Loading...
Cici's Addition-LR 990923CONTRA CT INSPECTION SER VICE, Inc. 4305 Glenwood Ct. Granbury, TX 76049 (817) 246-8096 FAX (817) 246-5889 REPORT OF S TR UCTUR/IL/JMC DISTRIBUTION CENTER Project: Client: Report No: 15179-9 Attention: Keith Atkins Date of Service: 09-23-99 CiCi - JMC Distribution Center Coppell, TX. Reed Engineering Group 2424 Stutz, Suite 400 Dallas, TX. 75235 Page ! of 1 I Drawings utilized: REPORT OF INSPECTION Structural Prints/AWS D 1.1-98 Locations/item inspected: Random only due to the advance stage of construction. Discrepancies/comments: 1.) Joist girder to panel pocket ( details F4/S4.01) and (01/E4). Connection found non-complaint due to: A.) Girder seat not welded full length. B.) Stiffener plate weld undersize. 2 .) Joist girder to column cap - Connection found non-compliant due to: A.) Missed welds B .) Weld length C .) Undersize welds 3.) Joist to panel at panel joint- Connection found non-compliant due to: A.) Welded side not per detail. B.) 3 I/2 "x 3 1/2" x 3/8"x 0 - Six (6) inch angle not welded as per detail. C.) Expansion side welded. 4.) Deck support angle was found non-compliant due to bottom side not welded. 5.) Joist to joist girder - Random inspection revealed compliance. Larry G Peel, CWI #89120661 Technician Contra~t l~ns ction Service This report is for the exclusive use of our client and shall not be modified or reproduced without written approval from said client