Loading...
CF-Village-CS 890224 (2)GINN, INC. CONSULTING ENGINEERS February 24, 1989 Mr. Karl D. Hirschey Cajun Contractors, Inc. P.O. Box 540487 Dallas, Texas 75354-0487 Re: Village Parkway Pump Station City of Coppell, Texas Proposed Change Order - Electrical Breakers Dear Mr. Hirschey: We have been requested by the City of Coppell's Building Inspection Department to investigate the possibility of adding remote trips for the main service breakers on the above referenced project. Enclosed is a letter from C.R. McCreary and Associates which outlines the additional materials required for this modification. Please review the enclosure and prepare a proposal for this work. Upon receipt of your proposal, we will discuss the matter with the City of Coppell and determine if a formal change order will be pursued. Please call if you have any questions. Sincerely, Sanford W. Case, P.E. Project Manager " enclosure cc: Russell Doyle, P.E. Steve Goram Dale Jackson Joe Kotrla, P.E., C.R. McCreary and Associates H. Wayne Ginn, P.E. Gabe Favre J.R.File Richardson380 17103 Preston Road · Suite 100 · LB 118 · Dallas, Texas 75248 · Phone 214/248-4900 CONSULTING ENGINEERS ,' SUITE 217 CHAR/ES R. tl//cCREARY & ASSOC/ATES : fREEWAY ~ DALLAS, TEXAS 75240 ,' 214/458-8M5 Mr. Sanford Case, P.E. -- Ginn, Inc. 17103 Preston Rd., Suite 100 Dallas, Texas 75248 Re: Village Parkway Pump Station C~.Ly of Coppell, Texas Subject: City of Coppell Electrical Ordinance Dear Sanford, I met with Mr. Dale Jackson of the City of Coppell earlier this week regarding the City Electrical Ordinance. He gave us permission to let the main breakers be tripped from the outside of the building. Please initiate a change to do this. The breakers are already specified to be electrically operated, so all we have to do is add the pushbuttons, control wiring, and the enclosures. The contractor will need to do the following: 1. Install a 3/4 inch conduit with 5 # 12 awg control wires from the switchgear to a NEMA 3R enclosure on an outside wall. The conduit should be in the slab. The enclosure should be on the outside building wall inside of the fence next to the double doors for the switchgear room. 2. The Enclosure shall be NF2~A 3R at least 10" tall by 8" wide by 6" deep, Hoffman # A-10R86HCR with a # A-10NSP backpanel. The pushbuttons shall be red in color, maintained type (push to trip, pull to reset) with a mushroom head, Square D class 9001 type SK. Each pushbutton shall be mounted in a Square D class 9001 type KY enclosure inside the Hoffman enclosure. Each pushbutton shall trip its respective main. The pushbutton shall not re-close the main when ~t is reset, however it will. be required to be reset before the breaker can be manually re-closed from the ~nside. 3. The outside of the enclosure shall have an engraved nameplate stating "MAIN BREAKER REMOTE TRIP" with white 1" high letters o~ a red background. Inside the pushbuttons shall have nameplates stating "MAIN BREAKER ~ 1 TRIP" and "MAIN BREAKER ~ 2 TRIP" white 1/4" high letters on a red CHAR/ES R. /V/cCREARY & ASSOCIATES background. Also, there shall be a nameplate on the inside door of the Hoffman enclosure stating "BREAKERS CAN ONLY BE CLOSED MANUALLY AFTER TRIP". Please call if you have any questions or if I can be of any assistance. Sincerely, Joseph Kotrla, P.E. page 2 of 2 CONSULTING ENGINEERS SUITE 2]7 CHAR/ES R. /I//cCREA£Y & ASSOC/ATES ~3~o lB.~ FREEWAY DALLAS, TEXAS 75240 214/455.$745 February 16, 1989 Mr. Dale Jackson City of Coppell P.O. Box 478 Coppell, Texas 75019 Re: Village Parkway Pump Station City of Coppell, Texas Subject: City of Coppell Electrical Ordinance Dear Mr. Jackson, This is to confirm our discussion on Monday the 13th of February, 1989. in order to comply with the City of Coppell's electrical ordinance we will initiate a change to install remote trip pushbuttons for each main breaker. These pushbuttons will be on the outside of the building in a lockable enclosure. The outside of the enclosure will have a permanent nameplate stating "MAIN BREAKER REMOTE TRIP" in white letters 1" tall on a red background. Inside two emergency type pushbuttons will be marked "MAIN BREAKER # 1 TRIP" and "MAIN BREAKER # 2 TRIP". Please notify us if you have any questions or comments. Sincerely, ~rla, P.E. CC: Mr. Sanford Case, P.E. Ginn, Inc. 17103 Preston Rd., Suite 100 Dallas, Texas 75248