ST0701-LR100421CONCRETE COMPRESSIVE STRENGTH TEST REPORT Report Number: 94091193.0126 Irerracon Service Date: 04/06/10 8901 Carpenter Frwy. Report Date: 04/21/10 Revision I Dallas, TX 75247 214- 630 -1010 Reg No: F -3272 Client City of Coppell TX Attn: Keith Marvin PO Box 9478 Coppell, TX 75019 Project Southwestern Boulevard Coppell Road to Grapevine Creek Coppell, TX Project Number: 94091193 Material Information Sample Information Specified Strength: 4,000 psi @ 28 days Mix ID: DCCOG504 Supplier: Redi -Mix Batch Time: 1323 Plant: P259 Truck No.: 1349 Ticket No.: 25182255 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pet): Result Specification 6 3 -5 3.5 3 -6 80 87 145.6 Laboratory Test Data Set Specimen Diameter Area No. ID (in) (sq in) 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 1 4 6.00 28.27 Sample Date: 04/06/10 Sampled By: Koda W. Weather Conditions: Clear Accumulative Yards: 6.5 Placement Method: Bucket Water Added Before (gal):0 Sample Time: 1318 Shadix Batch Size (cy): 6.5 Water Added After (gal): 0 Sample Location: Column C Placement Location: Columns C and D on Bent #2 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Koda W. Shadix Started: 1200 Reported To: Terry, Ashlar Finished: 1600 Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX Reviewed By: (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5- 21 -09, Rev.3 Page 1 of 1 Age at Maximum Compressive Date Date Test Load Strength Fracture Received Tested (days) (lbs) (psi) Type 04/07/10 04/13/10 7 94,910 3,360 4 04/07/10 04/20/10 14 103,620 3,670 4 04/07/10 05/04/10 28 04/07/10 05/04/10 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Terracon Rep.: Koda W. Shadix Started: 1200 Reported To: Terry, Ashlar Finished: 1600 Contractor: Lacy Construction Report Distribution: (1) City of Coppell TX (1) City of Coppell TX Reviewed By: (1) City of Coppell TX (2) Halff Assoc Inc (1) Lacy Construction (1) PacTrust Pacific Realty Associates LP Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CR0001, 5- 21 -09, Rev.3 Page 1 of 1