Loading...
CF-Village-CS 890202 GINN, INC. CONSI-LTING ENGINEERS February 2, 1989.~ Coppell~Texas 75019 Re: Village Parkway Pump Station Dual Service Power Dear Mr. Doyle: Per your request, we have investigated the possibility of reducing the cost of providing dual service power facilities to the Village Parkway Pump Station. The dual primary service with one set of transformers proposed by T.U. Electric could subject the station to a considerable power outage in the event of a transformer failure. It is our opinion that the reduced facilities will not satisfy the State Board of Insurance or Texas Department of Health regulations. We feel that the estimate of $65,000 by T.U. Electric to provide full dual service power is reasonable and within the project budget. The cost of auxiliary generation facilities would be much higher. We feel it is in the City of Coppell's best interest to pursue the full dual service power agreement at this time. We are including the comments of our electrical sub-consultant for your review. Please feel free to contact us if you have any questions. Sincerely, Sanford W Case, P.E .... ~~"~'~ attachment cc: Steve Goram ~~~~~'"- Frank Trando H. Wayne Ginn, P.E. File 380 17103 Preston Road · %t, ite 100 · I_B 118 · Dallas. Texas 75248 · Phone 214/248-4900