>>>> <marty.paris@kimley-horn.com> 11/15/2011 4:11 PM >>>
> George,
> We have addressed your comments on the Cypress Waters – Saintsbury Street - Water & Wastewater
Tie-in Plans as described below and shown on the attached drawings.
> Water
>
> 1. Delineate City of Coppell maintenance vs. City of Dallas.
>
> a. The delineation is shown and labeled in the plan view on Sheet C-101.
>
> 2. All tie-ins, borings, etc. shall be per City of Coppell Standards.
>
> a. Note #1 was added to the Sheet C-101.
>
> 3. Provide a compound meter instead of a transit time flow meter. Remove sump pump & power
service.
>
> a. The transit time flow meter was removed and replaced with a compound meter as shown on Sheet
C-101 and C-111.
>
> 4. Provide backflow prevention device on the Dallas side of the meter.
>
> a. A double check valve assembly was added as shown on Sheet C-101 and C-111.
>
> 5. All water line fittings, bends, valves, etc. shall have mega-lug type joint connections.
>
> a. Note #2 was added to Sheet C-101.
>
> 6. All bends and tees shall have thrust blocks provided.
>
> a. Note #3 was added to Sheet C-101.
>
> 7. Detail 1 – remove 10” segment of pipe between tee, valve and bend & provide flanged connection.
(1/30/2012) George Marshall - Re: Saintsbury Water and WW Connections to CoppellPage 2
>
> a. Detail 1 on Sheet C-101 was revised.
>
> 8. No compact fittings.
>
> a. Note #4 was added to Sheet C-101.
>
> 9. Use long sleeve dresser coupling to cut in 12”x12” tee (both sides).
>
> a. Note #5 was added to Sheet C-101.
>
> 10. Use City of Coppell standard on 4190 for lid on meter vault.
>
> a. The City of Coppell Standard Detail 4190 is reference on the detail Sheet C-111.
> Wastewater
>
> 11. Delineate City of Coppell maintenance vs. City of Dallas.
>
> a. Note #2 was added to Sheet C-02.
>
> 12. Check proposed size of pipe in call at Sta: 1+98.05 (15” vs. 16”)
>
> a. The size label was changed to 15” on Sheet C-02.
>
> 13. FYI, The City of Coppell has not seen nor approved wastewater plans for the line being tied into by
this construction. Additional comments or changes may be necessary.
> Please let us know if you have any questions or need additional information. Thank you.
> Marty S. Paris, PE
> Kimley-Horn and Associates, Inc.
> 12700 Park Central Drive, Suite 1800
> Dallas, Texas 75251
> 972-770-1300 (main) 972-239-3820 (fax)
> 972-776-1732 (direct)
> marty.paris@kimley-horn.com<mailto:marty.paris@kimley-horn.com>
>
> From: George Marshall [mailto:gmarshall@coppelltx.gov]
> Sent: Friday, November 04, 2011 8:38 AM
> To: Moss, Brad
> Subject: Saintsbury
>
> Brad,
>
> Please see attached comment letter on the Wastewater & water tie-in at Belt Line. The marked up
plans are here for you to pick up.
>
> Thank You, George
>
>