ST9902-LR140103flLL.If�YCE
C`CE-CHfiICRL
GROUP
Consulting Engineering * Geotechnical Engineering * Construction Materials
3228 Halifax Street, Suite A, Dallas, Texas 75247
Phone: (972) 444 -8889 Fax: (972) 444 -8893
Acct ID: 1770 File No: C13 -0634
Date Sampled: 12/31/2013
Report Date: 01/02/2014
Sampled By: Gatton, Tim
Project: West Sandy Lake Road
By Order Of: Walter
Location: Box Culvert eastbound Sandy Lake Rd., Sampled: 150' East of
Order Number: 1770
entrance to Verizon x 40' south of Sandy Lake Rd.
Number of
Client: City of Coppell
Specimens: 5
REPORT. REPORT OF CONCRETE COMPRESSIVE STRENGTH TEST
LAB NO: 156065
Material: Concrete
Test Method: See Below
TEST RESULTS
Report No: 156065
Page 1 of 1
Maximum Compressive
Average
Spec Age Tested Diameter Area Load Cure Strength
Strength Tested
Nbr (date : days) (in) (in 2) (lbs) Break Type Loc (PSI)
(PSI) By Comments
A 01/03/14: 3 6.00 28.27 88,115 Type 5 Lab 3,120
3,120
B 01/07/14:7 6.00 28.27 Lab
C 01/07/14:7 6.00 28.27 Lab
D 01/28/14:28 6.00 28.27 Lab
E 01/28/14:28 6.00 28.27 Lab
RK
Type 1 Type 2 Type 3 Type 4 Type 5 Type 6
Specification
Strength: 4,000 psi @ 28 days
Slump: 3 -5
Air Content: 4 -6
Date Received: 01/02/2014
Curing Method: Standard
Time Sampled: 3:04 pm
Time Batched: 1:50 pm
Temp.: Ambient: 51 °F Mix: 62 °F
Slump: 3.25 Inches
Air Content: 4.4%
Mix Code: 1083
Transported By: Argos
Source /Sampled At: Truck / Center
Plant: 110
Truck/Ticket No: 5012 / 1341842
Quantity Represented: 6 cu. yds. at 6 cu. yds. placed of a 6 cu. yd. total placement
Remarks:
Test Method (As Applicable): Unless noted, concrete was sampled and tested in accordance with ASTM C31, C172, C143, C231 or
C173, C1064 and C138. Compressive strength tests per ASTM C39.
Client: City of Coppell Attn: Mr. Rick O'Dell (1 -cc copy)
Ong: City of Coppell (Coppell, TX) Attn: Mr. Keith Marvin, P.E.
Respectfully Submitted,
Alliance Geotechnical Group
Perry C. Kakara, CME Department Manager
THIS REPORT APPLIES ONLY TO THE STANDARDS OR PROCEDURES INDICATED AND TO THE SAMPLE(S) TESTED AND /OR OBSERVED AND ARE NOT NECESSARILY INDICATIVE OF
THE QUALITIES OF APPARENTLY IDENTICAL OR SIMILAR PRODUCTS OR PROCEDURES, NOR DO THEY REPRESENT AN ONGOING QUALITY ASSURANCE PROGRAM UNLESS SO
NOTED. THESE REPORTS ARE FOR THE EXCLUSIVE USE OF THE ADDRESSED CLIENTAND ARE NOT TO BE REPRODUCED WITHOUT WRITTEN PERMISSION.