Coppell BC3-LR001220IN-PLACE DENSITY STING · Date of Service: Client No.: Client: 11/2012000 1332 Constructors & Associates Attn: Mike Donnelly 3333 Welborn St Suite 200 Dallas TX 75219 Report No.: 0030307 Project No.: 94.001487 Project: Charles Schwab 217 Wrangler Coppell, Texas a aivision of'ffmmczn 8901 Carpenter Frwy., Suite #100 Dallas, Texas 75247 Report Date 12/20/2000 Services: In-place density testing. CONTRACTOR: Constructors & Assoc. PROJECT DATA Laboratory Test Method: ASTM D-698 MOISTURE DENSITY RELATIONS: M/D No. Description 1 Reddish brown clayey sand Field Test Method: ASTM D2922 ASTM D3017 Maximum Project Requirements Moisture % Density pcf Moisture Density 13.0 114.5 -2/+2% 95 % FIELD DENSITY TESTS TEST NO TEST LOCATION PROBE LIFT/ M/D MOISTURE DRY DENSITY DEPTH ELEV No. (%) (pcf) 1 Room #103-C 2 Room #104 3 Room#101-C 4 Room #103-A 5 Room #102 6" at Grade 1 11.4 110.2 6" at Grade 1 12.8 109.3 6" at Grade 1 11.0 110.4 6" at Grade 1 13.1 108.9 6" at Grade 1 11.7 111.7 Test results on this report meet project specification. DENSITY (% max) 96 96 96 95 98 Technician: Phil Green Report Distribution: (I) Conslructors & Associates (I) City of Coppell - Constr. Iusp. (I) City of Coppell - Bldg. Insp. Started: 3:00p Finished: 4:30p ng, Inc. Eric J. Cleveland, P.E. Senior Project Engineer This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of HBC Engineering, Inc. 07SDS Page 1 of 1