DR1101-CS110628 Kimley -Horn and Associates, Inc.
12700 Park Central Drive, Suite 1800 Meeting Agenda
Dallas, Texas 75251
(972) 770 -1300
fax (972) 239 -3820
h o t•-1 Cok ke
Project: Cypress Waters
Dallas, Texas
Subject: Project Coordination Meeting for Water & Wastewater Connections to
Coppell System
Date: June 28, 2011
Prepared by: Marty S. Paris, P.E.
Items to Discuss:
1. Overall Project Status
2. Wastewater Force Main Connection at Beltline Road
3. Wastewater Lift Station Design
4. Wastewater Force Main Meter
5. Water Main Connection at Beltline Road
6. Emergency Water Meter
7. Status of Supplemental Agreement No. 3 to Treated Water Contract
8. Other Discussion Items
Meeting Agenda_20110628.doc Page 1 of 1
The Thermo Scientific DCT6088 "''�
advanced transit time flowmeter O
0 .
employs a unique digital correlation =
C)
technique to reliably measure the flow —
C#)
of clean liquids. Designed for use
on pipes of all sizes, the non - intrusive n
device is easy-to-install, simple
n
to operate, and eliminates pressure CO
..h
loss and leakage which reduces p'
downtime and increases profit potential. y
Dedicated Transit Time Flowmeter
,.
.d, ,
" - a
,a tat
ti " . ....1 i ,,, , , , ,
Flexible & Easy -to -Use Programmable Relays for Remote Output
Combining digital signal processing (DSP) Up to four programmable relays can be
lib IRO with correlation detection methods, the specified. The relays may be used as a contact
Thermo Scientific DCT6088 features output to a remote device such as an alarm,
-"" .' exceptional performance and flexibility. totalizer, sampler or chlorinator. A powerful
It tolerates higher concentrations of gas 30,000 point data logger programmable
A. bubbles or entrained solids compared to in intervals of one second or more is also
:,'� traditional transit time flowmeters which are incorporated in the flowmeter.
principally designed for extremely clean liquid Modular & Simple to Service
applications only. The non intrusive, camp- l The plug -in, modular construction of the
"'""'" _. - on transducers can be installed without flow
' _. �., interruption and ensure leak -free measurements instrument simplifies field service and,
in the unlikely event of failure, permits
... with zero pressure drop. The simple, menu the boards to be replaced in seconds.
The Thermo Scientific driven operation of the DCT6088 allows the p
,,,.` UltraScan program offers The DCT6088 features many parts which
meter to be commissioned in a fraction of
a simple method to configure are common to other Thermo Scientific
the flowmeter and access the time necessary for competitive transit
`=+ - to the extensive waveform time flowmeters. flowmeters, dramatically reducing spare
6 .----- ' ".- diagnostics. parts inventory at sites where multiple
Engineered for Maximum Uptime meters are in service.
Housed in a rugged IP65 enclosure and
Features qualified for -40 °C ( -40 °F) operation, the Sample Applications
• Accuracy to ±0.5% of velocity full scale DCT6088 is well- suited to most industrial • HVAC
• 0.01 ft/sec flow sensitivity environments. The high resolution, backlit • Potable water
•
• Up to 4 programmable relays LCD provides excellent visibility even Ultrapure liquid
• Easy to install, clamp -on design in poorly lit conditions. Outputs include • Deionized water
• Bi-directional flow measurement • Petroleum products
a 12 bit digital, optically isolated, 4 20 mA • Water and waste management
• Powerful 30,000 point data logger analog signal and RS232 serial interface. g
Part of Thermo Fisher Scientific S C I E N T I F I C
R
Specifications and Ordering Information
Thermo Scientific DCT6088
Performance Specifications
Velocity Range ±0 m/s to 15 m/s ( ±0 m/s to 50 ft/s)
Accuracy ±0.5% of velocity or ±0.05 ft /sec typical
Fluids Potable water, ultrapure liquids, deionized water, petroleum products
Pipe Size 25.4 mm to 5 m (1 in to 200 in); For line sizes smaller than 1 inch, consult Thermo Fisher Scientific
Physical Specifications
Transmitter IP65, flame retardant, fiberglass reinforced polyester
Transducers Two encapsulated transducers suitable for submersion or underground service; 9 m (30 ft) standard cable length
Weight Approximately 5.4 kg (12 Ibs)
Functional Specifications
Outputs 4 -20 mA (into 1 k - 5k ohms), 12 -bit, 5 kV, opto - isolated, loop or self - powered;
RS232 serial interface
Power Supply 90 -132 Vac or 190 -250 Vac, 50/60 Hz (switch selectable); 11 -28 Vdc
Temperature Range Transducers: (surface) -40 °C to +100 °C ( -40 °F to +212 °F); (ambient) -28 °C to +80 °C (-20 °F to +176 °F)
Transmitters: -40 °C to +60 °C ( -40 °F to +140 °F)
Contact factory for higher temperature range requirements
Keypad 19 -key with tactile action
Display 2 -line, 40- character, alphanumeric, backlit LCD indicating present and total flow, velocity and signal strength
Data Logger 30,000 point data logger; programmable in 1 second intervals
DCT6088 Dimensional Diagram Ordering Information
MODEL NUMBER
2e5 mm f ( ' DCT6088: Dedicated Digital Correlation Transit Time Flowmeter
(11. m)
A. POWER SUPPLY
II )1 — 1: 90 to 132 Vac, 50/60 Hz 3: 12 to 24 Vdc nominal
m m m o ,� T 2: 190 to 250 Vac, 50/60 Hz l
mmm o0o i
.mm 0
E -- a o o 'O O I 'Tr' a °� E' B. OUTPUT
0 0 0 0 t' 1 : O mA DC, no relay 4: Three yys
1: One ne relay 4: Four r relays
relalays
` 2: Two relays
1 C. TRANSMITTER ENCLOSURE
� 1: NEMA 4X 2: NEMA 7 l
1 D. TRANSDUCER TYPE
r. S: Standard cable (10000C/21200F max)
DCT6088 Mounting Methods \. H: High temp cable (200 cC /392°cF max)
E. CABLE LENGTH
T ' ; \ Z Method: directly across the pipe 030: 9 m (30 ft) cable
- 203 mm (8 in) and larger X)O(: XXX = length in feet
F. TRANSDUCER
V41%,, V Method: single reflex HAZARDOUS AREA
"` ;„4; - 101 mm (4 in) and larger CERTIFICATION
A: None
A.M B: CSA: Class I, Div. 2
t" W Method: double reflex
' Groups A, 8, C, D
- 50 mm (2 in) and larger
or Class II, Div. 2
Groups E F G
,,, C: CSA: Class I, Div.1
WW Method: multi reflex / = ^ ,- Groups C, D or Class II,
- 25 mm (1 in) DCT 1 B D Div. 1 Groups E, F, G
60 88 ...J- - - -- - . /
02008 Thermo Fisher Scientific Inc. All rights reserved. Results may vary under different operating conditions. Specifications, terms and pricing are subject to change.
Not all products are available in all countries. Please consult your local sales representatives for details. Literature Code PI.2018.1208
Room 1010 - 1019 +86 )10) 5850 -3588
Ping'an Mansion No. 23 Jinrong Street +86 (10) 6621 -0847 fax
Xicheng Dist, Beijing 100032 CHINA
A -101, ICC Trade Tower, Senapati Bapat Road +91 (20) 6626 7000
Pune 411016 Maharashtra, INDIA +91 (20) 6626 7001 fax
Ion Path, Road Three, Winsford +44 )0) 1606 548700
Cheshire CW7 3GA UNITED KINGDOM +44 )0) 1606 548711 fax
Process Instruments 1410 Gillingham Lane +1 (8001437 -7979 www.thermo.com
Sugar Land, TX 77478 USA +1)713)272 -0404
+1 (713) 272 -4573 fax S C I E N T I F I C