Townhouses-LR010220 REF )RT OF FIELD �i,• COMPACTION TESTS ALPHA TESTING, INC. 2209 Wisconsin St.,Suite 100 Dallas, Texas 75229 972/620-8911 - 972/263-4937(Metro) FAX: 972/406-8023 TESTED FOR LEMP DEVELOPMENT DATE 02/20/01 DALLAS, TEXAS PROJECT COPPELL TOWNHOMES OUR REPORT NO. 00430-103 COPPELL, TEXAS TEST DATA: TEST ELEV. SOIL ID OPTIMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT NO. DATE DEPTH NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT' % PCF % PCF 1787 02/20/01 FG-3.0 2 19.0 100.4 21.2 99 98 1-A 1788 02/20/01 FG-2.0 2 19.0 100.4 21.5 98 98 1-A 1789 02/20/01 FG-1.0 2 19.0 100.4 21.0 99 99 1-A 1790 02/20/01 FG-3.0 2 19.0 100.4 20.8 98 98 1-A 1791 02/20/01 FG-2.0 2 19.0 100.4 20.9 98 98 1-A 1792 02/20/01 FG-1.0 2 19.0 100.4 19.4 99 99 1-A TEST LOCATION: 1787 8"WATER LINE 100'WEST FROM THE 2ND FIRE HYDRANT ALONG CENTER LINE OF TRENCH 1788 8"WATER LINE 100' EAST FROM THE 2ND FIRE HYDRANT ALONG CENTER LINE OF TRENCH 1789 8"WATER LINE 40' EAST FROM THE 2ND FIRE HYDRANT ALONG CENTER LINE OF TRENCH 1790 8" WATER LINE 125' WEST FROM THE 4TH FIRE HYDRANT ALONG CENTER LINE OF TRENCH 1791 8" WATER LINE 25' EAST FROM THE 4TH FIRE HYDRANT ALONG CENTER LINE OF TRENCH 1792 8" WATER LINE 50'WEST FROM THE 4TH FIRE HYDRANT ALONG CENTER LINE OF TRENCH CC: STEVE TOPLETZ,ANDANTE 1 FILL * A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS 2. NATURAL SUBGRADE B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS R. e '/Ily • itted 3. LIME STABILIZED C. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS i/� 4 CEMENT TREATED D. RETEST ALP - a S ING, IN / Geotechnical Engineering / Construction Materials Testing I Environmental Engineering If Consulting