CF-TownC CHC-SY 841127GEOTECHNICAL INVESTIGATION
FOR
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
PREPARED FOR
CITY OF COPPELL
COPPELL, TEXAS
Maxim Engineers Inc. <~eotecsn~,ca/r¥1a[erial<' 3(}:s~ir~c/Cor~L ~ ~ia'
GEOTECHNI CAL INVESTIGATION
FOR
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
REPORT
to
CITY OF COPPELL
COPPELL, TEXAS
by
MAXIM ENGINEERS, INC.
GEOTECHNICAL/MATERIALS TESTING/CONSULTANTS
DALLAS, TEXAS
November 27. 1984
Maxim Engineers Inc.
Maxim Engineers, Inc.
Geotechnical
Materials Testing
Consultants
November 27, 1984
Mr. Ron Ragland
City of Coppell
Box 478
Coppell, Texas
75019
Re: Report No. C-4-0476
Geotechnical Investigation
Proposed Coppell City Hall
Parkway Boulevard
Coppell, Texas
Dear Mr. Ragland:
Submitted herein is a report summarizing the results of the geotechnical
investigation performed at the above referenced project.
We trust the recommendations derived from this investigation will pro-
vide an adequate and economical foundation design. As your project
develops we would be pleased to assist you with material quality inspec-
tion and quality assurance testing.
We thank you for the opportunity to provide you with our professional
services. If we can be of further assistance, please do not hesitate to
contact us.
Very truly yours,
MAXIM ENGINEERS, INC.
Vice President
due, P.E.
President
SMH: GWP :lsl
cc: O'Brien, O'Brien, Nyfeler & Callaway Corporation
TechniStructures
2342 Fabens
F~O. Box 59902
Dallas, Texas 75229
(214) 247-7575
SYNOPSIS
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
The synopsis is included for the convenience of our clients and is
intended only as a general overview of the results of this investiga-
tion. Designs based upon the information in this report should be made
only after reading and thoroughly understanding the recommendations as
they are stated in the main body of the report.
PROJECT DESCRIPTION
The proposed building will be located along the south side of
Parkway Boulevard, east of Denton Tap Road in Coppell, Texas.
II. SUBSURFACE CONDITIONS
Subsurface stratigraphy consisted of intermittent layers of dark
brown, brown, and yellowish brown clays, sandy clays, clayey sands
and sands underlain by a gray shale stratum encountered at a depth
of 15 to 18.5 feet below the ground surface.
Subsurface seepage water was encountered 10 to 20 feet below the
ground surface.
III.
FOUNDATION TYPE
The building's structural loads may be supported by auger
excavated, straight-sided, cast-in-place reinforced concrete piers
founded at least three (3) feet into the primary shale formation
encountered 15 to 18.5 feet below the existing ground surface.
These piers may be designed and proportioned using an allowable
end bearing pressure of 22,000 pounds per square foot and a skin
friction value of 2,750 pounds per square foot of shaft area in
direct contact with the gray shale below the recommended minimum
penetration.
IV. FLOOR SLABS
The building's floor slab may be placed on one of the following
subgrade systems:
a. 12 to 18 inches of select fill placed on existing compacted
soils - Estimated floor slab movement 0.75 to 1.00 inch; or
Maxim Engineers Inc.
b. A structural floor slab system with a six (6) inch void
provided between the concrete slab and the exposed subgrade.
V. PAVEMENT RECOMMENDATIONS
Light duty pavement may consist of four (4) inches of Portland
Cement Concrete over six (6) inches of compacted subgrade.
Channelized heavy traffic areas will require six (6) inches of
Portland Cement Concrete* over the compacted subgrade. Weakened
planes (sawed joints) of at least one fourth the pavement thick-
ness should be provided at maximum spacings of 15 feet.
*See Guidelines in Appendix of this report.
Maxim Engineers Inc.
TABLE OF CONTENTS
Introduction ............................................. 1
Project Description ..................................... 2
Subsurface Conditions ................................... 2
Analyses and Recommendations ........................... 3-6
APPENDIX
Field and Laboratory Investigations .....................
General Construction Recommendations ...................
Guidelines for Concrete Pavement ........................
Joint Cross-Section .....................................
Plan of Borings
Log of Borings
Symbols and Terms used on Boring Logs
Unified Soil Classification System
A-1
A-3
A-7
A-10
Maxim Engineers Inc.
GEOTECHNICAL INVESTIGATION
FOR
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
INTRODUCTION
This report transmits the findings of the geotechnical investi-
gation performed at the referenced site. The purpose of this
investigation was to define and evaluate the general subsurface
conditions in the immediate vicinity of the proposed City Hall
building. Specifically, the study was planned to determine the
following:
e
Subsurface stratigraphy within the limits of explor-
atory borings.
Classification. strength and compressibility char-
acteristics of the foundation strata.
Suitable foundation systems and allowable soil load-
ing pressures.
The Potential Vertical Rise (PVR) of critical soil
strata.
Interior floor slab recommendations to accommodate
anticipated subgrade movements.
Construction requirements for the alteration of
existing site conditions.
Construction requirements for the placement of
necessary earth embankments or fills.
Generalized section recommendations for roadways and
parking area pavements.
Other soil related problems which may be revealed by
the investigation.
Maxim Engineers Inc.
This study was performed in accordance with the request of
Mr. Tony Callaway with O'Brien, O'Brien, Nyfeler ~ Callaway
Corporation in Dallas, Texas. To accomplish the intended
purposes, a three phase study program was conducted which includ-
ed: a) a field investigation consisting of nine (9) exploration
test borings with samples obtained at selected intervals; b) a
laboratory testing program designed to evaluate the expansive and
strength characteristics of the subsurface soils; and c) an
engineering analysis of the field and test data for foundation and
pavement design recommendations. No additional analysis was
requested or performed. A brief description of the various field
and laboratory tests and their respective results is included in
the Appendix of this report.
II.
PROJECT DESCRIPTION
The proposed project will consist of a two-story City Hall. The
building will be built at the location indicated on the plan of
borings included in the appendix of this report. Light to
moderate structural loads are anticipated.
The project site is located along the south side of Parkway-Boule-
vard, east of Denton Tap Road in Coppell, Texas.
III.
SUBSURFACE CONDITIONS
The subsurface soils encountered at the test borings locations
consisted of a dark brown, brown, and yellowish brown clays, sandy
clays, clayey sands and sands that extended to a depth of 15 to
18.5 feet below the ground surface, where a gray shale stratum was
encountered.
Maxim Engineers Inc.
At the time this investigation was performed, groundwater was
encountered at the borehole locations at depth ranging between 10
and 20 feet. The depth to groundwater may change with variations
in atmospheric conditions, therefore, its depth should be verified
just prior to construction that may be affected by its presence.
If there is a drastic change, then Maxim Engineers, Inc. should be
notified to review the effect it may have on the recommended
foundation systems.
IV. ANALYSES AND RECOMMENDATIONS
The professional services which have been performed, the findings
obtained and the recommendations prepared were accomplished in
accordance with currently accepted geotechnical engineering prin-
ciples and practices. The possibility always exists that the sub-
surface conditions at the site may vary somewhat from those
encountered in the boreholes. The number of borings and spacing
was chosen in such a manner as to decrease the possibility of
undiscovered abnormalities, while considering the nature of load-
ing, size, and cost of the project. If there are any unusual
conditions differing from those described herein, Maxim Engineers,
Inc. should be notified to review the effects on the performance
of the designed foundation. The recommendations given in this
report are applicable only for the design of the previously
described City Hall to be constructed at locations indicated at
this site; they should not be used for any other purpose. This
firm is not responsible for the conclusions, opinions, or recom-
mendations made by others based on this information.
Maxim Engineers Inc.
1. Support of Structural Loads
The building's structural loads may be supported by a founda-
tion system consisting of auger excavated, straight-sided,
cast-in -place, reinforced concrete piers founded at least
three (3) feet into the primary shale formation encountered 15
to 18.5 feet below the existing ground surface. The piers may
be designed using an allowable end bearing pressure of 22,000
pounds per square foot and a skin friction value of 2,750
pounds per square foot of shaft area in direct contact with
the gray shale below the recommended minimum penetration.
Foundations designed and constructed in accordance with the
recommendations provided in this report will have a factor of
safety of 2.5 or more against shear type failure. Total
settlement potential is less than one (1) inch with differen-
tial settlement potential on the order of 0.50 to 0.75 inch.
The majority of all settlement should occur during initial
loading.
The subsurface water conditions encountered at the test boring
locations indicate that temporary casing of some of the
foundation piers will be required.
2. Soil Movement
The near surface soils encountered at the site exhibited
relatively moderate plasticity indices. Some of these soils
should be considered as relatively active and capable of
vertical soil movements ranging between 1.00 and 2.00 inches
with changes in moisture conditions.
Maxim Engineers Inc.
5
Floor Slabs
To reduce the effect of the moisture induced soil movement on
the building, the floor slab may be placed on 12 to 18 inches
of select fill that is placed above the surrounding grade.
The select fill should be processed in accordance with the
recommendations provided in the Appendix of this report.
Estimated vertical differential slab movements 0.75 to 1.00
inch. Considerable more movement will occur in areas where
water is allowed to pond next to the building during or after
construction.
In areas where floor slab movement can not be tolerated, a
structural floor slab with a six (6) inch void provided under
the concrete slab may be used.
All grade beams should be underlain by a six (6) inch void
space provided between the concrete and the surface soils·
Pavement Recommendations
Prior to beginning pavement construction, soils at the natural
ground surface in the proposed parking area should be scari-
fied and grubbed to a depth of at least six (6) inches. Orga-
nic materials and any vegetation should be removed from the
site. The scarified areas along with areas requiring addi-
tional fill should then be recompacted to a minimum of 95
percent of the maximum dry density as defined by ASTM D 698
(Standard Proctor Test) at a moisture content within three (3)
percent of the optimum moisture value.
Maxim Engineers Inc.
The following pavement sections are presented for your consid-
eration:
Areas of Light Traffic (Auto Parking)
4.00 inches Portland Cement Concrete*
(15 foot joint spacing)
6.00 inches Compacted Subgrade
Areas of Channelized Traffic
6.00 inches Portland Cement Concrete*
(15 foot joint spacing)
6.00 inches Compacted Subgrade
*See Guidelines for Concrete Pavement in the Appendix of this
report.
The light duty pavement is designed for 200 to 300 vehicles
per day, two (2) to three (3) of which may be heavy commercial
trucks. The channelized heavy traffic pavement is designed to
sustain 300 to 500 vehicles per day including five (5) to
seven (7) heavy commercial vehicles.
Maxim Engineers Inc.
FIELD AND LABORATORY INVESTIGATIONS
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
A-1
Field Investigation
Soil conditions at the project site were determined by nine (9)
intermittent sample borings which were drilled during November,
1984.
The locations of these borings are shown on the sheet entitled
"Plan of Borings" of this report. Descriptions of the various
strata encountered in each of the borings and the depths at which
samples were obtained are presented on the individual "Log of
Borings".
Undisturbed specimens of cohesive soils were obtained with thin-
wailed Shelby tube samplers (ASTM D 1587). The soil specimens
were extruded from the tube in the field, logged, sealed and pack-
aged to maintain "in situ" conditions.
Disturbed samples of the noncohesive granular or stiff to hard
cohesive materials have been obtained utilizing a two (2) inch
O.D. split-spoon sampler in conjunction with the Standard Penetra-
tion Test (ASTM D 1586). This test employs a 140 pound hammer
Maxim Engineers Inc.
A-2
that drops a free fall vertical distance of 30 inches, driving the
split-spoon sampler into the material. The number of blows
required for 18 inches of penetration is recorded and the value
for the last 12 inches, or the penetration obtained from 100
blows, is reported as the Standard Penetration Value (N) at the
appropriate depth on the attached "Log of Borings".
II.
Laboratory Soils Tests
Laboratory soil tests were performed on samples recovered from the
borings to verify visual classification and determine the perti-
nent engineering properties of the soils encountered.
Atterberg Limits, Moisture Content, Unit Dry Weight and Percent
Passing A No. 200 U.S. Sieve tests were performed on representa-
tive samples in order to classify them according to the Unified
Soil Classification System. The results of all the laboratory and
field tests are tabulated on the "Log of Borings" presented in the
Appendix.
Unconfined Compressive Strength tests were performed on selected
undisturbed soil samples to determine the ultimate unconfined
compressive strength of the different subsurface strata encounter-
ed. The results of all the laboratory and field tests are
tabulated on the "Log of Borings" presented in the Appendix.
Maxim Engineers Inc.
GENERAL CONSTRUCTION RECOMMENDATIONS
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
A-3
Site Preparation
Prior to placing any fill material, all existing surface vegeta-
tion should be removed. All exposed surfaces should then be scar-
ified, watered as required and recompacted to a minimum of 95 per-
cent of the maximum dry density as defined by ASTM D 698 (Standard
Proctor Test) at a moisture content within three (3) percent of
the optimum moisture value. The site may then be filled to grade
using a suitable fill material, free from deleterious matter.
Fill materials should be placed in six (6) to eight (8) inch loose
lifts at moisture contents within three (3) percent of optimum and
each lift compacted to between 93 and 100 percent of the maximum
dry density as defined in ASTM D 698.
inspected and approved by a qualified
supervised by a Geotechnical Engineer before
added.
Each lift should be
engineering technician,
another lift is
II.
Select Fill
"Select Fill" as referred to in the main body of the report should
consist of clayey sands free of organic materials and having a
Maxim Engineers Inc.
A-4
Plasticity Index between four (4) and fifteen (15), and a Liquid
Limit of 40 or less. Placement and compaction of the select fill
should be performed in accordance with the above mentioned "Site
Preparation" section.
III.
Foundation System
Normal construction procedures for this area of Texas should be
employed in the installation of drilled, cast-in-place, straight
shaft foundations. Concrete and reinforcing steel should be
placed immediately after the excavation has been completed and
inspected by a Soils Engineer to assure compliance with design
assumptions and to verify: A) the bearing stratum; B) the minimum
penetration; C) the removal of all smear zones and cuttings; and
D) that groundwater seepage is correctly handled. In no event
should an excavation be allowed to remain open for more than eight
(8) hours. Ail concrete placed in excavations in excess of ten
(10) feet in depth should be properly tremied to prevent separa-
tion of the aggregates. Based on borehole information, it appears
that temporary casing will be required at some locations to avoid
sloughing of the upper soils and seepage infiltration in the area
of the proposed excavations.
IV.
Surface Drainage, Vegetation
Drainage should be maintained away from the foundations, both dur-
ing and after construction. Trees and large shrubs can, by trans-
piration, remove water from the clays and cause shrinkage of these
Maxim Engineers Inc..
A-5
soils and settlement of the floor slabs. Therefore, any shrubs or
trees planted for landscaping should be located at least one and
one-half their anticipated mature height away from the building.
Ve
Secondary Design Considerations
The following information has been assimilated after examination
of numerous problems dealing with similar soil throughout the
area. It is presented here for your convenience. If these fea-
tures are incorporated in the overall design of the project, the
performance of the structure will be improved.
A. Roof drainage should be collected by a system of gutters and
downspouts and transmitted by a pipe to a storm drainage
system or to a paved surface where the water can drain away
without entering the soil,
B. The sidewalks should not be structurally connected to the
building. They should be sloped away from the building so
that water will be drained away from the structure.
Ce
Special consideration should be given to completion items out-
side the building area such as stairs, walkways, signs, etc.
They should be adequately designed to sustain the potential
vertical movements mentioned in the main body of the report.
Maxim Engineers Inc. _
A-6
D. Parking lots, streets and surface drainage should be sloped
away from the buildings on all sides. Water should not be
allowed to pond near the buildings after the slab has been
placed.
Et
Backfill for utility lines should be carefully placed so that
they will be stable. If the backfill is too dense or too dry,
swelling may form a mound along the ditch line. If the back-
fill is too loose or too wet, settlement may form a sink along
the ditch line. Either case is undesirable since several
inches of movement is possible and floor cracks are likely to
result. The soils should be processed using the previously
discussed compaction criteria. Where the utility lines pass
through the parking lot, the top 6 inches should be compacted
similarly to the remainder of the lot.
The floor slab placed at or below existing grades should be
provided with a moisture barrier in order to prevent wet
spots.
Maxim Engineers Inc..
GUIDELINES FOR CONCRETE PAVEMENT
PROPOSED COPPELL CITY HALL
PARKWAY BOULEVARD
COPPELL, TEXAS
REPORT NO. C-4-0476
A-7
CHARACTERISTICS OF CONCRETE:
1. Ail concrete should have a specified 28 -day compressive
strength of 3,000 psi. Concrete should be manufactured and
delivered in accordance with ASTM C 94; Standard Specification
for ready mixed concrete.
2. Four (4) to six (6) percent air should be entrained in the
concrete.
3. The maximum coarse aggregate size should not be greater than
one-fourth the slab depth.
4. Maximum slump should be four (4) inches + one (1) inch.
II.
SUBGRADE PREPARATION:
1. Prior to beginning paving operations, all vegetation should be
removed to a depth of at least six (6) inches.
The exposed surface should then be scarified and recompacted
to a minimum of 95 percent of the maximum dry density as
determined by ASTM D 698 [ Standard Proctor Test) at a moisture
content within three (3) percent of the optimum moisture
value.
Maxim Engineers Inc.
A-8
e
In the event that additional fill is necessary to bring the
parking area to grade, it should be placed in 6 to 8 inch
loose lifts and compacted to a minimum of 95 percent of the
maximum dry density as determined by ASTM D 698 (Standard
Proctor Test) at a moisture content within three (3) percent
of the optimum moisture value.
4. The subgrade should be in a moist condition at the time con-
crete is deposited thereon.
Using coarse sand (sand cushion) as a leveling material is not
recommended. Surface runoff water may be piped through the
coarse material and adversely affect the underlying subgrade.
III.
JOINT S:
1. Recommended joint spacings are provided in the "Pavement
Recommendations" section of this report.
Control joints or contraction joints should be formed by one
of the following methods: sawed, hand-formed or formed by
premolded filler. Joint depth should be equal to 1/4 of the
slab thickness. Hand-formed joints should have a maximum edge
radius of 1/4 inch. Sawing of joints should begin as soon as
the concrete has hardened sufficiently to permit sawing with-
out excessive ravelling. All joints should be completed
before uncontrolled shrinkage cracking occurs. Joints should
Maxim Engineers Inc.
A-9
be continuous across the slab unless interrupted by full-depth
premolded joint filler, and should extend completely through
the curb. Joint openings wider than 1/4 inch should be
cleaned and sealed before opening parking area to traffic.
Expansion joints or isolation joints should be used to isolate
fixed objects abutting or within the paved area. They should
contain premolded joint filler for the full depth of the slab
and should be sealed prior to opening to traffic.
4. Utilization of an integral curb is recommended.
Maxim Engineers Inc.
Structure
I i I
Isolation Joint
X. , Expansion
I 1
Material
-~d{Butt-faced
Construction Joint
JOIb~ CROSS-SECTIONS
iSawed Joint
4 Typical
Premolded Filler Jo.int, , 17
.~enolded Filler
Flush with Surface
Keyed Construction Joint
d
iHand-Formed Joint
-V
Thickened Edge Isolahion Joint
Expansion Material ,
- Use only where wheel loads
will cross the joint
Structure
Transverse Oonstruction Joint
Note: All joints should be cleaned and sealed
prior to opening to traffic.
PARKWAY BOULEVARD _..~..~
B-6 B-7
B-I
t~ B-4 ~B-3
-L1 ~._~ r-F
·
PROPOSED COPPELL CITY HALL COPPELL,
Log of Boring INumber [Location
B-1 See Plan of Borings
Project
Proposed Coppell City Hill Parkway Boulevard Coppell, Texas
Type
~ ~ ~ Intermittent Sampling
~ g . Surface Elevation o . = 'o ~ g .
~ = ~ ~ Unknown
~.~ STRATUM DESCRIPTION
10 Non,-?la ;tic
BROWN SAND
2.5 ' (
D~ BRO~ S~DY CLAY
13 120 6,020
~ (Yellowish bro~ sand and gravel
seams starting at 10.0') 11
16.0' (CL) 30 72 37~ 35
94 D~K G~Y S~E
25 50
~ 25.5'
- -,,
Completion Dopth Dato I Wator Obviations
25.5' 11-12-84~ Encountered at 10.0'
Maxim Englneem
Log of Boring INumberIL°cati°n
B-2 See Plan of Borings
Project
Pro. posed Coppell City Hall Parkway Boulevard Coppell, Texas
-- Type
i Intermittent Sampling
~ ~ . S,,rface Elevation O
i ~ 9 ~ g Unknown
~ .~ o STRATUM DESCRIPTION
~5 ]~3 2~580
BRO~ S~DY C~Y
2. ~' (C~)
11 122 22 15 7 4,570
5
D~K BRO~ SA~Y C~Y
13 117 3,060
(Gravel seams starting at 10.0')
15.0' (CL)
D~ G~Y S~E
72
~ 20
25 100~
'lb' 25.5' _ _
*THD Cone Penetration Test
I I
Completion Depth Date ~ Water Obviations
25.5' 11-12-84~ Encountered at 15.0'
Maxim Englneem
LogofBoringIB-3 IL°cati°n See Plan o:f Borings
Project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
~. Intermittent Sampling
~ ~ Surface Elevation & ¢ -";':'~ '~ ,-- '~ m
~ I~1~ ~ STRATUM DESCRiPTiON
~ - _ ,,~
Z6 ~8 30 ]5 Z5 8~000
~0~ S~D~ C~A~
2.5' (c~)
~ L2~ 6~460
s~e 8~a~e~
7.0' (C~)
13 118 1,670
15 18 15 3 26
~o
YELLOWISH BRO~ A~ G~Y C~YEY
S~D w~th some gravel 11 26 1~ 12 2~
~S .0' (SC)
D~ G~Y SH~EY
17.0~
93
9,~ DA~ G~Y SHOE
100·
6,~ 25.5~ _
Gomplotion ~pth D,to [ W~t~r
25.5~ 11-12-8~I Encountered at 20.0'
Maxim Englneer~
Log of Boring INumberIL°cati°n
B-4 See Plan of Borings
Project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
~ Intermittent Sampling
oU.E g o" Surface Elevation
& ~ ~ ._ o STRATUM DESCRIPTION
~ 15 114 29 16 13 2~850
BRO~ S~DY C~Y with yellowish
2.0' bro~ and red sand seams (CL)
D~ BRO~ SA~Y C~Y
14 117 3,800
~0.0' (c~)
10
BRO~ SA~ ~ G~VEL
~4.5' (s~)
18
G~Y SH~EY CLAY
18.5'
0
9~
10' 16
DA~ G~Y SHOE
~0~, ,,,
1" 25.5'
I
~ ~ *T~ Cone Penetration Test
Completion Depth Date ~ Water Obviations
25.5 ' 11-12-84~ None encountered
Maxim Englneem
Log of Boring INumber IL°cati°n
B-5 See Plan of Borings
Project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
Intermittent Sampling ~ ~ e~ c
~Eg' "' .... Surface Elevation O
lEI~~ ~'~--'
& ~ .- ~ STRATUM DESCRIPTION ;m~
YELLOWISH BRO~ S~Y C~Y 14 28 14 14 45
2.0 ' (CL)
BRO~ S~DY CLAY with some gravel
' 13 [17 4,280
5.0' (C~)
16 115 30 14 16
D~ BRO~ S~Y C~Y
10 '
15.0 ' (CL)
G~Y S~EY C~Y 30
17.0'
D~ G~Y S~E
~s ~ ~o~
25.5' __
~ [ *THD Cone Penetration Test I I
Completion ~pth Date ~ Water Obviations
~ 5' 11-12-84~ Encountered at 15.0'
Maxim Englneer~
Log of Boring INumber B-6 It°catl°n See Plan of BorinRs
Project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
Continuous Sam~lin~
~ STRATUM DESCRIPTION o
Z8 [t2 36 ~6 20 8~390,
2.0' (c[)
5.0' _ _ (sc)
Completion Depth Date ~ Water Obviations
Maxim Englneera
Log of Boring 1Number IL°cafl°n
B-7 See Plan of Borings
Project
Proposed Coppell City Hall Parkway Boulevard Coppell~ Texas
~ 3 ~ Continuous SamDlin~ ~ ~ ~
O0 ~ o
15 114
BROWN CLAYEY SAND with some
gravel 8 125 16 14 2
4.0' (sc)
~~ ~.0' ,A~_ B~O~ SA~Y C,.AY _ (CL)~V 11~ ~,~00
I
I I
Completion Depth Date I Water Observations
5.0' 11-12-841 None encountered
Maxim Engineers
Log of Boring INumber Location
B-8 I See Plan of Borings
Project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
~ ~. ContinUous Sampling.
. ~ ~g STRATUM DESCRIPTION
BRO~ C~YEY S~
s- 5.0' _
5.0 ' 11-12-8~~ None encountered
Maxim Engineers
Log of Boring [Number B-9 I L°cati°n See Plan of Borings
project
Proposed Coppell City Hall Parkway Boulevard Coppell, Texas
Type Continuous Sampling
~ sRo~ cL^~Y sm 11 122 10 is 4 3,870
... 4.0' (sc)
.5 ~ 5.0 ' BROWN SgaNDY CLAY (CL) 1 ?
Completion Depth Date ! Water Observations
I 11-12-84 None encountered
5.O'
Maxim Englneem
Symbols and Terms Used on Boring Logs
Soil or Rock Types Sampler Types
CLAY CLAYEY o e ' CONGLOMERATE Tube Core Spoon Auger Recoveq
Consistency of Cohesive Soils
DESCRIPTIVE TERM UNCONFINED COMPRESSIVE STRENGTH (TON/SQ. FOOT)
Very Soft Less than 0.25
Soft 0.25-0.50
Firm 0.50-1.00
Stiff 1.00-2.00
Very Stiff 2.00-4.00
Hard More than 4.00
Relative Density of Cohesionless Soils
STD. PENETRATION RESISTANCE BLOWS/FOOT DESCRIPTIVE TERM RELATIVE DENSITY
0-10 Loose 0 TO 40%
10-30 Medium Dense 40 TO 70%
30-50 Dense 70 TO 90%
OVER 50 Very Dense 90 TO 100%
Soil Structure
CALCAREOUS
SLICKENSlDED
LAMINATED
FISSURED
INTERBEDDED
Containing deposits of calcium carbonate: generally nodular
Having inclined planes of weakness that are slick and glossy in appearance.
Composed of thin layers of varying color and texture.
Containing shrinkage cracks frequently filled with fine sand or silt. Usually more or
less vertical.
Composed of alternate layers of different soil types.
Physical Properties of Rock
VERY SOFT OR PLASTIC
SOFT
MODERATELY HARD
HARD
VERY HARD
POORLY CEMENTED OR FRIABLE
CEMENTED
Hardness and Degree of Cementation
Can be remolded in hand: corresponds in consistency up to very stiff in soils.
Can be scratched with fingernail.
Can be scratched easily with knife: Cannot be scratched with fingernail.
Difficult to scratch with knife.
Cannot be scratched with knife.
Easily crumbled.
Bound together by chemically precipitated material occurring in the interstices between
allogenic particles of rock -- quartz, calcite, dolomite, siderite and iron oxide are common
cementing materials.
Physical Properties of Rock
UNWEATHERED
SLIGHTLY WEATHERED
WEATHERED
EXTREMELY WEATHERED
Degree of Weathering
Rock in its natural state before being exposed to atmospheric agents.
Noted predominantly by color change with no disintegrated zones.
Complete color change with zones of slightly decomposed rock.
Complete color change with consistency, texture, and general appearance approaching soil.
Maxim Engineers Inc.
SOIL CLASSIFICATION SYSTEM
SYM- TYPICAL NAMES
MAJOR DIVISIONS BOLS
GW Well graded gravels, gravel * sand mixtures,
little or no fines.
CLEAN
GRAVELS
GRAVELS (Little or no fines) GP Poorly graded gravels or gravel - sand
(More than 50% of mixtures, little or no fines.
coarse fraction is
LARGER than the
COARSE No. 4 sieve size) GRAVELS GM Silty gravels, gravel - sand - silt mixtures.
GRAINED WITH FINES
SO! LS (Appreciable amt.
(More than 50% of of fines) GC Clayey gravels, gravel - sand - clay mixtures.
material is
LARGER than Well graded sands, gravelly sands, little
No. 200 sieve SW or no fines.
size) CLEAN SANDS
(Little or no fines)
Poorly graded sands or gravelly sands,
SANDS SP little or no fines.
(More than 50% of
coarse fraction is
SMALLER than the
SM Silty sands, sand-silt mixtures.
No. 4 sieve size) SANDS
WITH FINES
(Appreciable amt.
of fines) SC Clayey sands, sand-clay mixtures.
Inorganic silts and very fine sands, rock flour,
U L silty or clayey fine sands or clayey silts with
slight plasticity.
Inorganic clays of iow to medium plasticity,
SILTS AND CLAYS CE gravelly clays, sandy clays, silty clays,
FINE (Liquid limit LESS than 50) lean clays.
GRAINED
SOl LS
(More than 50% of OL Organic silts and organic silty clays of
Iow plasticity.
material is
SMALLER than
No. 200 sieve MH Inorganic silts, micaceous or diatomaceous
fine sandy or silty soils, elastic silts.
size)
SILTS AND CLAYS
(Liquid limit GREATER than 50) CH Inorganic clays of high plasticity, fat clays.
OH Organic clays of medium to high plasticity,
organic silts.
HIGHLY ORGANIC SOl LS PT Peat and other highly organic soils.
BOUNDARY CLASSIFICATIONS: Soils possessing characteristics of two groups are designated by
combinations of group symbols.
Maxim Engineers Inc.