Loading...
ST1002-LR120417CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 0753 Plant: 95 Truck No.: 7058 Ticket No.: 564318895 Field Test Data Test Result Specification Slump (in): 5 1/4 3 -5 Air Content ( %): 4.2 3 -6 Concrete Temp. (F): 73 Ambient Temp. (F): 68 Sample Date: 03/16/12 Sample Time: 0848 Sampled By: Adam Wood Weather Conditions: Mostly cloudy Accumulative Yards: 40 Batch Size (cy): 10 Placement Method: Curb Machine Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: Houston Street - Sta. 6 +25 Placement Location: Paving - Houston Street, west bouund ID driveways, Sta. 6 +00 to 6 +50 and (sq in) Main Street, north bound driveways Tested from Sta. 0 +50 to 5 +00 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 03/17/12 03/20/12 4 100,410 3,550 4 1 2 6.00 28.27 03/17/12 03/23/12 7 115,350 4,080 2 1 3 6.00 28.27 03/17/12 03/23/12 7 119,470 4,230 2 Average (7 days) 4,160 1 4 6.00 28.27 03/17/12 04/13/12 28 148,020 5,240 2 1 5 6.00 28.27 03/17/12 04/13/12 28 147,010 5,200 2 Average (28 days) 5,220 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength samples. Terracon Rep.: Adam Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 0936 Plant: 95 Truck No.: 9150 Ticket No.: 564318913 Field Test Data Test Result Specification Slump (in): 41/2 3 -5 Air Content ( %): 3.8 3 -6 Concrete Temp. (F): 74 Ambient Temp. (F): 73 Sample Date: 03/16/12 Sample Time: 1030 Sampled By: Adam Wood Weather Conditions: Mostly cloudy Accumulative Yards: 110 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: Main Street - Sta. 5 +00 Placement Location: Paving - Houston Street, west bouund ID driveways, Sta. 6 +00 to 6 +50 and (sq in) Main Street, north bound driveways Tested from Sta. 0 +50 to 5 +00 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 2 1 6.00 28.27 03/19/12 03/20/12 4 114,910 4,060 2 2 2 6.00 28.27 03/19/12 03/23/12 7 125,970 4,460 2 2 3 6.00 28.27 03/19/12 03/23/12 7 129,520 4,580 2 Average (7 days) 4,520 2 4 6.00 28.27 03/19/12 04/13/12 28 148,800 5,260 2 2 5 6.00 28.27 03/19/12 04/13/12 28 152,640 5,400 2 Average (28 days) 5,330 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength samples. Terracon Rep.: Adam Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 2 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 1236 Plant: 95 Truck No.: 7069 Ticket No.: 562928161 Field Test Data Test Result Specification Slump (in): 4 3 -5 Air Content ( %): 4.4 3 -6 Concrete Temp. (F): 78 Ambient Temp. (F): 78 Sample Date: 03/16/12 Sample Time: 1330 Sampled By: Adam Wood Weather Conditions: Mostly cloudy Accumulative Yards: 230 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: Main Street - Sta. 1 +25 Placement Location: Paving - Houston Street, west bouund ID driveways, Sta. 6 +00 to 6 +50 and (sq in) Main Street, north bound driveways Tested from Sta. 0 +50 to 5 +00 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 3 1 6.00 28.27 03/19/12 03/20/12 4 112,980 4,000 5 3 2 6.00 28.27 03/19/12 03/23/12 7 118,400 4,190 2 3 3 6.00 28.27 03/19/12 03/23/12 7 120,070 4,250 2 Average (7 days) 4,220 3 4 6.00 28.27 03/19/12 04/13/12 28 143,110 5,060 2 3 5 6.00 28.27 03/19/12 04/13/12 28 153,850 5,440 2 Average (28 days) 5,250 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength samples. Terracon Rep.: Adam Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 3 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi (a, 28 days Sample Date: 03/16/12 Sample Time: 1715 Sampled By: Adam Wood Mix ID: 1851 Weather Conditions: Mostly cloudy Supplier: Lattimore Accumulative Yards: 310 Batch Size (cy): 10 Batch Time: 1632 Plant: 95 Placement Method: Direct Discharge Truck No.: 9105 Ticket No.: 62928186 Water Added Before (gal): 15 Field Test Data Water Added After (gal): 0 Sample Location: Main Street - Sta. 0 +50 Test Result Specification Placement Location: Paving - Houston Street, west bouund Slump (in): 53/4 3 -5 driveways, Sta. 6 +00 to 6 +50 and Air Content ( %): 5.0 3 -6 Main Street, north bound driveways Concrete Temp. (F): 76 from Sta. 0 +50 to 5 +00 Ambient Temp. (F): 77 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 4 1 6.00 28.27 03/19/12 03/20/12 4 111,600 3,950 4 4 2 6.00 28.27 03/19/12 03/23/12 7 123,850 4,380 4 4 3 6.00 28.27 03/19/12 03/23/12 7 127,930 4,530 4 Average (7 days) 4,460 4 4 6.00 28.27 03/19/12 04/13/12 28 156,910 5,550 2 4 5 6.00 28.27 03/19/12 04/13/12 28 157,740 5,580 2 Average (28 days) 5,570 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength samples. Terracon Rep.: Adam Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 4 of 4 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 3,600 psi (a, 28 days Mix ID: 1083 Supplier: Southern Star Batch Time: 1052 Plant: 110 Truck No.: 3041 Ticket No.: 1995489 Field Test Data Test Result Specification Slump (in): 43/4 3-5 Air Content ( %): 5.5 3-6 Concrete Temp. (F): 76 Ambient Temp. (F): 73 Sample Date: 03/16/12 Sample Time: 1115 Sampled By: Adain Wood Weather Conditions: Mostly cloudy Accumulative Yards: 6 Batch Size (cy): 6 Placement Method: Direct Discharge Water Added Before (gal): 5 Water Added After (gal): 0 Sample Location: Crockett St. (a, Sta 0 +50 Placement Location: Pavement - Crockett Street Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 03/19/12 03/23/12 7 101,350 3,590 2 1 2 6.00 28.27 03/19/12 03/23/12 7 94,210 3,330 2 Average (7 days) 3,460 1 3 6.00 28.27 03/19/12 04/13/12 28 128,790 4,560 1 1 4 6.00 28.27 03/19/12 04/13/12 28 117,550 4,160 2 Average (28 days) 4,360 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Adain Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,200 psi (a, 28 days Sample Date: 03/16/12 Sample Time: 1530 Sampled By: Adain Wood Mix ID: 1701 Weather Conditions: Mostly cloudy Supplier: Lattimore Accumulative Yards: 5 Batch Size (cy): 5 Batch Time: 1426 Plant: 95 Placement Method: Direct Discharge Truck No.: 9115 Ticket No.: 64318960 Water Added Before (gal): 10 Field Test Data Water Added After (gal): 0 Sample Location: Cottage Alley (a, Sta. 1 +00 Test Result Specification Placement Location: Inlet sides Slump (in): 3 1/4 3-5 Air Content ( %): 3.3 3-6 Concrete Temp. (F): 78 Ambient Temp. (F): 80 Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 03/19/12 03/23/12 7 127,480 4,510 4 1 2 6.00 28.27 03/19/12 03/23/12 7 124,060 4,390 4 Average (7 days) 4,450 1 3 6.00 28.27 03/19/12 04/13/12 28 161,600 5,720 1 1 4 6.00 28.27 03/19/12 04/13/12 28 155,230 5,490 4 Average (28 days) 5,610 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Not tested for plastic unit weight. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Adain Wood Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Sample Date: 04/06/12 Sample Time: 0720 Age at Maximum Sampled By: Randall Hollis Mix ID: 1851 Specimen Diameter Weather Conditions: Clear Supplier: Lattimore Test Load Accumulative Yards: 10 Batch Size (cy): 10 Batch Time: 0632 Plant: 95 Placement Method: Direct Discharge Truck No.: 5013 Ticket No.: 564320211 Water Added Before (gal): 10 Field Test Data 1 6.00 Water Added After (gal): 0 04/10/12 4 117,840 Sample Location: North side along Houston Test Result Specification Placement Location: Paving - north parking on Houston Slump (in): 41/2 3-5 between Hanuriond and Coppell road Air Content ( %): 4.7 3-6 28.27 04/07/12 Concrete Temp. (F): 75 125,810 4,450 5 Ambient Temp. (F): 55 Plastic Unit Wt. (pcf): 146.3 (7 days) 4,490 Yield (Cu. Yds.): 4 6.00 28.27 04/07/12 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 04/07/12 04/10/12 4 117,840 4,170 4 1 2 6.00 28.27 04/07/12 04/13/12 7 127,900 4,520 2 1 3 6.00 28.27 04/07/12 04/13/12 7 125,810 4,450 5 Average (7 days) 4,490 1 4 6.00 28.27 04/07/12 05/04/12 28 1 5 6.00 28.27 04/07/12 05/04/12 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Randall Hollis Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,200 psi (a, 28 days Sample Date: 04/06/12 Sample Time: 1513 Age at Maximum Sampled By: Randall Hollis Mix ID: 1701 Specimen Diameter Weather Conditions: Clear Supplier: Lattimore Test Load Accumulative Yards: 5 Batch Size (cy): 5 Batch Time: 1349 Plant: 95 Placement Method: Direct Discharge Truck No.: 7037 Ticket No.: 262428005 Water Added Before (gal): 10 Field Test Data 1 6.00 Water Added After (gal): 0 04/10/12 4 111,380 Sample Location: See placement location Test Result Specification Placement Location: Inlet at Bethel and South Coppell Slump (in): 3 3-5 4,150 4 Air Content ( %): 3.3 3-6 28.27 04/07/12 Concrete Temp. (F): 84 117,100 4,140 4 Ambient Temp. (F): 77 Plastic Unit Wt. (pcf): 147.3 (7 days) 4,150 Yield (Cu. Yds.): 4 6.00 28.27 04/07/12 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 04/07/12 04/10/12 4 111,380 3,940 5 1 2 6.00 28.27 04/07/12 04/13/12 7 117,400 4,150 4 1 3 6.00 28.27 04/07/12 04/13/12 7 117,100 4,140 4 Average (7 days) 4,150 1 4 6.00 28.27 04/07/12 05/04/12 28 1 5 6.00 28.27 04/07/12 05/04/12 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Randall Hollis Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,200 psi @ 28 days Mix ID: 1701 Supplier: Lattimore Batch Time: 1149 Plant: 955 Truck No.: 5033 Ticket No.: 64320305 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 43/4 3 -5 4.5 3-6 78 63 148.7 Sample Date: 04/09/12 Sample Time: 1230 Sampled By: Christopher Amoah Weather Conditions: Cloudy Accumulative Yards: 5 Batch Size (cy): 5 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: SW corner Placement Location: Storm Inlet (a, SE corner of S. Fracture Coppell Rd. and Bethel Rd. Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 04/10/12 04/16/12 7 127,780 4,520 2 1 2 6.00 28.27 04/10/12 04/16/12 7 121,970 4,310 2 Average (7 days) 4,420 1 3 6.00 28.27 04/10/12 05/07/12 28 1 4 6.00 28.27 04/10/12 05/07/12 28 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Christopher Amoah Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 0900 Plant: 955 Truck No.: 5028 Ticket No.: 64320406 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 4 3 -5 4.2 3-6 85 70 146.7 Laboratory Test Data Set Specimen Diameter No. ID (in) 1 1 6.00 1 2 6.00 1 3 6.00 1 4 6.00 Area Date (sq in) Received 28.27 04/12/12 28.27 04/12/12 28.27 04/12/12 28.27 04/12/12 Sample Date: 04/11/12 Sample Time: 0950 Sampled By: Christopher Amoah Weather Conditions: Clear Accumulative Yards: 10 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: 20' from Hammond on N Retail Alley Placement Location: Paving - North and South Retail Alleys Age at Date Test Tested (days) 04/18/12 7 04/18/12 7 05/09/12 28 05/09/12 28 Maximum Compressive Load Strength Fracture (lbs) (psi) Type Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Christopher Amoah Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 1047 Plant: 955 Truck No.: 7017 Ticket No.: 64320416 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 5 3 -5 4.2 3-6 85 75 144.7 Laboratory Test Data Set Specimen Diameter No. ID (in) 2 1 6.00 2 2 6.00 2 3 6.00 2 4 6.00 Area Date (sq in) Received 28.27 04/12/12 28.27 04/12/12 28.27 04/12/12 28.27 04/12/12 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: Age at Date Test Tested (days) 04/18/12 7 04/18/12 7 05/09/12 28 05/09/12 28 04/11/12 Sample Time: 1150 Christopher Amoah Clear 110 Batch Size (cy): 10 Direct Discharge 10 0 Center of North Retail Alley Paving - North and South Retail AlleysAlley Maximum Compressive Load Strength Fracture (lbs) (psi) Type Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Christopher Amoah Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 2 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi (a, 28 days Sample Date: 04/11/12 Sample Time: 1510 Sampled By: Christopher Amoah Mix ID: 1851 Weather Conditions: Clear Supplier: Lattimore Accumulative Yards: 210 Batch Size (cy): 10 Batch Time: 1356 Plant: 955 Placement Method: Pump Truck No.: 9141 Ticket No.: 62929187 Water Added Before (gal): 0 Water Added After (gal): 0 Field Test Data Sample Location: SE corner of South Retail Alley Test Result Specification Placement Location: Paving - North and South Retail Slump (in): 33/4 3-5 AlleysAlley Air Content ( %): 4.2 3-6 Concrete Temp. (F): 85 Ambient Temp. (F): 80 Plastic Unit Wt. (pcf): 145.5 Yield (Cu. Yds.): Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 3 1 6.00 28.27 04/12/12 04/13/12 2 92,970 3,290 6 3 2 6.00 28.27 04/12/12 04/14/12 3 116,040 4,100 5 3 3 6.00 28.27 04/12/12 04/18/12 7 3 4 6.00 28.27 04/12/12 05/09/12 28 3 5 6.00 28.27 04/12/12 05/09/12 28 3 6 6.00 28.27 04/12/12 06/06/12 56 Comments: Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Christopher Amoah Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 3 of 3 SAMPLE PICK -UP REPORT Irerracon Report Number: 94111246.0153 Service Date: 04/10/12 8901 Carpenter Frwy. Suite 100 Report Date: 04/17/12 Dallas, TX 75247 214 - 630 -1010 Reg No:F -3272 Client Project City of Coppell TX Old Town Coppell & Bethel Road Attn: Rick O'Dell #ST10 -02 Engineering Dept Between Coppell Rd & Freeport PO Box 9478 Coppell, TX Coppell, TX 75019 Project Number: 94111246 TOTAL NUMBER OF CONCRETE CYLINDERS PICKED UP: 4 Report No.: 94111246.0152 No. of Cylinders: 4 Services: Concrete cylinder pickup. Terracon Rep.: Michael Flute Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) JRJ Paving LP, Emailed Reviewed By: Eric J. Cleveland, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. BC0001, 10- 25 -10, Rev.9 Page 1 of 1 Inc