ST9902-LR131121f
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C13 -0634
Date Sampled: 11/14/2013
Report Date: 11/22/2013 Previously Reported: 11/21/2013
Sampled By: Roberts, Duce
Project: West Sandy Lake Road
By Order Of:
Location: Various Locations
Order Number: 1770
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH
TEST LAB NO: 154540
Test Method: See Below
TEST RESULTS Report No: 154540
Page 1 of 2
Set: 1 of 2 Material: Concrete
Number of Specimens: 4
Location: Standard 20ft Curb Inlet at Station 1 +20.01 Lat F -13
Maximum Compressive Average
Spec Age Tested Diameter Area Load Cure
Strength Strength Tested
Nbr (date : days) (in) (in 2) (Ibs) Break Type Loc
(PSI) (PSI) By Comments
A 11/21/13: 7 6.00 28.27 90,650 Type 3 Lab
3,210 3,210
B 12/12/13:28 6.00 28.27 Lab
C 12/12/13:28 6.00 28.27 Lab
D
HOLD (see remarks) -
Type 1 Type 2 Type 3 Type 4
Type 5 Type 6
Specification
Strength: 3,000 psi @ 28 days
Slump: 1 -3 Slump: 2.0 Inches
Transported By: LMC
Air Content: 3 -6 Air Content: 5.4%
Source /Sampled At: Truck / Center
Mix Code:
Plant:
Date Received: 11/15/2013
Truck /Ticket No:
Curing Method: Standard
Time Sampled: 1:40 pm
Time Batched: 12:26 pm
Temp.: Ambient: 54 °F Mix: 65 °F
Quantity Represented: 5 cu. yds. at 5 cu. yds. placed of a 5 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or
C173, C1064 and C138. Compressive strength tests per ASTM C39.
Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy)
Orig: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
IIN�AIq I
Acct ID: 1770 File No: C13 -0634
Date Sampled: 11/14/2013
Report Date: 11/22/2013 Previously Reported: 11/21/2013
Sampled By: Roberts, Duce
Project: West Sandy Lake Road
By Order Of:
Location: Various Locations
Order Number: 1770
Client: City of Coppell
REPORT. REPORT OF CONCRETE COMPRESSIVE STRENGTH
TEST LAB NO: 154540
Test Method: See Below
TEST RESULTS Report No: 154540
Page 2 of 2
Set: 2 of 2 Material: Concrete
Number of Specimens: 5
Location: Transverse Section Sleeper Slab West Side of Bridge
Maximum Compressive Average
Spec Age Tested Diameter Area Load Cure
Strength Strength Tested
Nbr (date : days) (in) (in 2) (Ibs) Break Type Loc
(PSI) (PSI) By Comments
A 11/18/13: 4 6.00 28.27 107,055 Type 3 Lab
3,790 3,790
B 11/21/13: 7 6.00 28.27 113,270 Type 3 Lab
4,010 4,010
C 12/12/13:28 6.00 28.27 Lab
D 12/12/13:28 6.00 28.27 Lab
E
HOLD (see remarks) -
HE- R1 M Mu E
FIFI, 1-1
Type 1 Type 2 Type 3 Type 4
Type 5 Type 6
Specification
Strength: 4,000 psi @ 28 days
Slump: 3 -5 Slump: 3.25 Inches
Transported By: LMC
Air Content: 3 -6 Air Content: 7.5%
Source /Sampled At: Truck / Center
Mix Code: 1261
Plant: 952
Date Received: 11/15/2013
Truck /Ticket No: 3029 / 62956455
Curing Method: Standard
Time Sampled: 3:10 pm
Time Batched: 2:15 pm
Temp.: Ambient: 56 °F Mix: 65 °F
Quantity Represented: 7 cu. yds. at 7 cu. yds. placed of a 7 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or
C173, C1064 and C138. Compressive strength tests per ASTM C39.
Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy)
Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
Respectfully Submitted,
Alliance Geotechnical Group
. � . -.
Perry C. Kakara, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENT AND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
e
Acct ID: 1770 File No: C13 -0634
Date Sampled: 10/24/2013
Report Date: 11/22/2013 Previously Reported: 10/25/2013
Sampled By: Hernandez, Caleb
Project: West Sandy Lake Road
By Order Of:
Location: Various Locations
Order Number: 1770
Client: City of Coppell
REPORT. REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
LAB NO: 153739
Test Method: See Below
TEST RESULTS
Report No: 153739
Page 1 of 2
Set: 1 of 2 Material: Concrete
Number of Specimens: 4
Location: Inlet and Inlet Top of Lat F2A; Sampled Inlet Lat 7AI Line F on Southeast Corner of Intersection East of Whispering Hill
Maximum Compressive
Average
Spec Age Tested Diameter Area Load Cure Strength
Strength Tested
Nbr (date : days) (in) (in 2) (Ibs) Break Type Loc (PSI)
(PSI) By Comments
A 10/31/13: 7 6.00 28.27 76,775 Type 3 Lab 2,720
2,720
B 11/21/13: 28 6.00 28.27 105,885 Type 3 Lab 3,740
C 11/21/13: 28 6.00 28.27 103,960 Type 3 Lab 3,680
3,710
D
HOLD (see remarks) -
Type 1
Specification
Strength: 3,600 psi @ 28 days
Slump: 3 -5
Air Content: 3 -6
Date Received: 10/25/2013
Curing Method: Standard
Time Sampled: 3:00 pm
Time Batched: 1:49 pm
Temp.: Ambient: 81'F Mix: 82 °F
�! F -1
Type 2 Type 3 Type 4
Slump: 4.0 Inch
Air Content: 5.0%
Mix Code: 1261
F11 11
Type 5 Type 6
CONFORMS
as Transported By: LMC
Source /Sampled At: Truck / Center
Plant: 952
Truck /Ticket No: 9102 / 62955761
Quantity Represented: 6 cu. yds. at 6 cu. yds. placed of a 6 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or
. C173, C1064 and C138. Compressive strength tests per ASTM C39.
Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy)
Orig: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
Respectfully Submitted,
Alliance Geotechnical `Group
Perry C. Kakara, CME Department Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.
MLIfCE
W-07' ICflL
CROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C13 -0634
Date Sampled: 10/24/2013
Report Date: 11/22/2013 Previously Reported: 10/25/2013
Sampled By: Hernandez, Caleb
Project: West Sandy Lake Road
By Order Of:
Location: Various Locations
Order Number: 1770
Client: City of Coppell
REPORT: REPORT OF CONCRETE COMPRESSIVE STRENGTH
TEST LAB NO: 153739
Test Method: See Below
TEST RESULTS Report No: 153739
Page 2 of 2
Set: 2 of 2 Material: Concrete
Number of Specimens: 5
Location: Junction Box Top (Box Culvert Line F and Line G); Sampled Station 1 +00 on West Sandy Lake Rd, Junction Box Top
Maximum Compressive Average
Spec Age Tested Diameter Area Load Cure
Strength Strength Tested
Nbr (date : days) (in) (in 2) (Ibs) Break Type Loc
(PSI) (PSI) By Comments
A 10/27/13: 3 6.00 28.27 110,630 Type 3 Lab
3,910 3,910
B 10/31/13: 7 6.00 28.27 118,010 Type 3 Lab
4,170 4,170
C 11/21/13: 28 6.00 28.27 140,940 Type 3 Lab
4,980
D 11/21/13: 28 6.00 28.27 139,310 Type 3 Lab
4,930 4,960
E
HOLD (see remarks) -
ff
.............. E ... S_ �.....�.� ..�. �_ ..{,�': I .., l \...
[1]
Type 1 Type 2 Type 3 Type 4
Type 5 Type 6
Specification
CONFORMS
Strength: 3,600 psi @ 28 days
Slump: 3 -5 Slump: 5.0 Inches
Transported By: Southern Star
Air Content: 3 -6 Air Content: 3.5%
Source /Sampled At: Truck / Center
Mix Code: 1083
Plant: 110
Date Received: 10/25/2013
Truck/Ticket No: 3555 / 1314042
Curing Method: Standard
Time Sampled: 4:10 pm
Time Batched: 3:25 pm
Temp.: Ambient: 81 °F Mix: 82 °F
Quantity Represented: 10 cu. yds. at 10 cu. yds. placed of a 10 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or
C173, C1064 and C138. Compressive strength tests perASTM C39.
Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy)
Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, CME Department Manager
THIS REPORTAPPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENTAN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.