CF-Village-CS 881020 GINN, INC. CONSI I,TING ENGINEEIIS Mr. Larry Overcast Smith Pump Company, Inc. 301 M & B Industrial Waco, Texas 76710 Re: Village Parkway Pump Station City of Coppell, Texas Dear Mr. Overcast: Thank you for. your recent request to submit Imo Delaval pumps on the above referenced project. Our review of your submittal indicates that the Imo Delaval P16/14D pump does appear to generally conform to the requirements specified in Addendum #1 for this project. The proposed pump speed of 1180 RPM is acceptable as long as the Starting KVA Code Letter on the motors remain F or below. Proposals will be evaluated in accordance with the procedures listed in Addendum #1 and any deficiencies will be subjected to the listed penalties at that time. Thank you for your interest in this project. Sincerely, Sanford W. Case, P.E. Project Manager Steve Goram H. Wayne Ginn, P.E. File 380 17103 Preston Road · .~uilc I00 · I,I; I1~ · I)alla'-. 'l'cxas 7524,"'; · Ph~,m' 214.'"24S-.1%~00