Loading...
CF-Village-CS 881014 GINN, INC. ( ONSI I..,TI October 14, 1988 Mr. Malcom Mur~ Jersey Equip~ent Company 1428 MacAr~hur, Suite 111 Carrollt~tS, Texas 75007 Re: Village Parkway Pump Station City of Coppell, Texas Dear Mr. Murphy: Thank you for your recent request to submit Allis Chalmers pumps on the above referenced project. Since the time of your submittal, Addendum #1 has been issued to all plan holders of record which includes a revision to the pump specifications. Our review of your submittal indicates that while the Allis Chalmers 16x12x23 9000 Series pump does appear to meet the design rated point, it appears to not meet the Minimum Capacity Point, Minimum Parallel Operating Point, and Required Minimum Shut Off Head for this project. Under the evaluation criteria, these deficiencies would be subjected to penalties. If you desire to revise your submittal or submit another pump for consideration, we will be happy to review it at that time. Sincerely, ~'~ / ~ >" /.; Sanford W. Case, P.E. Project Manager cc: Russell Doyle, P.E.~/ H. Wayne Ginn, P.E. File 380