ST0701-LR100415CONCRETE COMPRESSIVE STRENGTH TEST REPORT IkRrra Report Number: 94091 193.0129 Service Date: 011 /07/10 8901 Carpenter Frwy. Report Date: 04/15/10 Dallas, TX 75247 214- 630 -1010 Reg No: F -3 Client Project City of Coppell TX Attn: Keith Marvin PO Boa 9478 Coppell, TX 75019 Southwestern Boulevard Coppell Road to Grapevine Creels Coppell, TX Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Sample Date: 04/07/10 Sample Time: 1535 Sampled By: Francisco J. Morillo Mix ID: DCCOG504 Weather Conditions: Clear Supplier: Recli -Mix Accumulative Yards: 7 Batch Size (cy): 7 Batch Time: 1429 Plant: 136 Placement Method: Direct Discharge Truck No.: 1 187 Ticket No.: 25182785 Water Added Before (gal):0 Water Added After (gal): 0 Field Test Data Sample Location: See Placement Location Test Result Specification Placement Location: Bridge Beam #1, westbound Slump (in): 5 3 -5 Air Content ( %): 4.0 3 -6 Concrete Temp. (F): 81 Ambient Temp. (F): 83 Plastic Unit Wt. (pct): 145.0 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (lbs) (psi) Type 1 1 6.00 28.27 04/09/10 04/14/10 7 117,150 4,140 2 1 2 6.00 28.27 04/09/10 04/21/10 14 1 3 6.00 28.27 04/09/10 05/05/10 28 1 4 6.00 28.27 04/09/10 05/05/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations perform required field tests and ca compressive strength samples. Terracon Rep.: Francisco J. Morillo Started: 1400 Reported To: Superintendent Finished: 1630 Contractor: Lacy Construction Report Distribution: Reviewed By: (1) City of C'oppel l TN (1) City of Coppell TX (I) City of C'oppcll '1'N (� _) 1(iIff Assoc Gto ri . Clject eland, P.E. (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Senior Pro Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page I of I REINFORCING STEEL OBSERVATIONS REPORT Irerracon Report Number: 94091193.0135 Service Date: 04/12/10 8901 Carpenter Frwy. Report Date: 04/15/10 Dallas, TX 75247 214- 630 -1010 Reg No:F -3272 Client Project City of Coppell TX Southwestern Boulevard Attn: Keith Marvin Coppell Road to Grapevine Creek PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94091193 Drawings Utilized: SC1.08, dated 05/2009 Locations/Items Observed: Bridge Westbound at Beam #2 Test Method: Visual Observation . • . • • : • ITEMS OBSERVED CORRECT INCORRECT - ITEMS OBSERVED CORRECT INCORRECT ITEMS OBSERVED CORRECT INCORRECT Placing Drawings Approved X Bar Length and Shape X Column Tie Spacing & Type Bar Size X Proper Bar Placement X Stirrup Spacing & Type Bar Grade X Properly Tied X Welded Splices Reber Clean X Dowel Bars in Place X Mechanical Splices Trash & Debris Removed X Proper Bar Supports X Lapped Splices Number of Bars X Proper CoveriClearance X Discrepancies /Comments: No discrepancies were noted at the time of this observation. Services: Reinforcing steel (rebar) placement observation. Terracon Rep.: Francisco J. Morillo Reported To: Superintendent Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX (1) City of Coppell TX (2) Halff Assoc Inc Reviewed By: (1) Lacy Construction (1) PaeTrust Pacific Realty Associates LP Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CTOOO1, 3- 09 -10, Rev.6 Page 1 of 1 sa Irerracon Repurt Numbac 9409119 ^ Service Date: 04/08/10 8901 Carpenter Frwy. Report Dy Jluo �utu� O4/l6/lO , 77{75247 314'620-1010 Deallo:F �__—___ Client Project City ofCoppcUTX Attn: Keith Marvin PO Box 947D Coppe||,TX75Ol0 Southwestern Boulevard CopPoU Road to Grapevine Creek CoppeU,77C Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 poi 6� — %8 days Sample Date: 04/08/10 Sample Time: 1635 Sampled By: Francisco lK4miUo Mix ID: DCCOG504 Weather Conditions: Clear Supplier: Kudi'B8is Accumulative Yards: 6 Batch Size (cy): h Batch Time: 1532 Plant: 259 Placement Method: Direct Discharge Truck No.: 1321 Ticket No.: 25183555 Water Added Before (guD:0 Water Added After (gaD: 0 Field Test Data Sample Location: Sue Placement Location Test Bimmolt Specification Placement Location: Bridge Beam #4-Westbound 4 _' Air Content ('H.): 4.5 3-6 Concrete Tomp.UN: 87 Ambient Temp. 8q: 82 Plastic Unit Wt. (pcQ/ 146.0 Laboratory Test Data Age at Maximum Compressiv Set Specimen Diameter Area Date Date Test Loud 8truo%tb Fracture Mu lD i Received Tested (days) T y��_ -----' -------' | | 6.80 ------ 2827 04/10/10 -- n4/r��� 7 l2g24O 4 ' , 570 2 | 2 6.00 2827 04/10/10 04/22/10 14 | 3 6.00 2827 04/18/10 05N6/10 28 } 4 6.00 2827 04/10/10 05/06/10 28 Samples Made By: Teuncno Services: Obtain samples of fresh concrete o1 the placement locatiouq perform required fieldtests and cast compressive tren xomp|oa. Tu,ruoon Rep.: Francisco J.kYohUo Started: 1400 Reported To: Superintendent Finished: 1730 Contractor: Lacy Construction Report Distribution: Reviewed By: (/) City "rc"m,"xTx (V cit "ro"nna/rx (/)civ"rc"m=u�x cqaynxoo /= _'— - �� ' Senior Project Manager (1) Lacy consliliction (1) PacTrust Pacific Realty Associates LP �b �G����M�\ d� ��mc�n ^~~~~'`~^~~^~^---"----------- to the a nd shall not be ou °". Te resu t r a n sm itte d ..~ . .`~ .a o nly ~ applicab ' the |oogon(s) referenced and are not necessarily indicative uf the properties n[ other apparently similar nr identical materials. Page of