Willow Park-LR120116 8908 Ambassador Row, Dallas, TX 75247 Rone Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404980 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 Report Date: 01/16/2012 Project: Willow Park Townhomes - Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1043 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 01:45pm Batch time: 12:48pm 4.25 Strength: 3,000 psi @ 28 days Temperature - Air: 50 °F Concrete: 69 °F Slump (in.): 3" 5" Truck No: 7089 Ticket No: 1961901 Air ( %): 3% - 6% Air Content: 6.0% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) Sidewalk, Coppell Road, Lot 6 to Lot 28 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 Northeast corner of Lot 6 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in (Ibs) (psi) Type 1 1 01/14/2012 7 5.99 28.18 101,040 3,590 Type 2 1 2 02/04/2012 1 3 02/04/2012 Maid . LI ill .a Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Remarks: Water added at site 9 gallons 19/e �t 1 Technician: Ramiro Ramirez Rone Engineering See Report 404947 for technician time g g Report Distribution: Orig: JR Rose Development Companies (Grapevine, TX) Is? Attn: Mr. Jason Rose (1 -ec copy) 1 -ec Rone Project Manager Attn: Mr. Jason Creasy AET Jason Creasy, AET 1 -ec City of Coppell Attn: Mr. Mike Garza Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 1 of 1 8908 Ambassador Row, Dallas, TX 75247 R one Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404947 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 d Report Date: 01/16/2012 Project: Willow Park Townhomes Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 05:10am Batch time: 04:45am 3.75 Strength: 4,000 psi @ 28 days Temperature - Air: 50 °F Concrete: 60 °F Slump (in.): 3" 5" Truck No: 5018 Ticket No: 1961392 Air ( %): 3% - 6% Air Content: 5.0% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) DaVinci Court from Station 0 +30 to 2 +24.46 at center and Rembrandt Court, Station ASTM C -143 0 +30 to 2 +06.18 at center ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 DaVinci Court, Station 0 +40 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in (Ibs) (psi) Type 1 1 01/14/2012 7 5.99 28.18 114,610 4,070 Type 5 1 2 02/04/2012 28 1 3 02/04/2012 28 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Remarks: Water added at site: 10 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 1 of 5 8908 Ambassador Row, Dallas, TX 75247 R one Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404947 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 Report Date: 01/16/2012 Project: Willow Park Townhomes - Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 06:10am Batch time: 05:45am 3.25 Strength: 4,000 psi @ 28 days Temperature - Air: 44 °F Concrete: 58 °F Slump (in.): 3" - 5" Truck No: 6232 Ticket No: 1961414 Air ( %): 3% - 6% Air Content: 4.5% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) DaVinci Court from Station 0 +30 to 2 +24.46 at center and Rembrandt Court, Station ASTM C -143 0 +30 to 2 +06.18 at center ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 DaVinci Court, Station 1 +80 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in (Ibs) (psi) Type 2 1 01/14/2012 7 5.99 28.18 101,740 3,610 Type 2 2 2 02/04/2012 28 2 3 02/04/2012 28 .f R E u n /tT Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 ; ' f y / .. Remarks: Water added at site 10 gallons " LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 2 of 5 8908 Ambassador Row, Dallas, TX 75247 R one Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404947 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 Report Date: 01/16/2012 Project: Willow Park Townhomes - Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 07:40am Batch time: 07:26am 5.0 Strength: 4,000 psi @ 28 days Temperature - Air: 45 °F Concrete: 62 °F Slump (in.): 3" - 5" Truck No: 6237 Ticket No: 1961504 Air ( %): 3% - 6% Air Content: 3.8% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) DaVinci Court from Station 0 +30 to 2 +24.46 at center and Rembrandt Court, Station ASTM C -143 0 +30 to 2 +06.18 at center ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 DaVinci Court, 30' west from Station 2 +24.46 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested ' (days) (in) (in') (Ibs) (psi) Type 3 1 01/14/2012 7 f 5.99 28.18 115,510 4,100 Type 2 3 2 02/04/2012 28 \■-/` 3 3 02/04/2012 28 N Nd r Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Remarks: Water added at site: 5 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 3 of 5 8908 Ambassador Row, Dallas, TX 75247 R one Engineering 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404947 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 Report Date: 01/16/2012 Project: Willow Park Townhomes - Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 10:10am Batch time: 09:45am 5.0 Strength: 4,000 psi @ 28 days Temperature - Air: 49 °F Concrete: 65 °F Slump (in.): 3" - 5" Truck No: 5018 Ticket No: 1961698 Air ( %): 3% - 6% Air Content: 3.9% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) DaVinci Court from Station 0 +30 to 2 +24.46 at center and Rembrandt Court, Station ASTM C -143 0 +30 to 2 +06.18 at center ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 Rembrandt Court, Station 0 +40 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (lbs) ) Type 4 1 01/14/2012 7 5.99 28.18 135,390 4,800 Type 6 4 2 02/04/2012 28 4 3 02/04/2012 28 [ I �a r Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Remarks: Water added at site: 5 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 4 of 5 Rone Engineering 7701 8908 Ambassador Row, n, TX 75247 W Little le Yorork, , Ste te 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630 -9745 Report of Concrete Compressive Strength Test Client: JR Rose Development Companies Report No.: 404947 2209 Cameron Crossing Project No.: 1116815 Grapevine, TX 76051 Date of Service: 01/07/2012 Report Date: 01/16/2012 Project: Willow Park Townhomes - Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Mix Design I.D.: 1083 Measured Concrete Supplier: Southern Star Placement Date: 01/07/2012 Slump Plant: 110 Weather Conditions: Clear (inches) Specification Requirements Time Sampled: 11:25am Batch time: 11:08am 5.0 Strength: 4,000 psi @ 28 days Temperature - Air: 50 °F Concrete: 66 °F Slump (in.): 3" - 5" Truck No: 6237 Ticket No: 1961817 Air ( %): 3% - 6% Air Content: 3.5% Unit Weight (pcf): NA Test Method: ASTM C -172 Overall Placement Location: ASTM C -31 (except 10.1.2) DaVinci Court from Station 0 +30 to 2 +24.46 at center and Rembrandt Court, Station ASTM C -143 0 +30 to 2 +06.18 at center ASTM C -231 ASTM C -1064 ASTM C -138 Sample Location: ASTM C -1231 Rembrandt Court, 35' from Station 2 +06.18 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in (Ibs) (psi) Type 5 1 01/14/2012 j 7 5.99 28.18 133,220 4,730 Type 2 5 2 02/04/2012 28 5 3 02/04/2012 28 Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Technician: Ramiro Ramirez Started: 04:15am Finished: 02:45pm Rone Engineering Report Distribution: Orig: JR Rose Development Companies (Grapevine, TX) Attn: Mr. Jason Rose (1 -ec copy) - -• 1 -ec Rone Project Manager Attn: Mr. Jason Creasy AET .. 1 -ec City of Coppell Attn: Mr. Mike Garza Jason Creasy, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM /JC) Page 5 of 5