Gateway BP(2.5)-CS140109January 9, 2014 PK No.: 2768 - 13.062 Mr. Michael Garza, P.E. CITY OF COPPELL 255 Parkway Boulevard Coppell, Texas 75019 Re: BMSC /NATERRA CORPORATE HEADQUARTERS Lot 1, Block B, Gateway Business Park 2 Coppell, Texas Dear Mr. Garza: Naterra /BMSC Corporate Headquarters was designed to be served by a 6 inch sanitary sewer service. This sanitary sewer service was designed at a 0.5 percent slope which has the capacity to handle 232 gpm at a velocity of 2.63 feet per second. The proposed building will have two different sanitary discharges which we have classified as process waste and domestic waste. The domestic waste discharge for the project is 122 gpm based upon 100% usage calculations from Howard Kane Plumbing. The process waste will be discharged into a DAF pretreatment system which has been designed to have a release rate of 40 gpm based upon information received from BMSC /Naterra. The total proposed release rate for the building is 162 gpm which leaves a factor of safety of 70 gpm in the system. Based upon this information, the proposed service has sufficient capacity of the development. Sincerely, M Clayton J. Strolle, P.E., LEEDOAP BD +C CJS /alm 2768- 13.062_SanitaryLetter 8350 N Central E)epwy SuHe 1000 il, Ddlas, FX 75206 1 612 - : 972,235.3031 - F. 971235.9544 okc ie.c orn