conductors pass through a break -away support device. 9. For terminating the conductors, insulation - jacketing material shall be removed in such a manner as to not nick any of the individual strands of the conductor. When individual conductor strands are removed, the conductor shall be considered to be damaged. 10. When a conductor or cable has been damaged, or fails to pass an insulation resistance test, the conductor shall be replaced. 11. Duct tape, black electrical tape, or wire nuts shall not be used in the repair of a damaged conductor. 12. For terminations, no more than one wire may be installed under a single pressure connector, unless the device is listed for mare than one wire. 13. Conductors connected to break -away in line fuse holders must be installed in accordance with the specific manufacturer's installation instructions. Where threaded connections are made, they shall be properly torqued. Where crimp type connections are made, crimps shall be made using properly sized crimping pliers. Proper conductor terminations are critical to the safe operation of break -away devices. 14. Waterproofing boots shall be properly trimmed to fit snugly around the conductor so as to provide a water proof connection. No more than one wire may enter a single opening in any one boot. Water proofing boots must provide the correct number of openings. Where only one wire is to be connected to a boot, the boot may not be a two wire type. Heat Heat Shrink Shrink "C" clamp Tape f i l l er .,, a .... p , SPLICE OPTION 1 C -CLAMP Stainless steel or brass machine screw, nut, 2 flat washers, lock washer or self locking nut. Machine screw to be a m of 10 -24, 3/16 or the si size as the mounting ho provided by the manufac Secure wrench tight. Movement of lugs after final assembly shall be considered to be a defective connection. Seal between Conductors with heat shrink tape Tape to extend past end of tubing by 1/8 " to 1/4 ". SPLICE OPTION 2 BOLTED WIRE LUGS Heat Shrink Tape filler SPLICE OPTION 3 SPLIT BOLT Seal between / Conductors with heat shrink tape. Tape to extend past end of tubing by 1/8 " to 1/4 ". Split bolt or other type connector Heat Shrink Tube Increase insulation diameter with heat shrink tape if necessary. Tape to extend past end of tubing by 1/8 " to 1/4 ". See through molded cover SPLICE OPTION 4 GELCAP GelCap shall be sized and installed according to manufacturers specifications e Optional Lug for making connections Snap -lock, molded polypropylene clamp 15. All conduits that contain circuit wiring of 50 volts or more shall contain an equipment grounding conductor (EGC) . Conduit for traffic signals shall have an EGC, with a minimum size of #8 AWG stranded. Unless otherwise shown on the plans, the EGC for all other conduits shall be the same AWG size as the largest current carrying conductor contained in that conduit. The EGC shall be paid for item 620 - Electrical Conductors. C. TEMPORARY WIRING Temporary conductors and electrical equipment to provide power for utilization equipment, shall be installed in accordance with the NEC article 305. All temporary wiring materials and methods shall comply with the standard sheets. All power outlets for portable electrical equipment, power tools, ice machines, ice storage bins and refrigerators located outdoors at grade, supplied from a utility power source, shall be provided with a ground fault circuit interrupter. Residual current protective devices (GFCI) may be any one of the following: molded cord and plug set, receptacle, or circuit breaker type. Where wire nuts are approved for temporary wiring, they shall be of the self - sealing type. All conductor splices must be contained within a listed enclosure, ground box or the splices will be more than ten feet above grade vertically and more than five feet horizontally from any metal structure. Where temporary conductors are installed in any area that is likely to be subjected to vehicle traffic, or mobile construction equipment, the vertical clearance to ground shall be at least 18 feet when measured at the lowest point. Where power conductors are to be supported by a span wire, the span wire shall be properly grounded. Existing conduit containing service conductors uncovered during the construction process shall be repaired in a timely manner in accordance with the NEC. Existing non - metallic conduit exposed during construction shall not be left exposed above grade, or with less than eighteen inches of cover, without protective methods approved by the Engineer. Increase insulation diameter with heat shrink tape if necessary. Tape to extend post end of tubing by 1/8 " to 1/4 ". olt together ugs and prior to pplying heat hrink tubing, pply two layers of heat shrink tape to cover sharp edges. Wrap split bolt connector with heat shrink filler tape to protect heat shrink from sharp edges Seal between Increase insulation Conductors with diameter with heat shrink tape. heat shrink tape Tape to extend if necessary. past end of tubing Tape to extend by 1/8 " to 1/4 past end of tubing by 1/8 " to 1/4 ". 2" min overlap T I U311 I y p. Heat of heat shrink Shrink over wire Tube insulation W C L D Cm7 o> a o+ O O •EE- }LO C }L a 30Cb T} o }— Z -y -' aL QCN 0 a) CID VNE }La ooL LCO 0- U) am} CE- N 0 L C -H} Oo O w HL XLC 00 a> to w ' } T3 n m+ E °a > n� pTN CL qO} 0 L ' 00 0 ary COL +o'o y�C a +mur o •- OE+ WNO 'v C OE2 -C a J W 0 ww H J Q � O L� II. GROUND RODS A. MATERIALS 1. All ground rods installed at electrical services, including supplemental lightning protection ground rods specified by the plans in other locations such as pole bases, shall be copper clad and UL listed. Rods shall be a minimum diameter of 5/8 inch. The length shall be a minimum of 8 feet. Larger diameter or longer length rods may be called for in some specific locations, see the individual plans sheets. 2. Ground rod clamps shall be listed to be in direct contact with the soil. Where concrete encasement is required, the clamp shall be listed for concrete encasement. B. CONSTRUCTION METHODS 1. Ground rods installed in locations such as pole bases, to provide supplemental lightning protection need not be totally in contact with the soil. Where called for in the plans, rods may be encased in soil or concrete or any combination of soil and concrete. When concrete encased, the connection of the conductor to the rod shall be readily accessible for inspection or repairs. When driven into the soil the upper end shall be between 2 to 4 inches below finished grade. Ground rods shall not be placed in the same drilled hole as a timber pole. 2. Ground rods shall be installed such that the end imprinted with the rod's part number is installed as being the upper end. 3. Non - conductive coatings such as concrete splatter shall be removed from the rod at the clamp location. 4. Routing of lightning protection ground rod wires shall be run as short and straight as possible. Where bends are required they shall have a minimum radius of four inches. 5. Unless specifically called for by the plans, conduits used for ground rod wires shall be non - metallic. Where metal conduits are specified, a grounding bushing and properly sized bonding jumper shall be provided and properly installed on each end. 6. Where rocky soil or a solid rock bottom is encountered when driving a ground rod and the horizontal trench placement method is the only viable solution, written authorization from the Engineer must be obtained. III. GROUND BOX A. MATERIALS 1. Ground boxes l6x30x24 inches (WxLxD) or smaller shall be polymer concrete of the type required by the descriptive code shown elsewhere. Larger ground boxes shall be as shown elsewhere in the plans. 2. All ground boxes and covers shall be permanently marked either by impress or by permanent ink, with manufacturer's model number and manufacturer's name or logo. 3. Covers shall be bolted down, and bolt holes in the box shall be arranged to drain dirt. 4. Ground box Types A, B, C, D & E shall meet the following requirements: a. Ground boxes and covers be manufactured from polymer concrete reinforced with continuous strands of woven or stitched borosilicate fiberglass cloth. The polymer concrete shall be made from catalyzed polyester resin, sand and aggregate, and shall have a minimum compressive strength of 11,000 psi. Polymer concrete containing chopped fiberglass or fiber- glass reinforced plastic is not acceptable. b. Minimum inside dimensions shall be as follows (width x length x depth): Type A shall be 11.5 inches x 21 inches x 10 inches, (122311) Type B shall be 11.5 inches x 21 inches x 20 inches, (122322) Type C shall be 15.25 inches x 28.25 inches x 10 inches, (162911) Type D shall be 15.25 inches x 28.25 inches x 20 inches, (162922) Type E shall be 11.5 inches x 21 inches x 16 inches, (122317) c. Bottom edge of box or extension shall be footed with a minimum 1 1/4 inch flange. d. Ground boxes shall withstand 600 lbs. per sq. ft. applied over the entire sidewall with less than 1/4 inch deflection per foot length of box. Ground boxes and covers shall withstand a test loading of 20,000 lbs. over a 10 inch by 10 inch area centered on the cover with less than 1/2 inch deflection. Ground boxes and covers shall meet Western Underground Standards 3.6. Manufacturer shall supply certification by an independent laboratory or sealed by a Texas - Licensed Professional Engineer. e. Covers shall be 2 inch (nominal) thick polymer concrete. All hardware shall be stainless steel. Cover shall be secured with two 1/2 inch stainless steel bolts. Bolts shall be self- retaining and shall withstand a minimum of 70 ft-lbs. torque and shall have a minimum 750 lbs. straight pull out strength. Nuts shall be floating and shall provide a minimum of 1/2 inch movement from the center of the nut. Covers shall be skid resistant, minimum 0.5 coefficient of friction. Covers shall be interchangeable between manufacturers and shall conform to the dimensions shown herein. Unless otherwise approved by the Engineer, cover shall be legibly imprinted with the following words in minimum 1 inch letters: Ground Boxes containing wiring for traffic signals shall be labeled, Danger High Voltage Traffic Signal. Ground boxes containing wiring for illumination systems shall be labeled, Danger High Voltage Illumination. Ground boxes containing wiring for traffic management systems shall be labeled, Danger High Voltage Traffic Management. Ground boxes containing wiring for sign illumination systems shall be labeled, Danger High Voltage Sign Illumination. Ground boxes containing wiring for traffic signals that also contain illumination, powered by the signal electrical service, shall be labeled, Danger High Voltage Traffic Signal. B. CONSTRUCTION METHODS 0 1. Ground boxes shall be set on a 9 inch (minimum) bed of aggregate from 3/4 " up to 2" in size. Aggregate shall be in place prior to setting box and conduits shall be capped. Any gravel or dirt in conduit shall be removed. 2. When required by Item descriptive code, construction of an apron encasing a ground box including concrete and reinforcing steel shall not be paid for directly but shall be subsidiary to the ground box. Reinforcing steel may be field bent. Concrete for aprons shall be considered miscellaneous concrete for testing purposes. Aprons shall be cast in place. 3. Conduit holes may be cut in the walls of type B & D boxes at least 18 inches beneath the cover. 4. If, within the limits of this project, the Contractor must utilize an existing ground box equipped with a metal cover, the Contractor shall bond the cover to the grounding conductor with a 3 foot long flexible stranded jumper the same size as the grounding conductor. Connection of bonding jumper to metal ground cover shall not be paid for directly but shall be sub - sidlary to various bid items. The box(es) must be clearly shown on the plans with plan notes fully describing the work required. 5. If there are other ground boxes with metal Covers within the project limits but not involved in the contract, the Engineer may direct the Contractor to ground the covers, designating and identifying the specific boxes in writing. This work will be paid for separately. 6. Termination to metal ground box covers shall be made using a tank ground type lug. No. 3 Reinforcing steel - - -- 10 in. �� ------ - - - - -\ (typ.) I 10 in. (Typ) I I A I A _1 I I I I I� 2 in. 2 in. PLAN VIEW Ground box No. 3 Apron Class A 10" Reinforcing Concrete (t steel \ I ---- Ground box IT Grounding bushing Conduit or duct cable Rigid metal conduit ell SECTION A - A APRON FOR GROUND BOXES (Where required) (1) Final position of end of conduit shall not exceed one -half the distance to the side of box opposite the conduit entry. (2) Place gravel "under" the box. not "in" the box. Gravel should not encroach on the interior volume of the box. (3) Install bushing on the upper end of all ells. (4) Where a ground rod Is present in the ground box, connect it to any and all equipment grounding conductors using a listed connector. (5) Maintain sufficient space between all conduits so as to allow for proper installation of bushings. (6) All conduits shall be installed in a neat and workmanlike manner. (7) All conduits installed in the ground box shall be sealed after completion of conductor installation and any required pull tests. Silicone shall not be used as sealant. For cover logo see III.A.4.e u., i o o.,. I/_ 12" min. 9" Gravel fill (2) J H J k P 1 - - - SIDE END GROUND BOX COVER 5/03 Revision 0 Revised notes. PLAN VIEW GROUND BOX COVER DIMENSIONS BOX DIMENSIONS (INCHES) SIZE H I J K L M N P A, B & E 23 1 /4 23 13 /4 13 I /2 9 7 /s 5 1 /8 3 /s 2 C & D 30 1 /2 30 1 /4 17 1 /2 17 I/n 13 1 /4 6 3 /4 1 3 /s 2 5/03 Revision 0 Revised notes. PLAN VIEW W C L D Cm7 o a o+ O U•- T m EEOEEO CtL LL 0wC 3 T} o +— Z _ y a U N a) ¢0U a) CID V E a)0 }La LCO a lnln am+ E L U) a) 0L C —H} DO 0 w HL O . 0 0 XLC a) >. 00 a> In w }OL LO �T3 m+ E °O > n pTN CC ~ q0+ L ,u w+ 0 00 0 Ins o +my D .- OE+ WN0 '10 C Q)C0 HYN a J 0 ELECTRICAL SERVICES NOTES All work, materials, services, and incidentals, whether or not specifically shown on the plans, which may be necessary for a complete and proper electrical service installation as specified in the plans to obtain electrical power shall be paid for, performed, furnished and installed by the Contractor. The Contractor shall contact the Utility for metering and shall comply with all Utility requirements. Primary line extensions, connection charges, meter charges, and other charges by the Utility company to provide power to the location shown, when required, shall be paid for under force account work. The costs associated with these charges shall be approved by the Engineer prior to engaging the Utility company to do the work. The Contractor shall consult with the appropriate Utility to determine costs and requirements, and shall coordinate the Utility's work as approved by the Engineer. The Contractor shall be reimbursed only the amount billed by the Utility. No additional amount for supervision of the Utility's work will be paid. Materials shall be new and unused, materials and installation shall comply with the applicable provisions of the National Electrical Code (NEC) and National Electrical Manufacturers Association (NEMA) standards and shall be Underwriters Laboratories (UL) Listed. Electrical Service conduits, conductors, disconnects, contactors, circuit breaker panel sizes, and branch circuit breakers, shall be as shown in the Electrical Service Data elsewhere in the plans. Faulty fabrication or poor workmanship in any material, equipment, or installation shall be justification for rejection. The Contractor shall submit for approval no less than six (6) copies of catalog out sheets on electrical service materials. Submittals shall be legible and shall be marked to indicate which product on a cut -sheet is to be supplied. Where manufacturers provide warranties and guarantees as a customary trade practice, Contractor shall furnish to the State such warranties or guarantees. The Contractor shall provide locks keyed with Master x2195 for all lockable electrical enclosures. Keys and locks become property of the State. Unless otherwise approved by the Engineer, enclosures shall not be energized until locks are provided and all bolts are installed. Circuit directories, where provided, shall be filled out. All breakers and components in shop built panels and enclosures shall be labeled with duo - colored plastic labels. Letters shall be a minimum 3/8 " in height. Enclosures with external disconnects that de- energize all equipment inside the enclosure, need not have dead front trim, except that incoming line terminations shall be protected from incidental contact. When galvanized is specified for nuts, screws, bolts or miscellaneous hardware, stainless steel may be used. All wiring and components shall be rated for 75 degrees C. Minimrn size for service entrance conductors shall be u6 XHHW. I. Safety Switch. A safety switch, placed ahead of the meter, shall only be used when specified by the Utility and when shown on the Electrical Service Data. The switch shall be UL Listed, heavy duty type, 600 volt, unfused, with a UL type 3R enclosure and equipped with a solid neutral (s /n) assembly. The switch shall be padlockable in the "on" position. II. Service Type. Electrical service types A, C, D, and T shall be as schematically detailed on ED(4) or ED(5). Other service types shall be as detailed elsewhere on the plans. III. Branch Circuit Breakers. Circuit breakers shall be thermal magnetic and have a minimum interrupting capacity of 10,000 amps and a voltage rating compatible with their use. Circuit breakers shall be sized as shown in the electrical service data. Circuit breakers in panelboards and load centers shall be full size and designed exclusively for the ponelboard or load center in use. Tandem and half -width breakers shall not be used. All circuit breakers shall be permanently and clearly marked identifying the circuit or device supplied. Circuit breakers shall be UL Listed to UL489. IV. Circuit Breaker Panelboard. Panelboards shall be UL Listed. Panelboards shall have copper busses, a minimum of 6 one -pole spaces or as required in the electrical service data, and when required will be rated for service equipment. Enclosure shall meet or exceed UL type 3R classification. Panelboards shall have a threaded hub conduit entry for conduit entering the top of the enclosure. Circuit breakers shall be bolt -in type only. V. Circuit Breaker Load Center. Load centers shall be UL Listed. Load centers for type T services may have copper or aluminum busses, all other load centers will be copper bus only. Load center will have a minimum of 4 one -pole spaces, and shall be rated for service equipment. Enclosure shall meet UL type 3R classification. Load centers shall have a threaded hub conduit entry for conduit entering the top of the enclosure. Circuit breakers shall be plug -in type only. Load centers for type T services shall accomodate a maximum of 6 one -pole breakers. VI. Separate or Auxiliary Enclosure. Separate enclosures for HOA, photocell and lighting contactors for types D & T Services shall be a UL Listed assembly with outer door. Interior shall have dead front trim. HOA switch operator shall extend through the dead front trim. Photocell shall be mounted inside the enclosure as described in paragraph XIII when required by descriptive code. Separate enclosures shall meet the construction requirements of paragraph VIII. E, except that separate enclosure shall not have external operating handle, need not have a data pocket and door may latch at only one point. All equipment may be located in one enclosure instead of two, when approved by the Engineer. VII. where a Type D or T service is provided, laminated "as built" drawings are required as shown on ED(5) VIII E; shall be delivered before completion of the work, to the Engineer in lieu of placement within these smaller enclosures. Conduit may not enter the back wall of a service enclosure penetrating the equipment mounting panel. Provide grounding bushings on all metal conduits, terminate bonding jumper to grounding bus. Grounding bushing is not required when the end of the metal conduit is fitted with a conduit sealing hub or threaded boss such as a meter base. EXPLANATION OF ELECTRICAL SERVICE DESCRIPTIVE CODE ELEC SERV TY X (XXX /XXX) XXX Schematic Type — T-7- Service Voltage (V / V ) Disconnect Amp Rating (000 indicates main lug only) SS= Safety switch ahead of meter NS= No switch ahead of meter and /or no meter required Enclosure Type GS= Galvanized steel (see ED(5)VIII,D) SS= Stainless steel AL= Aluminum Photocell Mounting Location T= Top of pole E= Inside service /separate enclosure L= Luminaire mounted N= None Service Support Type GC= Granite concrete OC= Other concrete TP= Timber pole SP= Steel pole SF= Steel frame OT= Pole by others or paid for separately EX= Existing pole TS= Switch gear to be placed on traffic signal pole RT= Rectangular structural tubing PS= Pedestal Service (see ED(5)VIII,G) Color code 6" length of neutral conductors' insulation Color code with white tape where conductor 6" length of exits the weatherhead. 120 L1 or L2 E conductors' insulation Do not bond 240 with red tape Neutral bus to Neutral where conductor auxiliary when © I exits the enclosure required O weatherhead. 12 13 r G N G N N G Ground 1; 1 11 Rod Typical Typical Typical 240 Volt 120 Volt 120 / 240 Volt Luminaire Branch Circuit Branch Circuit Branch Circuit SCHEMATIC TYPE T 120/240 VOLTS -THREE WIRE Install photocell and lighting contactor when shown on Electrical Service Data. SCHEMATIC LEGEND Pole brand 1 - Class 5 pole, height as required Cut top of LIQUIDTIGHT FLEXIBLE 2 - Service drop from utility company pole to enhance O (attached below weatherhead) run off when Jv9 3 - Service conduit and service required by be used when meter and service entrance conductors(RMC) serving utility © ® (See Electrical Service Data) "IST 4 - Safety switch (when required) be securely supported within one ft. of 5 - Meter (when required) each end. No strap required for 6 - Service enclosure Bushing 2" to 6" 7 - 0 0 0 N 6 bare grounding electrode C i r c u i t 4" typ. conductor in 1/2 " PVC to grounding fitting. 7 ground rod - extend 1/2 "PVC 6" Point of attachment within the LFMC. underground. to be below - Bend in liquidtight flexible metal 8 - 5/8 " x 8' Copper clad weatherhead \ ground rod - drive ground rod 6:: C O completely installed conductors, at least six underground unless inches of free conductor movement shall D otherwise approved by the Engineer. be demonstrated to the satisfaction of N 9 9 - RM conduit - same size as branch E E circuit conduit. SERVICE 3 10 - Photocell and conduit - 1 O ® if top mounted. Upper end of ground (See Electrical Service Data) Provide FD 1-box, 4" below finished grade 11 - When required by the serving and 1/2" to utility provide bare #6 awg copper clearance from conductor. Run wire from pole top pole to photo- to butt wrap or copper butt plate. cell 1 1 Protect conductor to a height of 8 ft above finish grade. Pole brand must be QTxDOT Apri 1 1998 LIQUIDTIGHT FLEXIBLE 5 feet CK: rxoor o : TX OT METAL CONDUIT (LFMC) or less above (If applicable) grade. Jv9 - Liquidtight flexible metal conduit, may HIGHP10 3 -03 be used when meter and service enclosure are mounted 90 to 180 degrees © ® to each other. Size shall be same as service entrance conduit. "IST LFMC shall not exceed 3 ft. and shall 6" to 10" 1-10 be securely supported within one ft. of typical each end. No strap required for LFMC shorter then 12" Bushing Couple to - Each end of LFMC must have a grounding or Be 1 1 C i r c u i t bushing or be terminated with a Conduit grounding fitting. 7 - A neutral conductor must be installed within the LFMC. - Bend in liquidtight flexible metal conduit shall not exceed 180 degrees. - A pull test is required on all 6:: C installed conductors, at least six typ. inches of free conductor movement shall D be demonstrated to the satisfaction of N 9 the Engineer. E E W SERVICE SUPPORT TYPE TP (0) (timber pole, overhead service, typical arrangement) ® Upper end of ground rod to be 2" to 4" below finished grade TIMBER POLE NOTES 1. Conduit and electrical conductors attached to the electrical service pole and underground within 12 inches of service pole shall not be paid for directly but shall be subsidiary to the service pole. 2. Pole top mounted photocell, install on north side of pole or in service enclosure as required. See Electrical Service Data. 3. Attach mete and service equipment with stainless steel or galvanized channel r (Unistrut, Kindorf, or equal). Gain pole as required to provide flat surfaces for each strut. Paint ends of galvanized channel with zinc rich paint. Gain depth 5/8" max. Gain height 1 7/8" max. Strut to be 1" max. deep, and 1 5/8" wide max. Secure each strut section to timber pole with two galvanized or SS lag bolts, 1/4" diameter min. by 1 1/2" length min. Place flat out galvanized or SS washer on each lag bolt. Gain pole in a neat and workmanlike manner. 4. Embedment depth shall be as required in Item 627 Treated Timber Poles. 5. Poles trimmed for excess length shall be trimmed from the top end only. 1 - omitted 2 - Meter (when required) 3 - Service Assembly Enclosure 4 - Main Disconnect Breaker (Not Used) 5 - Omit 6 - Circuit Breaker, 15 Amp typical for control circuit wiring 7 - Auxiliary Enclosure 8 - Control Station ( "H -O -A" Switch) 9 - Photo Electric Control (enclosure- mounted shown) 10 - Lighting Contactor 11 - Power Distribution Terminal Blocks (Not Used) 12 - Neutral Bus required when 120 v. lights are controlled by lighting contactor 13 - Branch Circuit Breaker (See Electrical Service Data) 14 - Circuit Breaker Panelboard (Not Used) 15 - Load Center 16 - Ground Bus Power Wiring - - - - Control Wiring — N — Neutral Conductor (when required -to serve 120 v. loads only) — G— Equipment grounding conductor - always required ELECTRICAL DETAILS — SERVICE SCHEMATICS AND SUPPORT —TYPE TP (OVERHEAD) 0= Overhead service a U= Underground service o� Standard 3 -prong Photocell Receptacle and photocell Type FD Box 6" - T - 1/2" RM �► Conduit, bend to provide 1/2" to 1" clearance between photo- cell and pole. Conduit mounting channel(Unistrut, Kindorf, B -line or equal) Within 6" to 8" of top of pole or 18 to 20 feet above finished grade or as directed by Engineer, and as allowed by utility company. l�Serv1ce support TOP MOUNTED PHOTOCELL Conduit support spacing 3 feet from enclosure; 5 feet max. Photocell mounted inside enclosure Bracket attached to equipment mounting pan one each aid of enclosure Three prong recept. on each side of enclosure Enclosure wall Two viewing windows, one on each side of the enclosure ENCLOSURE MOUNTED PHOTOCELL (XX) XX (X) XX (X) Example: ELEC SERV TY A(240 /48O)l00(NS)SS(E)GC(0) I For photocell specifications see ED(5),XIII. Texas Department of Transportotlon Traffic Operations Division ED (4) —03 QTxDOT Apri 1 1998 i.: rXDOr CK: rxoor o : TX OT I CK: TOOT 12 REVISIONS Cv T S _ Jv9 1 HIGHP10 3 -03 "IST I 1 "'- T1 1H i, 0= Overhead service a U= Underground service o� Standard 3 -prong Photocell Receptacle and photocell Type FD Box 6" - T - 1/2" RM �► Conduit, bend to provide 1/2" to 1" clearance between photo- cell and pole. Conduit mounting channel(Unistrut, Kindorf, B -line or equal) Within 6" to 8" of top of pole or 18 to 20 feet above finished grade or as directed by Engineer, and as allowed by utility company. l�Serv1ce support TOP MOUNTED PHOTOCELL Conduit support spacing 3 feet from enclosure; 5 feet max. Photocell mounted inside enclosure Bracket attached to equipment mounting pan one each aid of enclosure Three prong recept. on each side of enclosure Enclosure wall Two viewing windows, one on each side of the enclosure ENCLOSURE MOUNTED PHOTOCELL (XX) XX (X) XX (X) Example: ELEC SERV TY A(240 /48O)l00(NS)SS(E)GC(0) I For photocell specifications see ED(5),XIII. Texas Department of Transportotlon Traffic Operations Division a) TL Cm7 o a o+ O O •EE- }C o } w LO Ot owc 3 Tt o +— Z _ y - a) a QCN 0U U0E Lv O a 0 LCO O mm am+ CE- poi C H + DO 0 LuXL m ~ 0 XLC a) a)•- �(D 00 a) to w T3 m+ E °a > CL P CL moo ~ L ,u w+ C:O L 000 0 0 moo o vy +mm o •- OE+ WN0 'v c wC0 -C a 0 ww H J Q � O L� SERVICE ENCLOSURE NOTES VIII.Service Assembly Enclosures. All service assemblies and enclosures shall be UL Listed for the intended purpose. A. Shop built or shop assembled service assemblies (all types except Type T and Type D without lighting contactor or enclosure mounted photo cell) and all auxilliary equipment enclosures mounted with service equipment and paid for as part of Item 628, "Electrical Services ", shall be built or assembled by a UL Listed Industrial Control Panel shop and shall have a unique serial numbered UL Label with the words "LISTED ENCLOSED INDUSTRIAL CONTROL PANEL ". The some or an additional label shall have the name, location, and phone number of the shop, the UL file number of the shop, the shop order or drawing number, date of manufacture or assembly, and the line voltage. The service assembly enclosure shall also be labeled "SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT ". B. Conduit entries into the top of enclosures shall have threaded hub. Conduit entries through the equipment mounting back plate will not be allowed. C. All service enclosure front doors shall be permanently labeled "DANGER HIGH VOLTAGE ". Label shall be a self sticking type, intended for outdoor installation. Lettering style, layout and colors of red, black and white shall be as required by OSHA. Label letters shall be 1 to 1 1/2 inches high or as high as the enclosure door width will permit for smaller services. Separate or auxiliary lighting enclosures need not be OSHA labeled when mounted in the same viewing plane as the service enclosure front door. where only one type of load is served by the service, the service door shall be marked using duo- colored plastic labels or self adhesive vinyl weather resistant labels, minimum of 1 inch high; applied in a neat and workmanlike manner. On the label will be the service number shown on the plans as well as Identifying the load served specifically (i.e. lighting, landscaping, signals, traffic management or other wording as directed by the Engineer). Safety switches need not be OSHA labeled unless specifically required by the serving utility. D. Type GS enclosures will only be allowed for service Types D and T without an enclosure mounted photocell and /or lighting contactor and the Type C Danelboard. This spec will allow an "off the shelf' product meeting these specifications to be used. Type GS enclosures shall be made from pre - galvanized steel sheeting, hot dipped galvanized steel, or powder coat painted steel unless shown differently on the plans. Steel enclosures shall be painted inside and outside; galvanized enclosures may be painted. Unless otherwise approved by the Engineer, painted enclosures shall be gray, beige, white or light green. Panelboard /loadcenter enclosures shall meet UL type 3R require- ments, shall have a dead front trim, and an outer padlockable door preventing unauthorized persons from operating contained equipment. Galvanized steel is no longer allowed for Types A,C,or custom -built D or T enclosures. If GS is shown in the descriptive code for any of these, an AL shall be provided. E. T AL enclosures for service Types A and C shall meet UL type 3R requirements and shall also meet additional requirements of this Type YPe YP q q paragraph. The enclosure shall have both a main disconnect remote operator handle and a door latch handle. Die -cast handles are not accep table. The main disconnect remote operator shall be flan e- mounted shall interlock the door when in the "on" p osition, and shall be D De g r D padlockable in both the "on" or "off" positions. Door latch shall latch at two or more points, operate by a handle separate from dis- connect switch and be capable of being locked. Door closure clamps will not be allowed. Lock must be keyed to Master *2195. All the enclosures shall have either a continuous stainless steel piano hinge with stainless steel pin or enclosures less than 30 inches may have two heavy duty hinges, those over 30 inches must have three. Heavy duty two and three point hinges shall have a 0.185 inch minimum diameter electro -zinc plated steel pin or a stainless steel pin. Two point hinged doors shall be rated for 56 IDs of loading. Three point hinged doors shall be rated for 70 IDs of loading. The door shall have an attached data pocket constructed of either thermoplastic or metal. Pocket shall be 12" x 12 ", unless that size will not fit in enclosure. The pocket shall then be as large as possible, as approved by the Engineer, and mechanically attached with stainless steel nuts and bolts, or stainless steel or aluminum rivets. Enclosure shall include an equipment mounting panel installed inside the enclosure on collar studs or tapped bosses, and constructed of a minimum 12 gunge galvanized steel. Equipment mounting panels shall not be painted. Enclosure shall have factory installed external mounting feet. Enclosure door shall be capable of opening at least 130 degrees, with arm or other approved means to hold the door open. Only the enclosure exterior will be primed and painted. Paint color shall be beige or gray and shall be powder coat paint as shown below. Condensation drainage shall be provided in the bottom of the enclosure before leaving the factory. The Contractor shall prepare and submit a schematic drawing unique to an individual service. The approved drawing shall be laminated and placed in the document Docket of the service at the time of shipment to the job site. All applicable wiring diagrams and plan sheet layouts for all equipment and branch breaker circuits supplied by that service shall also be laminated and placed in the document pocket prior to shipping. Type AL enclosures for Type D and T services with enclosure mounted photocell and /or lighting contactor shall have the loadcenter interior mounted in an enclosure with properly adapted dead front trim. Types D and T shall not have a loadcenter exterior "can" mounted inside another enclosure meeting these specifications. (Do not put one enclosure inside another enclosure). Types D and T with enclosure mounted photocell and /or lighting contactor shall meet the additional requirements of this paragraph except that remote- operating handle will not be provided. F. Type SS enclosures for Type A and C shall meet all the requirements above for their respective type AL. Type SS enclosures for D and T shall meet all the requirements above for their respective type AL. Stainless Steel shall not be painted. G. PS enclosure shall be as detailed and specified on ED(8). Galvanized steel will not be allowed for any pedestal service. If GS is shown in the descriptive code an AL will be provided. IX. Powder Coat Paint. Powder coating shall be either a polyester thermosetting resin, a zinc rich primer with a TGIC (triglyoidyl isooyanurate) powder overcoating, or a zinc - rich epoxy powder, applied by either electrostatic spray or fluidized bed immersion, high temperature oven cured, high density, low gloss, 4 mil thick (minimum), coating. Adhesion shall meet the 5A or 5B classifications of ASTM D3359. Finish shall be uniform in appearance and free of scratches. X. Main Disconnect. Main disconnect device shall be a circuit breaker, as specified in the Electrical Service Data, shall be two or three pole, and rated for the voltage and amperage specified. Circuit breaker shall be an UL Listed thermal- magnetic circuit breaker controlled by flange - mounted remote operator in the service assembly enclosure when required. Circuit breakers shall have a minimum interrupting rating of 10,000 Amps. when the utility company provides a transformer larger than 50 KVA, Contractor shall verify that the available fault current is less than the circuit breaker amps interrupting capacity (AIC) rating and shall provide documentation from the Utility to the Engineer. Documentation shall be submitted at the some time as other electrical submittals. Circuit breaker shall be UL Listed to UL489. No backfed breakers will be allowed for use as a main disconnect. XI. Control Circuit. Control circuit protection shall be 15 amp circuit breaker. XII. Control Station ( "H -O -A" Switch). Control station shall be a maintained- contact, three position selector switch in an UL type enclosure. Switch shall be rated 600 volts and shall be fitted with "Hand -Off- Auto" legend. XIII.Photc Electric Control. Photo electric control shall consist of a photocell, internal lightning arrester, and relay or bimetallic switch mounted inside a weatherproof enclosure with standard 3 -prong twist lock photocell plug and receptacle.The enclosure shall be made of poly - acrylic with clear acrylic window. Enclosure chassis shall be molded thermosetting plastic. The photocell shall have a polyethylene gasket, and shall have a hermetically sealed cadmium sulfide cell. The arrester shall have an enclosed type expulsion arrester rated 2.0 kV sparkover with 5,000 amps follow- through. Relay or switch shall be time delay type with normally closed contacts. Photo electric control shall be rated a minimum of 1800 VA, voltage as required. Enclosure mounted photocells shall be the some as above except that the photocell shall be mounted inside the enclosure. The enclosure shall have two acrylic paned windows, or other material approved by the Engineer, one on each side of the enclosure. Each window shall be rectangular approximately one inch by two inches, round 2 inch diameter, or as otherwise approved b the Engineer. Bracket and photocell's receptacle will be mounted inside enclosure next to each window. Except for window side PP Y 9 Ph P P 2" of clearance is required on all sides of photocell for ease of replacement. The photocell's receptacle is held in place by two mounting screws on bracket and located next to each window of the enclosure. The 3 -prong twist lock photocell shall be mounted in a position to receive light from the window closest to the photooell.The photocell shall be mounted in a position to receive light from one window. Top of pole mounted photocells shall be mounted as shown on ED(4). The Contractor shall be responsible for proper operation of the photo- electric control. The Contractor shall nave and /or adjust or shield the photocell from stray or ambient nighttime light or shall make any other adjustments required for proper operation. The photocell shall face North when practicable. Unless otherwise shown on the plans, the photo- cell shall turn on the illumination system at 1.0 -( -) 0.5 footcandle and turn off the illumination system at two footcandles higher than turn on. XIV. Lighting Contactor. Lighting contactor shall be a UL Listed NEMA rated lighting contactor, two -pole or multipole as required, electrically held type designed to control high pressure sodium lighting loads, with silver alloy double break contacts rated at 240 volts, 480 volts or 600 volts as required. Lighting contactor shall not be the DIN rail mounted type. XV. Power Distribution Terminal Blocks. Power distribution terminal blocks shall be rated for 600 volts and shall be used for line side connections to branch circuit breakers where more than one circuit breaker is required. Lugs on blocks shall be properly sized for conductors being used. Only one conductor shall be placed under each lug. XVI. Neutral /Ground Bus. Neutral /ground bus shall be a factory made bus permanently bonded to the enclosure with properly sized lugs for grounding and neutral conductors. Color code 6" length of neutral conductors' insulation with white tape where conductor exits the weatherhead. Color code 6" length of L1 or L2 conductors' insulation with red tape where conductor exits the weatherhead. Two Photocell viewing windows not shown but required when photocell is listed as enclosure mounted. Windows not required when photocell is listed as pole top mounted. I� 1 / 10 J � l O - I I I I 13 I Q ) I SCHEMATIC TYPE A THREE WIRE Maximum feeder circuit size (High Mast Poles): 100 amps for two pole 480V, 125 amps for one or two pole 120V or 24CV. Maximum branch circuit size: 50 amps. Color code V1 V2 E Color code 6" length of 6" length of _ L1 or L2 conductors' insulation neutral Q with red tape where conductor conductors' exits the weatherhead. insulation with white tape where conductor exits the weatherhead. Do not bond this bus to the enclosure I I E -0-1 n 04 Two Photocell viewing windows Q not shown but required when photocell is listed as enclosure haunted. Windows not required / when photocell is listed as pole top mounted. Q - — - — - — - — - 3 4 -- I 1 I I I I 6 I I ©I o O 1111 Color code Color code 6" length of � 6" length of neutral 12012401 L1 or L2 conductors' conductors' insulation insulation with white tape with red tape where conductor where conductor exits the exits the weatherhead. A \ p / n , weatherhead. F - A - - - J I � Two Photocell viewing win dows Bonding not shown but jumper required when photocell is listed as enclosure mounted. Windows not required when photocell L I is listed as 1 t 10 pole top mounted. L _ --- - I 11 G N G Ground Rod Typical Typical 120 Volt 240 Volt Branch Circuit Luminaire Branch Circuit SCHEMATIC TYPE D ICI Typical 120 / 240 Volt Branch Circuit 120/240 VOLTS - THREE WIRE Install photocell and lighting contactor when shown on Electrical Service Data. See Type D service notes. TYPE D SERVICE NOTES Photocell and lighting contactor shall be located either in the same UL type 3R enclosure with load center or, if approved b YP � PP Y , Engineer, in separate enclosure. There shall be a window on each 9 D side of enclosure to allow operation of photocell. Both photocell contactor and breaker area shall have dead front trim. Enclosure, DDo except for RT and PS supports, shall not exceed 36 inches in D height or 16 inches in width unless approved by the Engineer. Ty D load center with lighting controls or TY D separate lighting control enclosure shall have power distribution blocks for a minimum of 4, •8 conductors per phase. Ground Typical Branch Rod Circuits SCHEMATIC LEGEND Ground ! i i 1 - Safety Switch (when required) 12 - Neutral /Ground Bus Rod Typical Branch 2 - Meter (when required) 13 - Branch Circuit Breaker (See Electrical Service Data) Circuit 3 - Service Assembly Enclosure 14 - Circuit Breaker Panelboard (See Electrical Service Data) 4 - Main Disconnect Breaker (See Electrical Service Data) (If Type C is shown as AL or SS on descriptive code, this is the service SCHEMATIC TYPE C 5 - Omit assembly enclosure only. Panelboard enclosure is GS unless otherwise noted. 6 - Circuit Breaker, 15Amp 15 - Load Center THREE WIRE 7 - Auxiliary Enclosure 8 - Control Station ( "H -O -A Switch) Power wiring Maximum feeder c i r c u i t s i z e ( High Mast Poles): 9 - Photo Electric Control (enclosure - mounted shown) - - - - Control wiring 100 amps for two pole 4BOV, 125 amps for one 10 - Lighting Contactor —N— Neutral Conductor (when required) serve 120 v. loads only) or two pole 120V or 240V. Maximum branch 11 - Power Distribution Terminal Blocks — G — Equipment grounding conductor - always required circuit size: 50 amps. Color code Color code 6" length of � 6" length of neutral 12012401 L1 or L2 conductors' conductors' insulation insulation with white tape with red tape where conductor where conductor exits the exits the weatherhead. A \ p / n , weatherhead. F - A - - - J I � Two Photocell viewing win dows Bonding not shown but jumper required when photocell is listed as enclosure mounted. Windows not required when photocell L I is listed as 1 t 10 pole top mounted. L _ --- - I 11 G N G Ground Rod Typical Typical 120 Volt 240 Volt Branch Circuit Luminaire Branch Circuit SCHEMATIC TYPE D ICI Typical 120 / 240 Volt Branch Circuit 120/240 VOLTS - THREE WIRE Install photocell and lighting contactor when shown on Electrical Service Data. See Type D service notes. TYPE D SERVICE NOTES Photocell and lighting contactor shall be located either in the same UL type 3R enclosure with load center or, if approved b YP � PP Y , Engineer, in separate enclosure. There shall be a window on each 9 D side of enclosure to allow operation of photocell. Both photocell contactor and breaker area shall have dead front trim. Enclosure, DDo except for RT and PS supports, shall not exceed 36 inches in D height or 16 inches in width unless approved by the Engineer. Ty D load center with lighting controls or TY D separate lighting control enclosure shall have power distribution blocks for a minimum of 4, •8 conductors per phase. Ground Typical Branch Rod Circuits W TL o> w o+ O 0 :t T a) E C t L LL owc 3 T+ O }— Z -y a U N m ¢00, a) CID V E a)O }LL o0L LCO 0 - U) am+ CE- 0L C H+ Oro U w rL XLC 00 a> to r }OL LO m dD Q. CL P CL moo ~ L ' 00 C 00 0 w ii CC 0 L +mm L • OE+ WN0 'LC OE2 -C w a W 0 ww O J O L� , /z d' V (typ. ) ra ius ___F 1 = NOTE: 1 rough edges shall II II be ground smooth II J I I I � L 2J Drain hole for gale. I/ 2 - places � (typ.) M6 X16 " nF m' .. TOP OF POLE TYPE SF & SP I " 'A .. BOTTOM OF POLE Safety switch (w hen required) + 3 ci � max. 0 18" RMC to utility Color code 6" of grounded neutral conductors insulation with white tape where conductor exits the weatherhead. Color code 6" of L1 or L -2 Hot - ungrounded conductors insulation with red tape where conductor exits the weatherhead. Conductor free length, 12" min., 18" max. ce Enclosure Ground Rod 5 /e " x 8 ' upper end to o be 2 to 4" below finish grade 6" to 1� 6" 18 .. RMC Bushing PVC or Bell SERVICE SUPPORT TYPE SP (U) UNDERGROUND SERVICE WITH SAFETY SWITCH Varies SAFETY O SWITCH 72" METER above grade Max. T F RMC /z" PVC with #6 ground wire 20" min. Install bell or bushing on both ends 12" dia. x 36" depth foundation 4 - #4 reinforcing bars and #2 spiral (typ.) Number of mounting channels, as required Threaded boss DANGER 1 60" HIGH above VOLTAGE grade (typ.) RMC for branch circuits above ground (typ) 5" p" 1 din. x 46" 1 W ' foundation 4" (typ. ) ir — RMC 0 U n Provide grounding bushings on all metal conduits, terminate bonding jumpers(min. #6 AWG. Copper) to grounding bus. Grounding bushing not required when conduit end is fitted with a conduit sealing hub or a threaded type of boss such as a meter hub. Channel bracket or other arrangement approved by the Engineer. ( Kindorf, Unistrut, B -line or equal.) Ground Rod %" x B', G upper end to o be 2 to 4" below finish 6" to grade 2 10.. Jconcret�e 6" 18 .. RMC Bushing PVC or Bell 12" dia. x 60" depth foundation 4 - #4 reinforcing bars and #2 spiral (typ.) SERVICE SUPPORT TYPE SP (0) OVERHEAD SERVICE WITH SAFETY SWITCH SERVICE SUPPORT TYPE SF (U) UNDERGROUND SERVICE WITHOUT SAFETY SWITCH 4 - #4 reinforcing bars Ground Rod and #2 spiral at 6" V, x 8', pitch (typ.) do not install in slab SERVICE SUPPORT TYPE SF (U) UNDERGROUND SERVICE WITH SAFETY SWITCH (Typical Arrangement) Meter, Switch or enclosure, as required nduit support spacing, from the ends, max. id 5' in between unless herwise called for by „ie utility. AWL 12" dia. X 60" foundation 4 - #4 reinforcing bars and #2 spiral at 6" pitch (typ.) SERVICE SUPPORT TYPE SF (0) OVERHEAD SERVICE �/2 " expons i of joint materii 5" thick concrete pad (class A concrete and 6" X 6" #6 wire mesh) % " X 8' copper clad ground rod, #6 bare ground wire in %z" PVC. Ground rod shall not be under 3' -6" SERVICE SUPPORT TY SF (0) & SF (U) TOP VIEW 11/4 B.. —.� 1 If I O 7N" dia. 5 Y 2 .. _ 'bolt circle ELI 6" ry / .. BASE PLATE DETAIL TYPE SF & SP 0 TxDOT Jan 5/03 Revision 4 -98 REVISI 0 Revised 12 -00 notes. 3 -03 Stand off type conduit support hardware shown. Provide when f required by the utility. 1 RMC unless otherwise called for by the utility. U UNDERGROUND RISER Conduit support spacing, 3' from the ends, max. and 5' in between unless otherwise called for by the utility. AT UTILITY POLE (for underground service) Top of weatherhead to be 2" to 6 ", NOTES: 1. Support Type SP and SF: Fabricated from 4" x 4" x 3/16 " square structural tubing, ASTM A500 Grade A or G or equal. Base plate shall be 3/4 plate, ASTM A36 or equal. All equipment and conduit shall be mounted on galvanized channel strut, 1 1/2 x 1 5/8 " x 12 gunge galvanized steel channel (Unistrut, Kindorf, B -line or equal) clamped with channel hardware, bolted or welded to vertical member as approved by the Engineer. 2. Paint field out ends of all channels with zinc -rich paint. 3. All Steel Poles (SP and SF) shall be hot -dip galvanized after fabrication. Poles for overhead service shall be fitted with eyebolt or similar fitting, as approved by the utility company, for attachment of sevice drop to the pole. 4. All conduit and conductors attached to the electrical service and within 12 inches of the electrical service will not be paid for directly, but shall be subsidiary to the electrical service. All conduit and conductors from the utility company pole to the point 12 inches from the electrical service, including conduit and conductors required for the utility pole riser when furnished by the Contractor, will be paid for separately. 5. All mounting hardware and installation details of services shall be in accordance with utility company specifications. 6. Anchor bolts for underground service supports shall be 3/4" x 18" x 4" (dia. x length x hook length). Anchor bolts for overhead services shall be 3/4" x 56" x 4 ". Anchor bolts shall be provided with leveling nuts. 7. Conduit for grounding electrode conductor (ground rod wire) shall be 1/2" PVC. All other conduit on electrical services shall be rigid metal conduit. Service entrance conduit size shall be as shown elsewhere. Conduit for branch circuit entry to enclosure shall be the same size as that shown on the layout sheets for branch circuit conduit. Rigid metal conduit shall extend to the rigid metal elbow and then be coupled to the type conduit shown on the layout for that particular branch circuit. RMC shall have grounding bushings in enclosures. 8. If pole is pointed, each separate pointed piece shall have a bonding jumper attached to a tapped hole. 9. Sheet metal screws are not allowed for bonding. Provide 1/4 -20 machine screws. Remove all non - conductive material at contact points. Terminate bonding jumper using listed device. Bonding jumper min. #6 AWG Copper. Make up all threaded bonding connections wrench tight. 10.Conduits entering enclosure from underground shall be sealed at both ends. Silicone sealant will not be allowed. 10 11. Ground rod clamp to be UL listed for direct burial. 12.Service entrance conductors shall exit separately bushed non - metallic openings in weatherhead. 13.Free conductor at weatherhead to be 12 in. min., 18 in. max., or as required by utility. Color code grounded - neutral conductor with white tape covering 6 in. of conductor. Color code L1 or L2 Hot un- grounded conductor with red tape covering 6 in. of conductor. Service drop and service entrance conductors must not contact metal pole in such a manner as to result in abrasion of insulated conductors. 14. Conduit support spacing to be max. 3 ft. from ends, and max. 5 ft. in between. 15.Shop drawings are not required for service support structure unless specifically stated elsewhere or as directed by the Engineer. 16.Service enclosure to be labeled as specified on ED(5) VIII C. 17.Liquidtight flexible metal conduit (LFMC) may be used between the meter and service enclosure when they are mounted 90 to 180 degrees to each other. LFMC shall be the same size as service entrance conduit. LFMC shall not exceed 3 ft. and shall be securely supported within one foot of each end. LFMC shorter then 12" need not be strapped. Each end of LFMC must have a grounding bushing or be terminated with a grounding fitting. A neutral conductor must be installed within the LFMC. Bend in LFMC shall not exceed 180 degrees. A pull test is required on all installed conductors, at least six inches of free conductor movement shall be 4" typical demonstrated to the satisfaction of the Engineer. below the top of pole. As required Point of attachment of service drop to be below by utility co. weatherhead min. 20' max. 25' above grade RMC size as shown elsewh Color code 6" of grounded neutral conductors insula with white tape where conductor exits the weatherhead. Color code 6" of L1 or L -2 Hot - ungrounded conductors insulation with red tape where conductor exits the weatherhead. Conductor free length, 12" min., 18" max. I I Dimension varies, install only as wide as required to accomodate equipment a) TL o> w o O 0:t T a) E o} LL o c 3 T} o }- Z •- :) a a QCN 0U a) CID C a E a }La LCO 0- U) am} CE aa C H + w HL O .0 XLC a) m•- 00 a) to w T3 n m+ E °a > n� 0 L p T a) C.0 moo ~ L ' 00 0 0 00 m�C 0 +mm 0 •- OE+ WN0 10 OE2 -C a J W 0 NOTES: 1. Luminaire conductors shall not be looped through controller cabinet. 2. Electrical system to include an equipment grounding conductor noted here as "G ". All exposed metal parts are to be bonded to grounding conductor. 3. Photocell, when required, shall be mounted at top of pole or in enclosure as shown on ED(4) and ED(5) and as required by descriptive code. 4. Roadway lighting fixtures, when required, shall be in accordance with the material and construction methods of the Item, "Roadway Illumination Assemblies" except for the test period for proper operation of the luminaires. Installed roadway lighting luminaires and internally lighted street name signs shall be tested for proper operation as a part of the associated traffic signal system. 5. Internally lighted street name signs (ILSN), when required, shall be in accordance with the Item "Internally Lighted Street Name Signs ". Because of the electrical isolation of ILSN hinges, a #12 green grounding conductor shall be run to the ILSN fixture. 6. Install ground rod at alternate location when directed by the Engineer. Maintain a minimum of 8 ft in contact with the earth. 7. Liquidtight flexible metal conduit (LFMC), may be used when meter and service enclosure are mounted 90 to 1B0 degrees to each other. LFMC shall be some size as service entrance conduit. LFMC shall not exceed 3 ft. and shall be securely supported within one foot of each end. No strap required for a LFMC shorter than 12 ". Each end of LFMC must have a grounding bushing or be terminated with a grounding fitting. A neutral conductor must be installed within the LFMC. Bend in liquidtight flexible metal conduit shall not exceed 180 degrees. 8. Minimum embedment depth as per Item 627 Treated Timber Poles. 9. Pole to be set plumb. 10. Back fill thoroughly tamped in 6 in. lifts. Place 6 inches additional backfill above grade around pole base to allow for settling, as per Item 627. 11. Excess pole length shall be trimmed from the top at a slope to aid water run off. 12. Gain pole two places for each meter, service, separate or auxiliary enclosure. See ED(4) for details. 13. All illumination and power conductors to be pull tested and megged. Do not meg traffic signal cable. 14. Enclosures are to be locked, and ground box covers are to be bolted before power is applied to the circuit. 15. Conduits entering top of enclosures to be fitted with conduit sealing hub or threaded boss, such as meter hub. Off -set nipple, when required, shall not be zinc -die- pressure cast. All metal conduits not connected to conduit sealing hub, or threaded boss must have a grounding bushing. Terminate bonding jumper to ground bus. All conduits entering enclosures shall be sealed. Silicone shall not be allowed. Top of 120/240 VOLT Color code 6" weatherhead 3 WIRE SERVICE length of to be 2 to COPPER CLAD neutral conductors' 6 ", 4" typ. KVA insulation below the SINE with white tape top of pole. GROUND where conductor NO. CKT. BRK. exits the SERVICE SIZE weatherhead. AMPS CKT. BRK. AMPS / AUXILIARY ENCLOSURE I F_J_ I II SERVICE ENTRANCE I GROUND ROD N CONTROLLER SEPARATE CONDUITS (SEE NOTE 1) _i r. METER Color code 6" length of L1 or L2 conductors' insulation with red tape where conductor exits the weatherhead. \ \ METER LOAD CENTER TYPE T WHITE LOAD CENTER CONT ROLLER - 1 SIGNAL � - — NEUTRAL I o 0 POWER BUS N 0 0 BLOC EUTRAI BUS SIGNAL CONDUC 0 CONDUIT CIRCUIT _ BREAKER MULTICONDUCTOR TRAFFIC — - — - — - - — - - - — — SIGNAL CABLE FROM N CONDUCTORS TO I L S N LUMINAIRES ON TRAFFIC SIGNAL POLE SIGNAL HEADS SIGNS SIGNAL POLES (120V) (240V) G 1 G N See TS -CF for controller foundation 5' USUAL (or as specified by local Utility Company) details 1 - #6 BARE GROUND WIRE IN %2" PVC y/�\V 1" to telephone service PVC BELOW GROUND (OR OTHER CONDUIT AS SHOWN ON SIGNAL LAYOUT) 18 inches Bushing ELECTRICAL SERVICE or Bell SERVICE SAFETY % X 8 TWO -POLE COPPER CLAD CIRCUIT 6 to GROUND ROD - KVA 2 to 4 in. below grade. CONDUIT 10 in. in. Clamp - UL listed for BUTT -WRAP 6" direct burial. GROUND LOADCENTER NO. CKT. BRK. ELECTRICAL SERVICE SEPARATE CONDUIT FOR LUMINAIRES SEE LAYOUT SHEETS FOR CONDUIT AND CONDUCTOR SIZE AND LOCATION, AND FOR THE LOCATION OF GROUND BOXES AND GROUND RODS. SIGNAL CONTROLLER (TYPE T TIMBER POLE SHOWN AS EXAMPLE, SEE ELECTRICAL DETAILS, LAYOUT SHEETS, AND ELECTRICAL SERVICE DATA SHEET FOR SERVICE REQUIRED AND FOR DETAILS.) Unless shown elsewhere in the plans, electrical service data for Types D and T shall be as follows. ww H J Q � d L� ELECTRICAL SERVICE DATA ELECTRICAL SERVICE SERVICE SERVICE SAFETY MAIN TWO -POLE PANELBD./ CIRCUIT BRANCH KVA DESCRIPTION(SEE ED(4)) CONDUIT CONDUCTORS SWITCH DISCONNECT CONTACTOR LOADCENTER NO. CKT. BRK. LOAD SIZE NO. /SIZE AMPS CKT. BRK. AMPS AMP RATING POLE /AMPS (RMC) POLE /AMP * ** (MIN) TY D (120 /240)07O(NS)AL(E) * *(*) 1 3/ #4 N/A 2P/70 30 100 T.S. iP /50 <7.1 0 Lighting 2P/15 TY T (120 /240)0OO(NS)GS(E) * *( *) 1 3/ #4 N/A None 30 70 T. S. iP /50 <7.1 0 Lighting 2P/15 * ** Eliminate photocell, contactor and seperate enclosure if lighting, or internally lighted signs are not required by plans ** See descriptive code in estimate for service support type. * See descriptive code in estimate for overhead or underground service. _ J GROUND BOX SINGLE CONDUIT See layout sheets for signal pole type IY9G�a7��11169) 5/03 Revision 0 Revised notes. SIGNAL POLE GROUND BOX See sheet TS -FD for Foundation Detail when required ro TLro C o> w o+ O 0: EE }LO C+ L a LO Ot OWC 3 T+ o + Z -y -ro a U) U) Q C ro ern U0E roe }LO o0L LCO a rov, aro+ CE- -77 a C H + DO 0 w HL XLC a> a) 00 a> to w +DL T3 ' LLO a C.0 .2 0. 0 L , 00 0 000 ro ~ +roro D- oE+ WN0 'v C roC0 -C a 0 W 0 ww H J Q � O L� 16" 48" O 0 D J E -1I -Ed E -11 -El 3" max. O O X12 �O 13 6" min. �I.IIIN. :: c .a I•:. C °:' a..o , B .. Reinforcing Steel LOAD SIDE CO LOAD SIDE CONDUIT I� Copper -Clad Steel Ground Rod J(' %" X 10' Note: Ells in foundation are rigid metal, size called for on the plans. Extension conduits from these ells may be PVC, provided ends of rigid metal conduits are more than 2 in. below top of concrete foundation. Where extension conduits are metal, grounding bushing must be installed and a bonding jumper properly terminated. FRONT VIEW Ty C shown, Ty A similar except that Ty A shall have individual circuit breakers mounted on a equipment mounting panel. CB Handles shall protrude through hinged deadfront trim. 6" , 16" 20" 17 I /4 4 --_ i SECTION A -A II I__I II �;II II II, Equipment Mounting Studs (as required) Equipment Mounting Studs (as required) Bell End Fittings LOAD SIDE CONDUIT l� II I� LINE SIDE CONDUIT I�Copper-Clad Steel Ground Rod %,, X 10' SIDE VIEW 6" min. 2 Leveling Washers - u 10 "I Hex Nut Lock Washer a ° Q Z I ° ° a °�I I as 4 / ANCHOR BOLT DETAIL GENERAL NOTES 1. The pedestal service shall be UL type 3R, and shall be constructed of a minimum of 12 guage stainless steel or aluminum as required by descriptive code. Stainless steel shall not be pointed. For aluminum, the finish shell be an electrostatic applied poly- urethane baked on powder, light green in color, or color as shown elsewhere and as approved by the Engineer. The front of the interior dead front trim shell be permanently labeled, "Danger High Voltage" with OSHA style label. The exterior of the pedestal service door shall be permanently labeled with a placard as to its use (i.e. Roadway Lighting, Traffic Signals, etc.). Placard shall be neat and professional in appearance. Lettering shall be 1" minimum height. 2. Utility Access Door shall have stainless steel piano hinge and provisions for padlocking. 3. Pedestal door shall have stainless steel piano hinge and stainless steel latch with provisions for padlocking. 4. Meter Access shall be hinged and capable of padlocking. 5. All mounting hardware and installation details of services shall be in accordance with utility company specifications. The Contractor is responsible for contacting the local utility company and obtaining their approval of pedestal details prior to making submittal to the Department and prior to constructing the electrical pedestal service. Any changes required by the utility company shall be noted on the submittals. 6. Meter Socket shall be a minimum of 100 amp rating and shall comply with the local utility requirements. 7. Photoelectric Control shall meet the requirements as shown on ED(5). Shield to control stray light is aIIowable.The Contractor shall be responsible for proper operation of the photo - electric control. The Contractor shall move and /or adjust or shield the photocell from stray or anbient nighttime light or shall make any other adjustments required for proper operation. The photocell shall face North when practicable. Unless otherwise shown on the plans, the photocell shall turn on the illumination system at 1.0 +( -) 0.5 foot - candle and turn off the illumination system at two footcandles higher than turn on. 8. The Control Station (H -O -A Switch) shall be as shown on ED(5) except that H -O -A Switch operating handle shall protrude through hinged deadfront trim and NEMA 1 enclosure will not be required. 9. Concrete for pedestal service foundation shall be class A or C and shall be in accordance with Item 420, "CONCRETE STRUCTURES ", except that concrete will not be paid for directly but shall be considered subsidiary to Item 628, "ELECTRICAL SERVICES ". 10. Reinforcing steel shall be #4 rebar in accordance with Item 440, "REINFORCING STEEL ". 11. Anchor bolts shall be A361A55 in accordance with Item 449, "ANCHOR BOLTS ". Anchor bolts shall bel /2 inch x 12 inches x 4 inches (di a. x length x hook length). 12. All conduit and conductors attached to the pedestal service and within 12 inches of the pedestal service will not be paid for directly, but shall be subsidiary to the pedestal service. All service conduit and conductors from the utility company transformer to a point 12 inches from the pedestal service shall be paid for separately. Service conduit shall be the size and type as shown in the Electrical Service Data. 13. Dimensions may vary to accomodate required equipment, utility company requirements, or manufacturer's standard equipment dimensions. The Contractor shall submit to the Engineer for approval, six (6) copies of brochures and /or drawings of the pedestal service to be supplied, including actual dimensions, and a paint color sample. 14. A separate enclosure as shown on ED(4) or ED(5) for photocell shall not be used for pedestal services. Photocell shall be installed as shown here. 15. The pedestal door shall have a mechanically attached data pocket on the inside. Pocket shall be either metal or thermoplastic and shall measure at least 12 inches by 12 inches. The Contractor shall prepare and submit a schematic drawing unique to an individual service. The approved drawing shall be laminated and placed in the document pocket of the service at the time of shipment to the job site. All applicable wiring diagrams and plan sheet layouts for all equipment and branch breaker circuits supplied by that service shall Q also be laminated and placed in the document pocket prior to shipping. 1 16. Ground rod clamp to be UL listed for direct burial. All non - conductive coating to be removed from ground rod at clamp IacatIon. Ground rod wire to be 96 AWG solid copper. Metal conduit ells to have grounding bushing and bonding jumpers correctly installed. 17. All conduits entering enclosures from underground must be sealed. Silicone shall not be allowed. 18. All conductors shall be megged and Dull tested. Traffic signal cable not to be megged after connection, as electronics will be damaged. 19. Top of concrete foundation to be finished in a neat and workman like manner. If leveling washers are used, no more thanl /Bin. height shall be used at any one corner. Maximum dip or rise in foundation is not to exceed/8 in per foot. when properly installed, top of service enclosure shall read level front to back and side to side withinl /4in. Rocking or movement of the service enclosure shall be repaired by the contractor at no cost to the state. 20. Liquidtight flexible metal conduit shall not be allowed on PS type services. LEGEND 1. METER SOCKET, (when required) 2. METER SOCKET WINDOW, (when required) 3. EQUIPMENT MOUNTING PANEL 4. PHOTO ELECTRIC CONTROL WINDOW, (when required) 5. HINGED DEADFRONT TRIM 6. LOAD SIDE CONDUIT AREA 7. LINE SIDE CONDUIT AREA 8. UTILITY ACCESS DOOR, with handle 9. PEDESTAL DOOR 10. HINGED METER ACCESS 11. CONTROL STATION (H -O -A Switch) 12. MAIN DISCONNECT 13. BRANCH CIRCUIT BREAKERS r 5/03 Revision 0 Revised notes. m TL Cm7 w o+ O U•— T a) E 0+ LO Ot 3wc T+ O +— z •- :) a n_L U N m ¢0U UmE Lv ooL LCO a mp am+ CE- o0L C DO 0 H + w HL XLC a) >. = 00 a) to w + LO T3 n U) E °a > n P CL moo L ,w + O 00 0 mi- 0 m T+ —vm L +mm CIE oE+ WNO 'v c mC0 HYm w a J W 0 6" to 12' 2" to 6" (4" typ.) :� 1 1 (As required or allowed Color code grounded - neutral I by utility company) conductor with white tape fl covering 6 in. of conductor length. Color code L1 or L2 Hot conductor with red tape cover- ing 6 in. of conductor length. 25' min. or Where conductors exit weather- as required head, conductors free length by utility co. shall be 12 in. min., 18 in. max. Safety switch RMC Pole marking (when required) \ Service Enclosure approx. k Conduit above ground support See line. spacing Detail A Det ee l A Extend 1/2 3 ft max. PVC 6 in. Extend 112 PVC = a 6 in. below grade o T below grade. } RMC* GROUND ROD- 5 /B" x 8' RMC* 2 to 4 in. below grade. GROUND ROD- 5 /e" x 8' 2 to 4 in. below grade. I'. J 18.. 42 „ 18"** f: ; I PVC, or other 10% of p o l e min. IF' :1 conduit type length plus PVC, or other RMC to l,; . to as shown on layout 2 ft., min. 42 6 to conduit type utility I; 1 1 :0 i n. iF , in. as shown on layout i8 tYp• I•' 'D Min. 24' Bush i ng M i n. 24" rg" tYP• d i a. h o l e Concrete or Bel I d i a. h o l e Bushing Pole Concrete or Bell Pole CONCRETE SERVICE SUPPORT CONCRETE SERVICE SUPPORT (Underground) (Overhead) *same size as branch circuit conduit shown on layout sheets. ** or as required by utility company. Stand off type conduit support hardware shown. (Provide when uti I ity required by the pole uti I ity company File sharp edges and paint TOP end of channel with zinc rich paint. Do not allow paint to splatter on or over the concrete pole. Height, materials, — and details as required by utility company SIDE DETAIL A Channel bracket or other arrangement approved by the Engineer. (Kindorf, Unistrut, B -line or equal) Note: Attach channels with stainless steel concrete anchors (max. 1" depth), square U -bolts or back to back channel with long bolts, or other secure mounting as approved by the Engineer. Bolts galvanized in accordance with ASTM A153. Channel shall be galvanized. Conduit support spacing, 3 ft. from the ends, max. 5 ft. in between unless otherwise called for by the utility UTILITY POLE CONNECTIONS (When underground service is required by descriptive code and utility is overhead.) NOTES: Electrical service support structures bid as type GC or OC shall be concrete poles and shall meet the following specifications. 1. Poles shall be prestressed concrete and suitable for direct embedment into the ground without special foundations. 2. Poles bid as type "GC" shall be a granite concrete mixture consisting of gray Portland cement with exposed pink granite aggregate. Poles bid as type "OC" shall be other concrete mixture as shown elsewhere on the plans or as directed by the Engineer. 3. Poles greater than 10 ' shall be square in cross - section, with chamfered corners, and shall have a standard taper of 0.162 inch per foot. Cross sectional dimensions shall not deviate by more than 3/8 inch. Poles 10' or less may be tapered .162 " /ft or may be non - tapered. The allowable tolerance shall be plus 3 inches and -2 inches in the overall length. The width of the bottom face of the pole as it is cost may be less than the top face. All small cavities shall be cleaned, saturated with water and then filled with mortar. A small cavity is defined as one larger than 1/4 inch but smaller than 3/4 inch in diameter, and less than 3/8 inch deep. Larger non - structural cavities and spalls shall be repaired by opening side of the damaged area on a 1 to 1 slope using a mechanical grinder, cleaning thoroughly and filling with a high- strength non - shrink concrete repair material. Poles with other defects may be repaired only upon authorization of and using the method prescribed by the Engineer. 4. The end of each steel reinforcing strand in the tip and butt sholI be burned back to a minimum depth of 1/2 inch. The holes left by the removal of the strand shall be thoroughly cleaned of any loose residue. The holes shall then be completely filled with non - shrink grout and smoothed evenly with tip or butt surface. 5. Prestressing strands shall have a minimum concrete cover of 1 1/4 inch. 6. A straight line joining the edge of the pole at the butt and the edge of the pole at the top shall not be distant from the surface of the pole at any point by more than 3/9 inch for each 10 feet of length. 7. The chloride content of the concrete mix, including all ingredients shall be 0.4 pounds per cubic yard, or less. 8. Concrete used in poles shall have a compressive strength at transfer of not less than 4,000 PSI, and a 28 -day compressive strength of not less than 7,000 PSI. 9. Materials shall comply with the latest version of the following standards: a) Portland Cement - ASTM C105 b) Admixtures - ASTM C494 c) Aggregates - ASTM C33 or C330 d) Reinforcing Bars - ASTM A615 e) Cold -Drawn Spiral Wire - ASTM A82 f) Prestressing Strand, 270K - ASTM A416 10.PoIes greater than 10' shall have a 4 inch tip and 3/8 inch strands. Poles 10' or less shall have a 5 inch min. tip and 3/8 inch strands. Pole shall have a load capacity of greater than 11BB lbs. applied 2 ft. below tip. ll.Poles shall be capable of withstanding single point pick up from the horizontal position when lifting from a point 30% of the overall length down from the tip. 12.A11 poles shall be marked by imprinting on one face. Marking shall indicate manufacturer's name, year of manufacture, length and name or type of pole. Marking shall be located approximately 4 ft. above ground line. 13.Dunnage points, two -point pickup locations for handling pole in horizontal position, and one -point pickup locations for use in raising the pole to a vertical position and handling in setting operation shall be marked on the pole with durable ink or paint or cast into the pole. These marks shall be small but conspicuous. 14.Poles shall be embedded 42 inches or 10% of length plus 2 ft. into the ground whichever is greater. 15. When required by utility company for overhead services, poles longer than 10 feet shall have a #6 solid ground wire running the entire length exiting within 6 inches from the top and bottom of the pole. The Contractor shall connect the bottom to a butt wrap or butt plate grounding device. 16.AII conduit and conductors attached to the service support and within 12 inches of the service support will not be paid for directly, but shall be subsidiary to the electrical service. All conduit and conductors from the utility company pole to a point 12 inches from the service support, including conduit and conductors required for the utility pole riser when furnished by the Contractor, will be paid for separately. 17.All mounting hardware and installation details of services shall be in accordance with utility company specifications. 1B.All conduit on service supports shall be rigid metal conduit except the conduit for grounding electrode conductor (ground rod wire) shall be 1/2 inch PVC. Service entrance conduit size shall be as shown elsewhere. Conduit for branch circuit entry to enclosure shall be the some size as that shown on the layout sheets for branch circuit conduit. Rigid metal conduit shall extend a minimum of six inches underground and then coupled to the type conduit shown on the layout for that particular branch circuit. RMC shall have grounding bushings in enclosures. 19. Boo kfiII shall be in accordance with Item 400 except for measurement and payment. BackfiIIing will not be paid for directly but shall be subsidiary to the various bid items. 20.Liquid tight flexible metal conduit (LFMC), may be used when meter and service enclosure are mounted 90 to 180 degrees to each other. LFMC shall not exceed 3 ft. and shall be securely supported within one ft. of each end. Each end of LFMC must have a grounding bushing or be terminated with a grounding fitting. A neutral conductor must be installed within the LFMC. Bend in LFMC shall not exceed 160 degrees. LFMC may not be installed on utility company owned poles. A pull test is required on all installed conductors, at least six inches of free conductor pavement shall be demonstrated to the satisfaction of the Engineer. 21.Contractor may order concrete service support structures with 3/4" hole near top of pole for eye bolt type bracket. Eye bolt bracket may be installed as means of overhead service drop anchoring point by utility. Pole may also be center drilled in the field for installation of eye bolt bracket. When used, install bracket 6" to 12" below weatherhead. ww H J Q � O L� N TL CN7 0> C m a O} O U •EE— }LO o } w LOU 3wc T} o }— Z _ y -'aL U N m C N UmE N0 }LO o0L LCO d mm aN} E L U) U) u) (D N0L C H+ Oro U CON W H L N O O . U XLC N a) �> (DL 00 N to Cr }DL � N} E °a > n� o L P CC moo ~ L 'D 4 + O CO �L 000 moo +Nm 0 •- OE+ WN0 7 10 NCO HY(0 W J W 0 I. DUCT CABLE A. Duct cable shall be placed by the open trench method at a minimum depth of 18 inches. Bends in duct cable shall be made in the manner recommended by the manufacturer; minimum bending radius shall be 20 inches for 1 1/2 inch duct and 26 inches for 2 inch duct. Unless otherwise approved by the Engineer in writing, duct cable shall be 2 inch diameter. Handling of duct cable reels and installation of duct shall be as recommended by the manufacturer. Duct for duct cable is designed as a conduit system and shall be considered as such in NEC interpretations. Conductors shall not be spliced within a duct. Duct entering a ground box or foundation shall be coupled to a RMC elbow. B. Duct cable shall have factory installed conductors. AWG size of electrical conductors shall be as called for in the plans or as required by the National Electrical Code. Conduit bid as High Density Polyethylene (HDPE) conduit shall meet the requirements of duct cable except that the conduit shall be supplied without factory installed conductors. HDPE conduit may be substituted for duct cable. After HDPE conduit is installed, conductors shall be installed. AWG size of electrical conductors shall be as called for in the plans. C. Duct cable shall be extended through conduit casings in one continuous length without connection to the casing. D. After duct cable has been installed, a pull test will be made on conductors. If conductors cannot be freely pulled, Contractor shall replace or otherwise adjust installation to free up the conductors. Duct cable ends shall be sealed with foam electrical conduit sealant or with heat - shrinking material after pull test is completed. E. Sufficient clearance shall be left between each conduit ell so the bonding bushings may be correctly installed. Conduit cover is shown as 18 inches minimum, where run under a road, the minimum cover requirement is 24 inches. F. All duct splices shall be by means of UL listed fittings, threaded duct with PVC threaded connector or UL listed tiewrap fitting or central Fusamatic electrically heated fusing conduit coupling installed in accordance with the manufacturer's instructions and approved by the Engineer. Glue on connectors, water pipefittings and heat shrink tubing splices will not be allowed. ®D D' 18" min. D D . . D. D 3to6 Ground inches box D D q D a ° a ❑ ° °❑ ° ° ° a ° ° 0 Duct Cable ❑ a ❑ ° ❑ °a grounding bushing RMC extension ° ❑ ❑a ❑ °° ° °pqa °a 9 .. ° ° o ° ° ° ❑ ❑ aaa❑ ° °❑ ❑ min. ❑ ° RMC elbow When the upper end of an RMC Ell does not enter the ground box, it may be extended with a Sch -40 PVC conduit nipple and bell end, provided there is 18" of cover over all parts of the elbow. If not, a rigid extension and ground bushing is required. Gravel bed is to be a min, of 9 inches deep, placed under and not in the ground box. Gravel shall not encroach into the interior of the box. Duct Cable to Conduit Adapter - Duct cable - HDPE conduit and couplings shall comply with the material specification as shown on ED (1) II Conduit A. Materials 12. DUCT CABLE AT GROUND BOX Couple duct to conduit elbow at foundations. Extend conductors to pole base. Conductors shall not be spliced in duct or conduit. See EDO), II,11 BORE PIT DETAIL Duct HDPE Nonmetallic Liquidtight Fitting (T &B- Plastic Bullet® or equal.) EXAMPLES OF PROPER CONNECTIONS Rigid Conduit PVC / Bell end fitting extension 1 - 3" exposed p p D' 2" min., from top of p D D drill shaft to RMC RMC to PVC RMC elbow D D . Ground rods are not shown on this standard sheet, but may be required else where in pla.. D D D D ° Drill shaft foundation (class "A" concrete) DUCT CABLE AT FOUNDATION ww H J O L� Rigid Coupling Conduit Central Fuseamatic Electrically Heated Fusing Conduit Coupling Compact back fill to bottom of conduit casing prior to placing duct cable, to prevent kinking. N TL D C o> C ul 00 t O U •EE- }.c CtL O f LL LOU owe 3 Tt O t — Z — :) _ a L QCN OU UtiE } ooL LCO 0- U) wmt CU)U) a)0L C H + w N ~ o XLC a� m•- ~ oo a� to w T3 � m+ E n o > n� U C.0 q0. ~ L 'D 4 + D +XV y�C a +min D oE+ WNO 'DC OCO HYN J W 0 co I 10 _ io TYPICAL VERTICAL SECTION 10 Concrete ground box Type J - shall be 48" by 48" inside dimension and shall have AASHTO HS 20 wheel loading structural design. Fabricator shall submit shop drawings sealed by a Texas Licensed Structural Engineer. Shop drawings and calculations shall be for the box and lid as a unit. �2 Lid and ring shall be cast from Gray Iron in accordance with AASHTO M306, and shall be suitable for HS 20 loading or better. Proof -load testing certification in accordance with AASHTO M 306 shall be submitted. Lid shall have type T hinges and type G handles, and shall have a safety device to prevent accidental closing once the lid has been opened. Lid shall be cast with "TxDOT CONNUMICATIONS" in one inch lettering on top. Lid and ring shall be supplied together, and shall have no sharp edges. Shop drawings shall be submitted. (Neenah Foundry R- 6662 -TH, or equal.) �3 18" by 9" knockout in concrete �4 Cable rack - Joslyn J5124, Chance C203 -1124 or equivalent �5 Cable rach hooks - Joslyn J5131A, Chance C203 -1131 or equivalent �6 Concrete drain invert, %2" pitch from center to walls �7 3" drain �8 Filter material - Grade 3 aggregate or finer. See ITEM 302 �9 RPM ground box, as called for in layouts, for electrical power conductors and traffic signal cables. See ED(3) for ground box details 1� Conduits (See layouts for number, details, specifications, and sizes) 11 Concrete riprap apron, Bid as ITEM 432. 1 cubic yard minimum 1 24" 48" ° 12 ° J L - - - z Z x - -- I ° I I I I I I I I 11 12 I I I I 10 GENERAL NOTES 1) Illumination, traffic signal and other conductors carrying full voltages (50 volts or greater) shall not enter the communications ground box, but shall be run into an adjacent RPM ground box, as shown in the detail. 2) Conductors in the Type J ground box shall be laid on the racks and secured in place with plastic ties. At no time shall any conductor be run through the center of the box. Contractor shall arrange conduit runs so cables shall enter and exit the box without violating the required bend radius or running throught the center of the box. 3) Riprap shown is the minimum required. Riprap shall extend to protect all conduits with less than the minimum allowed ground cover. 4) Conduits shall not extend inside the box more than 1 ", including the required bell end fitting or bushing. Conduits shall be securely grounted in place with Portland cement completely filling the knockout window around the conduits. 5) Rigrap and boxes shall be cast flat with a maximum slope of 0.25% (3" over 10'). 6) Payment - concrete ground box Type J shall be bid as ITEM 628. RPM ground box and riprap shall be bid separately. TYPICAL PLAN VIEW ww H J Q � O L� W C L D Cm7 0> C al a 0 O U •t EE }LO o } w L L 0U 3wc Tt ot- Z -y a U N a) ¢00, a) CID V E ()O }LO LCO 0 - U) amt CE 0L C H + 00 (D W H L XLC a) >. (DL 00 a> to w T = 0 n m+ E °a > n� pTN C.0 m0} 0 L ' 00 0 00 0 N�0 +mur o •- OE+ WN0 'v c OE2 -C W J W 0 ww H J Q � C1 L� GENERAL NOTES: DRILL 1.5" HOLE VENT BOTH SIDES, COVER WITH STAINLESS STEEL SCREEN 9 /� BACK ELEVATION VIEW 0 o rn �VAR5" BASE PLAN VIEW 716 " I/ " RnTTnU nF POI F: 3" I VARIES - — I/ " L 10" MAX. I (TYP) I I , I o 1.5" X 1.5" X .188" ANGLE 0.65" Photo cell viewing window typ. location 1.5" X 1.5" X .188" TOP ANGLE SEE DETAIL "A" GROUNDING ELECTRODE CONDUCTOR, NEED NOT BE IN CONDUIT. DRILL & TAP 1 /4" HOLE FOR GROUNDING GROUND WIRE TO STRUCTURE (CLEAN PAINT FROM STRUCTURE PRIOR TO GROUNDING) �" i l 0.5 BOTTOM ANGLES 3/4 " 12 GAUGE STEEL COVER PANEL, FRONT AND BACK; ATTACH WITH 0.25" DIA. GALV. BOLTS L - - 5/8 X 10' COPPERCLAD GROUND ROD LEAVE 15" EXPOSED FRONT ELEVATION VIEW SECTION A -A io M DIMENSION VARIES, INSTALL P LAN VIE ONLY AS WIDE AS REQUIRED TO ACCOMODATE EQUIPMENT AND FOUNDATION ENCLOSURE R. 0. W. GROUND BOX (WHEN SHOWN ON LAYOUT PAID FOR SEPARATELY) CONDUIT FROM SERVICE SUPPORT I� TO A GROUND BOX LOCATED AT R.O.W. LINE OR TO UTILITY POLE RISER. SEE LAYOUT SHEET FOR SIZES. ¢� METER (WHEN REQUIRED) L A W. " X 10' 11 COPPER CLAD GROUND ROD PVC FOR CIRCUIT GROUND WIRE SHALL BE #6 BARE I I CONDUCTORS SIZE VARIES. SEE LAYOUT SHEETS. PLAN VIEW w > VARIES 0 0 0 I' ®ARC O V) IA&H VOLTAGE ENCLOSURE PVC CONDUITS FRONT 1. Structure shall be designed in accordance with latest issue of AASHTO "STANDARD SPECIFICATIONS FOR STRUCTURAL SUPPORTS FOR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS." Structures shall be designed for 80 mph wind load with 1.3 gust factor. Shop drawings shall include ASTM material designations. Shop drawings shall be submitted for the electrical service support in accordance with Item 441, "STEEL STRUCTURES." Catalog cut sheets shall be submitted for the enclosure and equipment. 2. The structure shall be galvanized. Twelve gauge sheet covers and enclosure may be made from pre - galvanized sheeting. When shown elsewhere on the plans, structure and outside of enclosure may be pointed in lieu of galvanizing. S 3. Structure mounting dimensions may vary to match enclosure provided. 4. All conduit and conductors attached to the electrical service and within 12" of the electrical service will not be paid for directly, but shall be subsidiary to the electrical service. All conduit and conductors from the utility company pole to a point 12" from the electrical service, including conduit and conductors required for the utility pole riser, when furnished by the Contractor, will be paid for separately. 5. All conduits entering enclosures from underground to be sealed. Silicone will not be allowed. 6. All PVC conduits to be fitted with a bell end or bushing. 7. Support structure to be bonded to the ground rod using a #6 AWG Copper Bonding jumper to be terminated with a listed eyelet type connector connected to a 1/4 -20 SS machine screw -bolt. Sheet metal screws will not be 1 allowed for bonding. All threaded bonding connections shall be mode up wrench tight. All non- conductive materials to be removed from contact surfaces. B. Service enclosures to be labeled and steciled see ED(5) VIII C. 10 9. Ground rod clamp to be UL listed for direct burial. 10.Photo cell viewing window location on each side of the service enclosure to be clear of obstructure and provide a clear line of sight view and allow for the proper light level sensing by the photo cell. 11.Liquidtight flexible metal conduit may not be used on type RT(U) service supports. Photo cell viewing window typ. location RIGHT SIDE FNPI nCI IRF STRUCTURE DATA TUBULAR POLE ANCHOR BOLTS MEMBER SIZE DIA.X LENGTH X HOOK 8" X 3 "X 3 /16 " 5 /s" X 16" X 4" A CONCRETE X 1 /4" X 1 " TABS FOUNDATION ELEVATION — --I — 0.65" 1/4 DIA. BOLTS nFTATI A 5/03 Revision 0 Revised notes. 5" X 1.5" X .188" ANGLE OMIT COVER PANEL SCREWS ON TOP OF BACK COVER PLATE. DRILL AND TAP ANGLES AS SHOWN FOR 3/8" BOLT FOR ENCLOSURE MOUNTING. DRILL COVER PANEL FOR 3/8" BOLT. VARIES 8" CONCRETE PAD COMPONENT ASTM T TUBING A500 GRADE A MEMBERS IV BASE PLATES A36 18" DIA. X 48" DRILL SHAFT ANCHOR BOLTS A307 or A36 FOUNDATION. 4 -#4 REINFORCING BARS .XPANSION AND 2 -#2 SPIRAL (TYP. f MATERIAL 6" PITCH) K CONCRETE DRILL AND TAP .. X 6" �6 �*Texas De rtment of Tra FOR 1/4 BOLT =SH) CHASE THREADS \ , Traffic Operaflons Dlvlslon — AFTER GALVANIZING. n Il Ili A CONCRETE X 1 /4" X 1 " TABS FOUNDATION ELEVATION — --I — 0.65" 1/4 DIA. BOLTS nFTATI A 5/03 Revision 0 Revised notes. 5" X 1.5" X .188" ANGLE OMIT COVER PANEL SCREWS ON TOP OF BACK COVER PLATE. DRILL AND TAP ANGLES AS SHOWN FOR 3/8" BOLT FOR ENCLOSURE MOUNTING. DRILL COVER PANEL FOR 3/8" BOLT. VARIES 8" N C L D CN7 o> w 0+ O 0: EE }LO C+ L O f LO at awc 3 T+ o +— Z °— � _ a U N y C N UNE Lv ooL LCO 0- U) ma N+ E L U) U) 4 C H+ Oro U CON W H L O . U XLC N a) �> (DL 00 L t + N+ E °a > n pTN CL ~ Na+ L 'w + 0 00 0 +XV NHc a u) T+ +Nmn v •— OE+ WNO 10 NCO HYN (r a J U (n 0 GROUND BOX - Type - Battery Box A. MATERIALS 1. Battery box ground boxes shall be constructed such that it will be possible to install and accomodate up to 4 batteries measuring 8" x 13.5" x 10" (w x L x D). 2. All battery box ground boxes and covers shall be permanently marked either by impress or by permanent ink, with manufacturer's model number and manufacturer's name or logo. 3. Covers shall be bolted down, and bolt holes in the box shall be arranged to drain dirt. 4. Battery box ground boxes shall meet the following requirements: a. Battery box cover and cover ring will be manufactured from polymer concrete reinforced with continuous strands of woven or stitched borosilicate fiberglass cloth. The polymer concrete shall be made from catalyzed polyester resin, sand and aggregate, and shall have a minimum compressive strength of 11,000 psi. Polymer concrete containing chopped fiberglass or fiberglass reinforced plastic is not acceptable. b. Battery box ground box walls will be manufactured from fiberglass reinforced plastic reinforced with continuos strands of woven or stitched borosilicate fiberglass cloth. The fiberglass reinforced plastic shall be made from catalyzed polyester resin, lightweight filler and reinforced with woven roving and shall have a minimum compressive strength of 7,500 psi. c. Minimum inside dimensions shall be at least as follows (width x length x depth): Battery box shall be at least 15 I / x 28 I / x 14 %2 inches. d. Bottom edge of box or extension shall be footed with a minimum 1 inch flange. e. Battery ground boxes shall withstand 600 lbs. per sq. ft. applied over the entire sidewall with less than l/4 inch deflection per foot length of box. Ground boxes and covers shall withstand a test loading of 20,000 lbs. over a 10 inch by 20 inch area centered on the cover with less than %2 inch deflection. Battery ground boxes and covers shall meet western Underground Standards 3.6. Manufacturer shall supply certification by an independent laboratory or sealed by a Texas- Licensed Professional Engineer. f. Covers shall be 2 inch thick polymer concrete. All hardware shall be stainless steel. Cover shall be secured with two 1/2 inch stainless steel bolts. Bolts shall be self- retaining and shall withstand a minimum of 70 ft -lbs. torque and shall have a minimum 750 lbs. straight pull out strength. Nuts shall be floating and shall provide a minimum of 1/2 inch movement from the center of the nut. Covers shall be skid resistant, minimum 0.5 coefficient of friction. Covers shall be interchangeable between manufacturers and shall conform to the dimensions shown herein. Unless otherwise approved by the Engineer, cover shall be legibly labeled, "Traffic Signals Danger High Voltage" in minimum 1 inch letters. g. The battery box shall be supplied with predrilled holes to accept % inch stainless steel rods. The holes shall be installed 1 inches ( « /- 1 /4inches) above the bottom edge of the box along the length of the box at 3 %2inch centers beginning 4 %2 inches from the edge of the box. h. A minimum of seven % inch stainless steel rods threaded on both ends shall came equipped to be inserted in the predrilled holes to serve as a rack sufficient to accommodate up to four batteries. The rods shall be secured in place utilizing %" stainless steel (s. s.) nuts and %" X 1" s. s. flat washers. i. Ground boxes of the type specified above shall meet the requirements shown above. The Contractor will be permitted to furnish like materials of any manufacturer provided they are of equal quality and comply with the specifications. j. Two Y6" plastic sheets measuring a nominal 6" x 24" shall be supplied which are to be placed on the secured rods upon which the batteries (supplied by others) are to be set. k. A minimum of four battery "bell jars" and respective tie down straps are to be supplied. These bell jars are inverted over the batteries and strapped to the batteries. B. CONSTRUCTION METHODS 1. Battery box ground boxes shall be set on a 9 inch (minimum) bed of coarse No. 1 aggregate as defined by Item 421. Gravel shall be in place prior to setting box and conduits shall be capped. Any gravel or dirt in conduit shall be removed. 2. Construction of an apron encasing the battery box ground box including concrete and reinforcing steel is required and shall not be paid for directly but shall be subsidiary to the ground box. Reinforcing steel may be field bent. Concrete for aprons shall be considered miscellaneous concrete for testing purposes. Aprons shall be cast in place. 3. Any holes out into the sidewall of battery box ground boxes shall be accomplished using a round hole saw or other method approved by the Engineer. SECTION X - X A t PLAN VIEW For cover logo see A,4,f 2 3 14 18" PIN Class A to" Concrete (typ.) Bushing SECTION A - A APRON FOR GROUND BOXES No. 3 Apron Reinforcing steel ri4pYni r, ig Ground �: •° box Conduit or duct cable (Where required) 16" min. 9" Gravel fill (2) (1) Place gravel "under" the box. not "in" the box. Gravel should not encroach on the interior volume of the box. (2) Install bushing on the upper end of all ells. (3) All conduits shall be installed in a neat and workmanlike manner. 31 /2 14 18" SECTION Y - Y lam mil H J Q � O L� Hole for %2" bolt with recess for head. PLAN VIEW J JK END GROUND BOX COVER L � H _ P 1 — — 1 I _ 1 SIDE GROUND BOX COVER DIMENSIONS BOX DIMENSIONS (INCHES) SIZE H I J K L M N P Battery box 30 %2 30 1/4 17 1 /z 17 1/4 13 1/4 6 ]4 1 % 2 30Y4 17 Bar "A" Reinforcing steel