Loading...
Red Hawk-LR111114REPORT OF FIELD COMPACTION TESTS 2209 Wisconsin Street, Suite 100 Dallas, Texas 75229 II Geotechnical Construction Materials Environmental www.alphatesting.com TBPE Firm No. 813 TESTED FOR:Creststone GroupDATE: 11/14/11 Coppell, Texas PROJECT:Red Hawk ResidentialOUR REPORT NO.:110991-33 Coppell, Texas TEST DATA:TECHNICIAN:Daniel Montenegro OPTIMUMMAXIMUM LABIN PLACEIN PLACE TESTSOIL ID ELEV. PERCENT DATECOMMENT* MOISTUREDRY DENSITYMOISTUREDRY DENSITY NO.NUMBER COMPACTION DEPTH %PCF%PCF 55511/14/11FG-4.0116.6106.717.0103971-A 55611/14/11FG-3.5116.6106.713.9105981-A 55711/14/11FG-3.0116.6106.715.6106991-A 55811/14/11FG-2.5116.6106.714.7102961-A 55911/14/11FG-2.0116.6106.718.2105981-A 56011/14/11FG-1.5116.6106.719.2106991-A 56111/14/11FG-1.0116.6106.719.0104971-A TEST LOCATION:Utilities 555Sanitary Sewer Service Line to Block A, Pad 26 556Sanitary Sewer Service Line to Block A, Pad 26 557Sanitary Sewer Service Line to Block A, Pad 26 558Sanitary Sewer Service Line to Block A, Pad 26 559Sanitary Sewer Service Line to Block A, Pad 26 560Sanitary Sewer Service Line to Block A, Pad 26 561Sanitary Sewer Service Line to Block A, Pad 26 1. FILL*A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADEB. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS 3. LIME STABILIZEDC. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONSRespectfully Submitted, 4. CEMENT TREATEDD. RETEST Yonas Tanga ALPHA TESTING, INC. Our test results and reports are for the exclusive use of the Client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. REPORT OF FIELD COMPACTION TESTS 2209 Wisconsin Street, Suite 100 Dallas, Texas 75229 II Geotechnical Construction Materials Environmental www.alphatesting.com TBPE Firm No. 813 TESTED FOR:Creststone GroupDATE: 11/14/11 Coppell, Texas PROJECT:OUR REPORT NO.:110991-33A Red Hawk Residential Coppell, Texas TEST DATA:TECHNICIAN:Daniel Montenegro MAXIMUM LABIN PLACEIN PLACE OPTIMUM TESTSOIL ID ELEV. PERCENT DATE COMMENT* MOISTUREDRY DENSITYMOISTUREDRY DENSITY NO.NUMBER COMPACTION DEPTH %PCF%PCF 56211/14/11FG-4.0116.6106.715.6105991-A 56311/14/11FG-3.5116.6106.716.2103971-A 56411/14/11FG-3.0116.6106.718.4102961-A 56511/14/11FG-2.5116.6106.719.2103961-A 56611/14/11FG-2.0116.6106.718.2105981-A 56711/14/11FG-1.5116.6106.718.3105991-A 56811/14/11FG-1.0116.6106.714.6103961-A TEST LOCATION:Utilities 562Sanitary Sewer Service Line to Block B, Pad 12 563Sanitary Sewer Service Line to Block B, Pad 12 564Sanitary Sewer Service Line to Block B, Pad 12 565Sanitary Sewer Service Line to Block B, Pad 12 566Sanitary Sewer Service Line to Block B, Pad 12 567Sanitary Sewer Service Line to Block B, Pad 12 568Sanitary Sewer Service Line to Block B, Pad 12 1. FILL*A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADEB. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS 3. LIME STABILIZEDC. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONSRespectfully Submitted, 4. CEMENT TREATEDD. RETEST Yonas Tanga ALPHA TESTING, INC. Our test results and reports are for the exclusive use of the Client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. REPORT OF FIELD COMPACTION TESTS 2209 Wisconsin Street, Suite 100 Dallas, Texas 75229 II Geotechnical Construction Materials Environmental www.alphatesting.com TBPE Firm No. 813 TESTED FOR:Creststone GroupDATE: 11/14/11 Coppell, Texas PROJECT:Red Hawk ResidentialOUR REPORT NO.:110991-33B Coppell, Texas TEST DATA:TECHNICIAN:Daniel Montenegro OPTIMUMMAXIMUM LABIN PLACEIN PLACE TESTSOIL ID ELEV. PERCENT DATECOMMENT* MOISTUREDRY DENSITYMOISTUREDRY DENSITY NO.NUMBER COMPACTION DEPTH %PCF%PCF 56911/14/11FG-4.0116.6106.719.2104971-A 57011/14/11FG-3.5116.6106.716.3105981-A 57111/14/11FG-3.0116.6106.716.0103971-A 57211/14/11FG-2.5116.6106.716.7105991-A 57311/14/11FG-2.0116.6106.717.5105981-A 57411/14/11FG-1.5116.6106.718.8102961-A 57511/14/11FG-1.0116.6106.719.61071001-A TEST LOCATION:Utilities 569Sanitary Sewer Service Line to Block B, Pad 15 570Sanitary Sewer Service Line to Block B, Pad 15 571Sanitary Sewer Service Line to Block B, Pad 15 572Sanitary Sewer Service Line to Block B, Pad 15 573Sanitary Sewer Service Line to Block B, Pad 15 574Sanitary Sewer Service Line to Block B, Pad 15 575Sanitary Sewer Service Line to Block B, Pad 15 1. FILL*A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADEB. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS 3. LIME STABILIZEDC. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONSRespectfully Submitted, 4. CEMENT TREATEDD. RETEST Yonas Tanga ALPHA TESTING, INC. Our test results and reports are for the exclusive use of the Client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. REPORT OF FIELD COMPACTION TESTS 2209 Wisconsin Street, Suite 100 Dallas, Texas 75229 II Geotechnical Construction Materials Environmental www.alphatesting.com TBPE Firm No. 813 TESTED FOR:Creststone GroupDATE: 11/14/11 Coppell, Texas PROJECT:OUR REPORT NO.:110991-33C Red Hawk Residential Coppell, Texas TEST DATA:TECHNICIAN:Daniel Montenegro MAXIMUM LABIN PLACEIN PLACE OPTIMUM TESTSOIL ID ELEV. PERCENT DATE COMMENT* MOISTUREDRY DENSITYMOISTUREDRY DENSITY NO.NUMBER COMPACTION DEPTH %PCF%PCF 57611/14/11FG-4.0116.6106.716.2102961-A 57711/14/11FG-3.5116.6106.718.21071001-A 57811/14/11FG-3.0116.6106.718.9105981-A 57911/14/11FG-2.5116.6106.718.110319661-A 58011/14/11FG-2.0116.6106.717.2103961-A 58111/14/11FG-1.5116.6106.716.0102961-A 58211/14/11FG-1.0116.6106.717.6102951-A TEST LOCATION:Utilities 576Sanitary Sewer Service Line to Block B, Pad 18 577Sanitary Sewer Service Line to Block B, Pad 18 578Sanitary Sewer Service Line to Block B, Pad 18 579Sanitary Sewer Service Line to Block B, Pad 18 580Sanitary Sewer Service Line to Block B, Pad 18 581Sanitary Sewer Service Line to Block B, Pad 18 582Sanitary Sewer Service Line to Block B, Pad 18 1. FILL*A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADEB. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS 3. LIME STABILIZEDC. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONSRespectfully Submitted, 4. CEMENT TREATEDD. RETEST Yonas Tanga ALPHA TESTING, INC. Our test results and reports are for the exclusive use of the Client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens. REPORT OF FIELD COMPACTION TESTS 2209 Wisconsin Street, Suite 100 Dallas, Texas 75229 II Geotechnical Construction Materials Environmental www.alphatesting.com TBPE Firm No. 813 TESTED FOR:Creststone GroupDATE: 11/14/11 Coppell, Texas PROJECT:Red Hawk ResidentialOUR REPORT NO.:110991-33D Coppell, Texas TEST DATA:TECHNICIAN:Daniel Montenegro OPTIMUMMAXIMUM LABIN PLACEIN PLACE TESTSOIL ID ELEV. PERCENT DATECOMMENT* MOISTUREDRY DENSITYMOISTUREDRY DENSITY NO.NUMBER COMPACTION DEPTH %PCF%PCF 58311/14/11FG-4.0116.6106.719.2103971-A 58411/14/11FG-3.5116.6106.713.6103961-A 58511/14/11FG-3.0116.6106.713.8105981-A 58611/14/11FG-2.5116.6106.718.3106991-A 58711/14/11FG-2.0116.6106.714.6104981-A 58811/14/11FG-1.5116.6106.714.0103961-A 58911/14/11FG-1.0116.6106.715.2103971-A TEST LOCATION:Utilities 583Sanitary Sewer Service Line to Block B, Pad 21 584Sanitary Sewer Service Line to Block B, Pad 21 585Sanitary Sewer Service Line to Block B, Pad 21 586Sanitary Sewer Service Line to Block B, Pad 21 587Sanitary Sewer Service Line to Block B, Pad 21 588Sanitary Sewer Service Line to Block B, Pad 21 589Sanitary Sewer Service Line to Block B, Pad 21 1. FILL*A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADEB. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS 3. LIME STABILIZEDC. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONSRespectfully Submitted, 4. CEMENT TREATEDD. RETEST Yonas Tanga ALPHA TESTING, INC. Our test results and reports are for the exclusive use of the Client (and their designated recipients on file in our office) and shall not be reproduced and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens.