Villas at LV 2-LR121129 IliFrom: 12/12/2012 15:20 #234 P.001 /021
41N11. Alpha Testing,Inc. ��
2209 Wisconsin St.,Suite 100 Concrete Compression Test
Dallas,TX 75229
(972)620-8911 Report
TBPE Firm No.813
Tested For: JBGL BF DEVELOPMENT LLC Date Issued: 11/29/2012
ATTN: SCOT WHITWER Our Report#: 121732-2
3131 HARVARD AVE.,SUITE 103
DALLAS,TX 75205 PM: BULENT ETHEM,P.G.
Fax Number: (214)383-1117
Project Desc:VILLAS AT LAKE VISTA PHASE 2-UTILITIES PAVING 1 Z 1 7
SE OF MACARTHUR BLVD.&LAKE VISTA DRIVE
FIELD DATA
Placement Location: SIDEWALK ALONG LAKE VISTA DR.
Sample Location: 10'N OF 1ST SECTION OF SIDEWALK ON WEST SIDE
Date Placed: 11/21/2012 Plant Number: 955
Time Placed: 9:45 AM Delivery Ticket No.: 64333189
Slump(ASTM C-143): 3.5 Mix ID: 1261
Air Content: N/A Made By: ALPHA
Air Temperature: 53
Specimen Temperature: 65 L Cured Specification: ASTM C-31
Date Received: 11/22/2012
•K i \Field Data Submitted By: Villegas,Julian
Mix Data Submitted By: LMC
a
CYLINDER COI -RESSION TEST RESULTS
Lab Cure Break Cap • a Age Avg. Avg. Avg Depth/ Area: Max
No.: Type: Type: Spec: ested: (Days): Length Width Diameter Sq.In. Load: PSI:
1 LAB C-1231 11/28/2012 7 8 N/A 4 12.56 45590 3630
2 LAB 12/19/2012 28 8 N/A 4 12.56 0
3 LAB 12/19/2012 28 8 N/A 4 12.56 0
4 LAB HOLD HOLD 8 N/A 4 12.56 0
Specifications: ---------- ----- 28 -------------000
— -- - —
Results to Date: N/
CC:
Respectfully Submitted By: - of Alpha Testing,Inc.
Test Method:Unless noted,concrete was sampled and tested in accordance with ASTM C172,C143,C231,C173,C1064 AND C138.Compression strength tests
per ASTM C39. Our test results and reports are for the exclusive use of the Client(and their designated recepients on file in our office)and shall not be reproduced
and/or distributed except with express approval of ALPHA. The use of our name and test results must receive our written approval. Test results and reports apply
only to the samples tested and/or observed,and are not indicative of the qualities of apparently identical or similar specimens.