Loading...
CF-Cozby Library-LR 940520 (10) REPORT OF IN-PLACE DENSITY AND MOISTURE OF SOIL Method: ASTM D2922 D3017 D698 Page 1 of 2 Client: City of Coppell M~terial Description Maximum Optimum Dry Moisture Densi~' Content Project: W.T. Cozby Library (Lbs/CuFf) Percent Test Date: April 8, 1994 1. Select Fill: Reddish Bro~ Clayey Sand 112.5 13.2 Report Date: May 20, 1994 2. Required Density (%): 95% to 105% 3. Required Moisture (%): _+3% Optimum 4. Mat Location/Elevation (and/or) Lift In-Place In-Place Percent No. Dr)' Density Moisture Compaction Test No. (Lbs/CuF0 Content (~) Probe. Depth 1 Building Pad Select Fill - 3rd Lift 46 116.8 12.8 103.8 BS 15' east and 27' north of southwest corner 1 Building Pad Select Fill - 3rd Lift 47 112.7 14.1 100.2 6" 60' north and 51' east of southwest comer 1 Building Pad Select Fill - 3~ Lift 48 112.6 12.4 100.1 BS 24' south and 12' east of northwest corner Above Test Results Meet Specification Requirements cc: Gary Sieb - City of Coppell Mike Sherpinskas - Diversified Construction Services, Inc. Jim Bullock - F & S Partners Robert Williams - Brockette Davis Drake, Inc.