Loading...
CF-Village-CS 890117 ,' ' CONSUl TING ENGINEERS CHAR/ES R. /I/lc£REAR) & ,4SSO£/ATES ,, · SUITE · 63/0 LBJ FREEWAY / OALLAS, TEXAS 75240 214/458-8745 Mr. Sanford Case, P.E. Ginn, Inc. 17103 Preston Rd., Suite 100 Dallas, Texas 75248 Re: Village Parkway Pump Station City of Coppell, Texas Subject: Dual Service Dear Sanford, In regard to our conversation last week about the dual service arrangement at the Village Parkway Pump Station, I would like to make the following comments: 1. A dual prima~y with one set of transformers in our opinion does not meet the requirements for "duplicate electrical circuits" as described in the State Board of Insurance Waterworks Regulation TW ~ 3 dated 6-11-71. 2. A transformer failure in a single transformer service clearly shows that the circuits are not duplicate since that failure disables the pump station until the utility can install a replacement. The down time will depend on whether the utility has that particular transformer in stock. 3. According to Mr. Jerry Itidalgo at the [leaith Department, a change to a single transformer service would require a resubmittal of the plans to the Plan Review Department at the state. Since the Village Parkway Pump Station is likely to be the City's only pump station in the near future we feel that the dual service including dual service primaries and transformers is warranted. Please call if you have any questions or if I can be of any assistance. Sincerely, ~trla, P.E.