George Marshall, PE
469- 964 -4731
Begin forwarded message:
George Marshall
Thursday, August 08, 2013 11:18 AM
Larry Davis; Rhonda Adloo; Richard Gee
Fwd: Creekview RFI #1
RFI #1 - Acitve Anchor Modification.pdf, ATT00001.htm
From: "Ernest Fields" <EFields @walterpmoore.com>
To: "George Marshall" <GMarshall @coppelltx.gov>
Cc: " mnorth @arkcontractingservices.com11 < m north @arkcontracti ngservices.com >, "Rod Lacy
(RLacv @faingp.com)" <RLacv @faingp.com>
Subject: Creekview RFI #1
George,
I received the attached email requesting a change to our active anchor detail. Ark has asked if we would
allow them to use concrete in the unbonded length of the active anchors instead of the non - shrink
grout. We have no problem with changing the detail as marked up by Ark. Please let me know if you
need anything more formal from me. Thanks,
Ernie
Ernest L. Fields, P.E., LEED BD +C
Principal
WALTER P MOORE
1845 Woodall Rodgers Freeway, Suite 1650
Dallas, Texas 75201 -2287
214.740.6200
214.740.6300 fax
214.783.5157 mobile
efieldsawalterpmoore.com
www.walterpmoore.com
THE CONTENTS OF THIS E -MAIL AND ANY ATTACHMENT(S) ARE CONFIDENTIAL AND THE PROPERTY OF WALTER P.
MOORE AND ASSOCIATES, INC.
1
Ernest Fields
From: Mark North < mnorth@arkcontractingservices.com >
Sent: Thursday, August 08, 2013 10:36 AM
To: Ernest Fields
Cc: rlacy @faingp.com; 'Tiffany Rawls'
Subject: Active Anchor Grout RFI
Attachments: CREEKVIEW TIEBACK ANCHOR GROUT RFI DETAIL.pdf
Ernie,
Pursuant to our conversation this morning please find attached the Tieback Anchor Grout RFI Detail for your approval. We
would like to install the specified 5000 PSI non shrink grout in the bonded zone of the tieback anchors. The non shrink grout
would extend over the end of the 3 inch PVC pipe sleeve 12 inches to seal the unbounded tieback zone. Grease would be
installed inside the 3 inch PVC pipe in the unbounded zone as specified. The void between the 10 inch drilled shaft and the 3
inch PVC sleeve would be filled with ready -mix concrete.
Please notify us of your approval. If you have any questions please do hesitate to contact me.
Thanks,
Mark North
Ark Contracting Services, LLC
817.478.7400 Office
817.478.7438 Fax
817.475.1355 Cell
BFAW BEYOND ANCHOR-N" f-YAR'Eli a- 3` -0.
GAMN MKETF REF
SECMNS FOR DIMENSION
1 'x6'x6' PLATE ACHORAGE
r
CAST SWING SURFACE FOR
PLATE ANCHC E AND BEAM
PWE NON - SHRINK GROUT--
MM ANCHORAGE SYYU To
MWAIN 3' MJN CLM COVER .
3" PVC CASING -FILL wml oREASI
REF, ROCK ANCHOR NOTES
2
60 Mk DRIM HOLE
ANCHOR GROUT, REF.
ROCK Al'CHOft NOTES
L- Cf?Nl`NDJ5 SiI�El. REINF, BAR WRH-'
A4 f? ZERS AT MAX SPACING OF 5`-
REF. PUN A�hIO SECTION' FOR
qVLENGV, SIDE. AND SIREN
• - ��
M-1 A L 'Z3L - A TI
SCALE: 1/2'= V -Q"
,Y
HIGHLY PERMEABLE FILTER FABRIC;
AEF. GENETUL NOTES
CRUSHED ROCK t1 ER ZONF_
REF. GENERAL NOTES
NOTE: ILK E1.EYATIONS DEPICTED IN THE
SECTIONS ARE BASED ON INFORMATON
CONTAINED IN THE GEOVECH REPORT. THE
ACTUAL ROCK EU -YAWNS WILL VARY. IF
THE ANCHOR LfNMU INCREASES SY MORE
THAN 10' LONGpR THAN THE .PL*3 INDIarF,
A CONTRACT MOM17CATION IS WARRANTED.
OCK ANCHOR' DETAIL
UMESTONE