ST1002-LR120430CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 0648 Plant: 955 Truck No.: 7059 Ticket No.: 64319747 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 41/2 3 -5 3.9 3 -6 82 69 147.6 Sample Date: Sampled By: Weather Conditions: Accumulative Yards: Placement Method: Water Added Before (gal): Water Added After (gal): Sample Location: Placement Location: 03/30/12 Sample Time: 0740 Jonathan O'Connor Cloudy 20 Batch Size (cy): 10 Direct Discharge 15 0 Center of Alley Paving - Alley east of West Main Street between Houston and Travis Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 03/31/12 04/02/12 3 118,020 4,170 2 1 2 6.00 28.27 03/31/12 04/06/12 7 131,970 4,670 2 1 3 6.00 28.27 03/31/12 04/27/12 28 149,500 5,290 2 1 4 6.00 28.27 03/31/12 04/27/12 28 148,400 5,250 2 Average (28 days) 5,270 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Jonathan O'Connor Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 0849 Plant: 955 Truck No.: 7059 Ticket No.: 64319758 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 3 1/2 3 -5 3.6 3 -6 84 70 150.1 Sample Date: 03/30/12 Sample Time: 0945 Sampled By: Jonathan O'Connor Weather Conditions: Cloudy Accumulative Yards: 110 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: South end of Alley Placement Location: Paving - Alley east of West Main Fracture Street between Houston and Travis Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 2 1 6.00 28.27 03/31/12 04/02/12 3 113,840 4,030 5 2 2 6.00 28.27 03/31/12 04/06/12 7 130,820 4,630 1 2 3 6.00 28.27 03/31/12 04/27/12 28 157,550 5,570 4 2 4 6.00 28.27 03/31/12 04/27/12 28 156,060 5,520 2 Average (28 days) 5,550 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Jonathan O'Connor Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 2 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,500 psi @ 28 days Mix ID: 1851 Supplier: Lattimore Batch Time: 1142 Plant: 955 Truck No.: 7008 Ticket No.: 64319782 Field Test Data Test Slump (in): Air Content ( %): Concrete Temp. (F): Ambient Temp. (F): Plastic Unit Wt. (pcf): Yield (Cu. Yds.): Result Specification 6 3 -5 3.5 3 -6 84 73 148.8 Sample Date: 03/30/12 Sample Time: 1225 Sampled By: Jonathan O'Connor Weather Conditions: Cloudy Accumulative Yards: 220 Batch Size (cy): 10 Placement Method: Direct Discharge Water Added Before (gal): 0 Water Added After (gal): 0 Sample Location: Center of parking Placement Location: Paving - Head -in parking on west side Fracture of Travis between west Main and ID Hammond Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 3 1 6.00 28.27 03/31/12 04/02/12 3 112,600 3,980 2 3 2 6.00 28.27 03/31/12 04/06/12 7 120,700 4,270 2 3 3 6.00 28.27 03/31/12 04/27/12 28 143,100 5,060 2 3 4 6.00 28.27 03/31/12 04/27/12 28 139,730 4,940 2 Average (28 days) 5,000 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Jonathan O'Connor Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 3 of 3 CONCRETE COMPRESSIVE STRENGTH TEST REPORT Material Information Sample Information Specified Strength: 4,200 psi @ 28 days Mix ID: 1701 Supplier: Lattimore Batch Time: 1356 Plant: 952 Truck No.: 7069 Ticket No.: 62928721 Field Test Data Test Result Specification Slump (in): 3 3 -5 Air Content ( %): 3.0 3 -6 Concrete Temp. (F): 90 Ambient Temp. (F): 77 Plastic Unit Wt. (pcf): 147.0 Yield (Cu. Yds.): Sample Date: 03/30/12 Sample Time: 1454 Sampled By: Jonathan O'Connor Weather Conditions: Clear Accumulative Yards: 5 Batch Size (cy): 5 Placement Method: Direct Discharge Water Added Before (gal): 5 Water Added After (gal): 0 Sample Location: See Placement Location Placement Location: Inlet on S Coppell, S of Bethel Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Date Test Load Strength Fracture No. ID (in) (sq in) Received Tested (days) (ibs) (psi) Type 1 1 6.00 28.27 03/31/12 04/06/12 7 137,160 4,850 4 1 2 6.00 28.27 03/31/12 04/06/12 7 132,490 4,690 2 Average (7 days) 4,770 1 3 6.00 28.27 03/31/12 04/27/12 28 160,550 5,680 2 1 4 6.00 28.27 03/31/12 04/27/12 28 160,510 5,680 2 Average (28 days) 5,680 Comments: Average compressive strength of 28 day cylinders complies with the specified strength. Samples Made By: Terracon Services: Obtain samples of fresh concrete at the placement locations, perfonn required field tests and cast compressive strength sainples. Terracon Rep.: Jonathan O'Connor Reported To: Contractor: Report Distribution: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Reviewed By: (1) City of Coppell TX, Emailed (1) City of Coppell TX, Emailed Eric J. Cleveland, P.E. (1) Freese and Nichols Inc, Emailed (1) 7R7 Paving LP, Emailed Senior Project Manager Test Methods: ASTM C 31, ASTM C39, ASTM C138, ASTM C143, ASTM C172, ASTM C231, ASTM C1064, ASTM C1231 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. CROOO1, 8- 27 -11, Revs Page 1 of 1