CF-Village-CS 890516 GINN, INC. CONSULTING ENGINEERS
Mr. Steve Ooram, Director of Public Works
City of Coppell -
P.O. Box478 ~[ ..... ""--I~)
Copp~ll, Texas 75019
Re: Village Parkway Pump Station
Sandy Lake Road Rate of Flow Controller Modifications
Dear Mr. Goram:
As you are aware, the Village Parkway Pump Station (VPPS) Project includes
upgrading the Dallas Water Utilities (DWU) bypass meter at the Sandy Lake Road
Rate of Flow Controller. The existing 4" meter is being upgraded to an
turbine meter. The original specifications submitted by DWU and incorporated
into the VPPS contract documents requested a Rockwell Series W meter and
strainer. The VPPS Contractor submitted a Hersey turbine meter and Neptune
strainer for approval (by DWU). At that time, DWU requested that a UL listed
strainer be installed in lieu of a standard strainer.
Since the UL rated strainer is a significant variance from the Contract
Documents, Cajun Contractors, Inc. has requested a Change Order in the amount
of $3,824.00 to provide the UL rated strainer (see attached letter). Upon
receipt of the request, we contacted DWU to clarify their position and desires
on this matter. The attached letter from DWU indicates that this decision
should be made by the City of Coppell.
We are unable to fully justify the necessity of a UL rated strainer at this /
location. The strainer will be located on the bypass (maintenance) meter and
not on the primary delivery facility. We are_nnaware of any pn~ib~e savings
(or penalty) to the City of Coppell from th~State Board of Insurance-~ relatedJ
to this strainer. Should the City of Coppell-de¢lde fo become a "Key Rated"'-
city, the UL strainer may have some benefit.
Please review this matter and inform us of the City's desires as soon as
possible. If you need additional information, please contact us.
Sincerely,
attachments
cc: Russell Doyle, P.E.
H. Waynj/' Ginn, P.E.
File 38JY
17103 Preston Road · Suite 100 · LB 118 · Dallas, Texas 75248 · Phone 214/248-4900
Aprzi ~
;' I 1989 i i
DATO~ nOUG£
~AI.LA$ · ATI.A~TA
, 1989
Home Office: Dallas Office: Atlanta Office:
P.O. ~x 1~ · Balon R~, ~ 70821~1~ P.O. ~x 54~87 * Dallas, ~ 75354~487 4000 Cumberland Pkwy., Bldg. 800, Ste. A · Atlanta, GA 3~39
(504) ~3-~57 · F~ No. (5~) ~1-9777 (214) 55~8611 · Fax No. (214) 55~1816 (404) 333~195 · Fax No. (4~) 333-01~
Ginn, Incorporated
17103 Preston Road Suite 100
Dallas, Texas 75248
Attention: Mr. Sanford Case, P.E.
RE: Village Pkwy Pump Station
Coppell, Texas
Gentlemen:
Ca~un Contractors, Inc. has reviewed your comments on the strainer
submittal for the above referenced pro~ect. Your note requires
the strainer to be UL approved; however, 'the pro~ect
Specifications do not. Consequently, this requirement represents
extra work in accordance with Section Six of the Contract
Specification.
Ca~un has researched and obtained pricing information on the
requested strainer which we propose to furnish for an additional
$3,824.00. Cost detail is shown below.
Adder for UL Approved Strainer $3,2~0.00
Bonds and Insurance ~§.00
Subtotal Cost $3,3~§.00
Ca~un - 15% 499.00
Total Change Order Cost $3,8~4.00
Your review of and response to this request at your earliest
convenience shall be appreciated.
Sincerely,
CAJUN CONTR%CTORS, INC.
Karl D. Hirschey
Pro~ect Manger
cc: File 1.11 (8821)
Baton Rouge (8821)
Field
dallas
uJa el-
utllltl(
HAY i 11989
City Hall · Dallas. Texas 75277 · (214)670-3146 j..
Na.y 8, 1989
Sanford Case
Ginn, [nc.
Consulting Engineers
17103 Preston Road
Suite 100, LB 188
Dallas, Texas 75248
Dear Nr. Case:
This letter is to confirm Dallas Water Utilities' recon~nendation regarding the
type of strainer (domestic vs. UL rated) which should be used with the 6"
turbine meter replacing the 4" FM meter at the water metering station serving
the City of Coppell.
The decision regarding the type strainer to be used should be made by the City
of Coppell. Dallas Water Utilities prefers that the UL (fire) rated strainer
be used; however, this is not a requirement for this metering station.
Designs of future metering stations should include thc UL rated strainer in
conjunction with turbine meters.
Please let me know if we can be of further assistance. Please call me or Phil
Boyd (670-5887) if you have any questions.
Sincerely,
W. David Ryburn
Manager
Wholesale Services Division
PB/trh
c: Bill Kaster, Engineering Division
Mike Rickman, Distribution Division
Larry McDaniel, Pumping & Watershed Management
A cily utility providing Dallas wilh water purification and distribulion, waste water collection and lreatment
FILE COPY
VILLAGE PARKWAY PUMP STATION
CITY OF COPPELL
PROJECT NO. 380
APPROVED ~~
APPROVED AS NOI'ED
REVISE & RESUBMIT F'-3
NOT APPROVED 12-'-I
FOR RECORD ONLY [-'-3
APPROVAL DOES NOT RELIEVE THE
CONTRACTOR FROM RESPONSIBILITY
FOR CONFORMANCE WITH CON'rRACT
REQUIRErViENTS. SE[~ SPECIFICATION
.SECTION 01300
Blt B.
,, DALLAS ~',,'A'r_.r.~_R_ {jT/Li'.rIES DEPT.
~-A.P-P.,I-, G-.V.A.b V. ES ~ ~~_~,~ -"----
'~P ~.~.l~Aq'.,I~) N--NU M B.E R ~,,~2.6,1.0 ,~.2~ 64.0
TURBIN~ M~.TER AND STRAINP. R
DRAWING SiIE~.T 42 OF 46
]'Ills I.')['[AWIr4C; I IA$I,,...h"'""' ' l,," ..... .'IF..WXD
I..l( Ol.ll'~ Ol'l'll:?: /',rid L .... ,,,:.;.,.
TO 'I'IIE l.ti'.?UiJ,c~,-c~il:, di.'
DOCtJi',~JI .['] "'
CAJUN CO "'"" .... '"' I'~G '"""'~ "
Industrial International
cJallas water UTIIITIOS
..o,....,.o
320 East Jefferson Dallas, Texa~ 75203 (214) 946-4550
February 14, 1989 /~~--'~~j -
Sanford Case, P.E.
GINN , INC.
Consulting Engineers
17103 Preston Road, Suite 100, I,B 118
Dallas, Texas 75248
Re: Village Parkway Pump Station and Reservoir
And Related Dallas I{quipment
Dear Mr. Case:
Thank you £or the opportunity to review your plans covering
some of the new DWU Equipment related to serving this nel,,
facility.
Information sliown on plan sheets 42 and 43 supplied to you
by DWIJ was to assist you in your design efforts and was not
intended to release Ginn, Inc., £rom design responsi, b[]ity
of tile project.
The Hersey Turbine Meter submittal is acceptable however,
DWU requires the U .L. listed strainer be used in
conjunction with it.
Sorry for the delay in responding. If you have any
questions or if I can be of any assistance please contact
me.
Sincerely,
Bi. Il Kaster
Project Management