Loading...
Cambridge Phase 1-CS 941228 COPPELL PUBLIC WORKS MEMORANDUM DATE: December 28, 1994 TO: Garreth Campbell, Construction Inspector FROM: Howard Pafford, Utilities Superintendent ~ RE: Utilities Walk Through Punchlist for Cambridge Manor Phase I Below I have listed the items found deficient during the above referenced walk through, conducted yesterday afternoon. Walk thru - 12/27/94 1. Cambridge Manor lane & Deforest, mainline valve needs blockout 2. Needs 1 1/2" setter & double check complete with boxes at Deforest entry. 3. Manhole needs retaining wall and set at proper grade- eTA 19+83.36A 4. Cambridge Manor Lane Lot 2-unable to locate mainline valve, unable to locate fire hydrant valve cap. Paint red and mark curb. 5. Cambridge Manor Court-mainline - Paint cap blue and mark curb 6. Ail valve caps need to be painted and marked on curb. 7. Lot 7-water in meter can, possible leak -(Kings Canyon) 8. Sta.# 1+99.08 line H - clean out bottom of manhole 9. Replace cleanout pad on Lot 9 10. Sta.#02041-1ine-E clean out bottom of manhole 11. Sta.#2t85 line I - reset chimney seal in manhole 12. Sta.#0+95 line J - cleanout full of dirt, pour concrete bottom and cleanout 13. Lot 16 Block D - check meter service for leak 14. Cleanout on Lot 13- full of rock, replace pipe and clean 15. Sta.# St66.09 line I - reset chimney seal in manhole 16. Sta.# St13.62 line G - needs chimney seal in manhole 17. Lower curb stop on setter, should be in separate can or in box with setter-17" flange to flange, Located on north service common area 18. Sta.#15.19 line C- add one more chimney seal extension to manhole 19. Lot 1 blk. E - meter can full of water, possible leak 20. Tighten chimney seal in manhole @ eta.# 4+79.23 line C 21. Lot 2 meter can full of water, possible leak 22. Clean out bottom of manhole Sta.#15+47.35 23. Rainpan for manhole @ Sta.#17+86.41-A 24. Pour pad for cleanout Terry's property. All sewer laterals from Subdivision to west have no pads. Need to pour. 25. Sta.#00+00A manhole needs cleaning, shape bottom invert to carry better 26. Manhole in rear of first lot on west side of entry to subdivision needs to be set at grade 27. Entry to subdivision-some type of retaining walls should be built to prevent erosion along street right-of-ways and back and side yards of lots.